Home » Generation Transmission and Distribution » Power System MCQs with Explanatory Answers

Power System MCQs with Explanatory Answers

Power System MCQs with Explanatory Answers

(Generation, Transmission and Distribution  MCQs with Explanatory Answers )
1.
Volume of The Conductor is inversely proportional to the ____________.

  1. Voltage (V)
  2. Half of the Voltage (½ V)
  3. Squire of the Voltage (V2)
  4. None of the above

Show Explanatory Answer

Show Explanatory Answer

Answer:     3     Squire of the Voltage (V2)
Explanation: 
Power in Three Phase Circuits    P = √3 V I Cosθ   OR     I = P / √3 V Cos θ        (1)
Law’s of resistance =                 R = ρ (l /A)                                                    (2)
Power Loss in Three Phase Circuits = P = 3 I2R                                                      (3)
Putting the Values of I and R from Equation (1) and (2) into Equation (3).
P = 3 (P / √3 V Cos θ)2 x [ρ (l /A)]
P = 3 (P2/3 V2 Cos2 θ) x ρ (l /A)        
P = W = P2 ρ l/ V Cos2 θ A… OR … A = P2 ρ l/ V2 Cos2 θ W                              (4)
Volumeof the conductor in Three Phase System= Vol = 3A x Length              (5)
Putting the value of “A” from Equation (4) into Equation (5)
Vol = 3 P2 ρ l/ W V2 Cos2 θ x l 
Vol = 3 P2 ρ l2/ W V2 Cos2 θ 
Hence Proved that Volume of the Conductor is inversely proportional to squire of Voltage
Volume of the Conductor = Vol   ∞ 1/V2

From Schematic Drawing to PCB Production, Just Need One Tool
Cheap PCB Prototype: 10 pcs 2 layers only $10, quick delivery, 100% E-test.

About Electrical Technology

All about Electrical & Electronics Engineering & Technology. Follow , Facebook , Twitter , Instagram , Pinterest & Linkedin to get the latest updates or subscribe Here to get latest Engineering Articles in your mailbox. Also, Follow

Check Also

Integration of Renewable Energy with Grid System

Integration of Renewable Energy with Grid System

Integration of Renewable Energy with Grid System Types of energy which exist infinitely and never …

3 comments

  1. Dear If we will put the value of equation (4) into (5) there should be Length^2 even there is no change in the result as this A = P2 ρ l/ V2 Cos2 θ W (4)<br />Volume of the conductor in Three Phase System= Vol = 3A x Length <br /><br />Vol = 3 P2 ρ l^2/ W V2 Cos2 θ

  2. keep it up!

Leave a Reply

Your email address will not be published. Required fields are marked *