Breaking News
Home » Basic Electrical Fundamentals » Earthing and Electrical Grounding Installation | A Complete Guide

Earthing and Electrical Grounding Installation | A Complete Guide

Earthing and Types of Electrical Earthing | Electrical Grounding Installation (Step by Step)

Earthing, Grounding, Methods Of Earthing, Types of Earthing And Is Specifications In Respect To Earthing Of Electrical Installations

Keep In mind:

We have to updated this post with different and useful articles related to Earthing & Grounding.

Please Subscribe to Electrical Technology Blog by Email and don’t miss even a single post about the story. OR just see the last paragraph of the article. Thanks

Happy learning 🙂

What is Grounding or Earthing?

To connect the metallic (conductive) Parts of an Electric appliance or installations to the earth (ground) is called Earthing or Grounding.

In other words, to connect the metallic parts of electric machinery and devices to the earth plate or earth electrode (which is buried in the moisture earth) through a thick conductor wire (which has very low resistance) for safety purpose is known as Earthing or grounding.

To earth or earthing rather, means to connect the part of electrical apparatus such as metallic covering of metals, earth terminal of socket cables, stay wires that do not carry current to the earth. Earthing can be said as the connection of the neutral point of a power supply system to the earth so as to avoid or minimize danger during discharge of electrical energy.Earthing, Grounding, Bonding, Types of Earthing, Grounding Installation

 

Good to know

Difference between Earthing, Grounding and Bonding.

Let me clear the confusion among earhing, grounding and bonding.

Earthing and Grounding is the same terms used for earthing. Grounding is the commonly word used for earthing in the North American standards like IEEE, NEC, ANSI and UL etc while, Earthing is used in European, Common wealth countries and Britain standards like IS and IEC etc.

The word Bonding used for jointing two wires (as well as conductors, pipes or appliances together. Bonding is known as connecting the metallic parts of different machines which is not considered to be carrying electric current during normal operation of the machines to bring them at the same level of electric potential.

Need of Earthing or Grounding. Why Earthing is Important?

The primary purpose of earthing is to avoid or minimize the danger of electrocution, fire due to earth leakage of current through undesired path and to ensure that the potential of a current carrying conductor does not rise with respect to the earth than its designed insulation.

When the metallic part of electrical appliances (parts that can conduct or allow passage of electric current) comes in contact with a live wire, maybe due to failure of installations or failure in cable insulation, the metal become charged and static charge accumulates on it. If a person touches such a charged metal, the result is a severe shock.

To avoid such instances, the power supply systems and parts of appliances have to be earthed so as to transfer the charge directly to the earth.

Below are the basic needs of Earthing.

  • To protect human lives as well as provide safety to electrical devices and appliances from leakage current.
  • To keep voltage as constant in the healthy phase (If fault occurs on any one phase).
  • To Protect Electric system and buildings form lighting.
  • To serve as a return conductor in electric traction system and communication.
  • To avoid the risk of fire in electrical installation systems.

Different Terms used in Electrical Earthing

  • Earth: The proper connection between electrical installation systems via conductor to the buried plate in the earth is known as Earth.
  • Earthed: When an electrical device, appliance or wiring system connected to the earth through earth electrode, it is known as earthed device or simple “Earthed”.
  • Solidly Earthed: When an electric device, appliance or electrical installation is connected to the earth electrode without a fuse, circuit breaker or resistance/Impedance, It is called “solidly earthed”.
  • Earth Electrode: When a conductor (or conductive plate) buried in the earth for electrical earthing system. It is known to be Earth Electrode. Earth electrodes are in different shapes like, conductive plate, conductive rod, metal water pipe or any other conductor with low resistance.
  • Earthing Lead: The conductor wire or conductive strip connected between Earth electrode and Electrical installation system and devices in called Earthing lead.
  • Earth Continuity Conductor: The conductor wire, which is connected among different electrical devices and appliances like, distribution board, different plugs and appliances etc. in other words, the wire between earthing lead and electrical device or appliance is called earth continuity conductor. It may be in the shape of metal pipe (fully or partial), or cable metallic sheath or flexible wire.
  • Sub Main Earthing Conductor: A wire connected between switch board and distribution board i.e. that conductor is related to sub main circuits.
  • Earth Resistance: This is the total resistance between earth electrode and earth in Ω (Ohms). Earth resistance is the algebraic sum of the resistances of earth continuity conductor, earthing lead, earth electrode and earth.

POINTS TO BE EARTHED

     Earthing is not done anyhow. According to IE rules and IEE (Institute of Electrical Engineers) regulations,

  • Earth pin of 3-pin lighting plug sockets and 4-pin power plug should be efficiently and permanently earthed.
  • All metal casing or metallic coverings containing or protecting any electric supply line or apparatus such as GI pipes and conduits enclosing VIR or PVC cables, iron clad switches, iron clad distribution fuse boards etc should be earthed (connected to earth).
  • The frame of every generator, stationary motors and metallic parts of all transformers used for controlling energy should be earthed by two separate and yet distinct connections with the earth.
  • In a dc 3-wire system, the middle conductors should be earthed at the generating station.
  • Stay wires that are for overhead lines should be connected to earth by connecting at least one strand to the earth wires.

Components of Earthing System

A complete electrical earthing system consists on the following basic components.

  • Earth Continuity Conductor
  • Earthing Lead
  • Earth Electrode
Components of Earthing System. A Complete Electrical Grounding System
Components of Electrical Earthing System

 Earth Continuity Conductor or Earth Wire

That part of the earthing system which interconnects the overall metallic parts of electrical installation e.g. conduit, ducts, boxes, metallic shells of the switches, distribution boards, Switches, fuses, Regulating and controlling devices, metallic parts of electrical machines such as, motors, generators, transformers and the metallic framework where electrical devices and components are installed is known as earth wire or earth continuity conductor as shown in the above fig.

The resistance of the earth continuity conductor is very low. According to IEEE rules, resistance between consumer earth terminal and earth Continuity conductor (at the end) should not be increased than 1Ω. In simple words, resistance of earth wire should be less than 1Ω.

Size of the Earth Continuity Conductor or Earth Wire depends on the cable size used in the wiring circuit.

Size of Earth Continuity Conductor

The cross sectional area of the Earth Continuity Conductor should not be less than the half of the cross sectional area of the thickest wire used in the electrical wiring installation.

Generally, the size of the bare copper wire used as earth continuity conductor is 3SWG. But keep in mind that, don’t use less than 14SWG as earth wire. Copper strip is also can be used as earth continuity conductor instead of bare copper wire but don’t go for it until manufacture recommend it.

Earthing Lead or Earthing Joint

The conductor wire connected between earth continuity conductor and earth electrode or earth plate is called earthing joint or “Earthing lead”. The point where earth continuity conductor and earth electrode meet is known as “connecting point” as shown in the above fig.

Earthing lead is the final part of the earthing system which is connected to the earth electrode (which is underground) through earth connecting point.

There should be minimum joints in earthing lead as well as lower in size and straight in the direction.

Generally, copper wire can be used as earthing lead but, copper strip is also used for high installation and it can handle the high fault current because of wider area than the copper wire.

A hard drawn bare copper wire is also used as an earthing lead. In this method, all earth conductors connected to a common (one or more) connecting points and then, earthing lead is used to connect earth electrode (earth plat) to the connecting point.

To increase the safety factor of installation, two copper wires are used as earthing lead to connect the device metallic body to the earth electrode or earth plate. I.e. if we use two earth electrodes or earth plats, there would be four earthing leads. It should not be considered that the two earth leads are used as parallel paths to flow the fault currents but both paths should work properly to carry the fault current because it is important for better safety.Motor Earthing. Motor Grounding

Size of the Earthing Lead

The size or area of earthing lead should not be less than the half of the thickest wire used in the installation.

The largest size for earthing lead is 3SWG and the minimum size should not be less than 8SWG. If 37/.083 wire is used or the load current is 200A from the supply voltage, then it is recommended to use copper strip instead of double earthing lead. The earth lead connection methods is shown in the above fig.

Note: We will post additional article about Earth Plate size with simple calculations… Stay tune.

Earthing Electrode or Earth Plate

A metallic electrode or plate which is buried in the earth (underground) and it is the last part of the electrical earthing system. In simple words, the final underground metallic (plate) part of the earthing system which is connected with earthing lead is called earth plate or earth electrode.

A metallic plate, pipe or rode can be used as an earth electrode which has very low resistance and carry the fault current safely towards ground (earth).Jointing Copper Wire Earthing Leads to Earth Plate & Wrong & right ways for Earthing Lead InstallationSize of Earthing Electrode

Both copper and iron can be used as earthing electrode.

The size of earth electrode (In case of copper)

2×2 (two foot wide as well as in length) and 1/8 inch thickness.. I.e. 2’ x 2’ x 1/8”. (600x600x300 mm)

In case of Iron

2’ x2’ x ¼” = 600x600x6 mm

It is recommended to bury the earth electrode in the moisture earth. If it is not possible, then put water in the GI (Galvanized Iron) pipe to make possible the moisture condition.

In the earthing system, put the earth electrode in vertical position (underground) as shown in the above fig. Also, put a 1 foot (about 30cm) layer of powdered charcoal and lime mixture around the earth plate (don’t confuse with earth electrode and earth plate as both are the same thing).

This action makes the possible increase in the size of the earth electrode which leads a better continuity in the earth (earthing system) and also helps to maintain the moisture condition around earth plate.

P.S: We will post Example calculation about Earth Electrode Sizing… Stay tune.

Good to know:

Don’t use coke (after burning coal in the furnace to emit all the gases and other components, the remaining 88% carbon is called coke) or stone coal instead of charcoal (wood coal) because it causes to corrosion in the earth plate.

Since, the water level is different in the different areas; therefore, the depth for earth electrode installation is also different in various areas. But, the depth for earth electrode installation should not be less than 10ft (3 meter) and should below 1 foot (304.8mm) from the constant water level.

Motors, Generator, Transformers etc should be connected from to earth electrode two different places.

Earth Plate or Earth Electrode Size for Small installation

In small installation, use metallic rod (diameter = 25mm (1inch) and length = 2m (6ft) instead of earth plate for earthing system. The metallic pipe should be 2 meter below from the surface of ground. To maintain the moister condition, put 25mm (1inch) coal and lime mixture around the earth plate.

For effectiveness and convenience, you may use the copper rods 12.5mm (0.5 inch) to 25mm (1 inch) diameter and 4m (12ft) length. We will discuss the installation method of rod earthing latter.

Methods of Earthing | Types of Earthing

Earthing can be done in many ways. The various methods employed in earthing (in house wiring or factory and other connected electrical equipment and machines) are discussed as follows:

1). Plate Earthing:

In plate earthing system, a plate made up of either copper with dimensions 60cm x 60cm x 3.18mm (i.e. 2ft x 2ft x 1/8 in) or galvanized iron (GI) of dimensions 60cm x 60cm x 6.35 mm (2ft x 2ft x ¼ in) is buried vertical in the earth (earth pit) which should not be less than 3m (10ft) from the ground level.

For proper earthing system, follow the above mentioned steps in the (Earth Plate introduction) to maintain the moisture condition around the earth electrode or earth plate.plate earthing, plate grounding

2). Pipe Earthing:

A galvanized steel and a perforated pipe of approved length and diameter is placed vertically in a wet soil in this kind of system of earthing. It is the most common system of earthing.

The size of pipe to use depends on the magnitude of current and the type of soil. The dimension of the pipe is usually 40mm (1.5in) in diameter and 2.75m (9ft) in length for ordinary soil or greater for dry and rocky soil. The moisture of the soil will determine the length of the pipe to be buried but usually it should be 4.75m (15.5ft).Pipe Earthing and Grounding

3). Rod Earthing

 it is the same method as pipe earthing. A copper rod of 12.5mm (1/2 inch) diameter or 16mm (0.6in) diameter of galvanized steel or hollow section 25mm (1inch) of GI pipe of length above 2.5m (8.2 ft) are buried upright in the earth manually or with the help of a pneumatic hammer. The length of embedded electrodes in the soil reduces earth resistance to a desired value.

Copper Rod Electrode Earthing System
Copper Rod Electrode Earthing System

 

4). Earthing through the Waterman

In this method of earthing, the waterman (Galvanized GI) pipes are used for earthing purpose. Make sure to check the resistance of GI pipes and use earthing clamps to minimize the resistance for proper earthing connection.

If stranded conductor is used as earth wire, then clean the end of the strands of the wire and make sure it is in the straight and parallel position which is possible then to connect tightly to the waterman pipe.

5). Strip or Wire Earthing:

In this method of earthing, strip electrodes of cross-section not less than 25mm x 1.6mm (1in x 0.06in) is buried in a horizontal trenches of a minimum depth of 0.5m. If copper with a cross-section of 25mm x 4mm (1in x 0.15in) is used and a dimension of 3.0mm2 if it’s a galvanized iron or steel.

If at all round conductors are used, their cross-section area should not be too small, say less than 6.0mm2 if it’s a galvanized iron or steel. The length of the conductor buried in the ground would give a sufficient earth resistance and this length should not be less than 15m.

General method of Earthing / Proper Grounding Installation (Step by Step)

The usual method of earthing of electric equipments, devices and appliances are as follow:

  1. First of all, dig a 5x5ft (1.5×1.5m) pit about 20-30ft (6-9 meters) in the ground. (Note that, depth and width depends on the nature and structure of the ground)
  2. Bury an appropriate (usually 2’ x 2’ x 1/8” (600x600x300 mm) copper plate in that pit in vertical position.
  3. Tight earth lead through nut bolts from two different places on earth plate.
  4. Use two earth leads with each earth plate (in case of two earth plates) and tight them.
  5. To protect the joints from corrosion, put grease around it.
  6. Collect all the wires in a metallic pipe from the earth electrode(s). Make sure the pipe is 1ft (30cm) above the surface of the ground.
  7. To maintain the moisture condition around the earth plate, put a 1ft (30cm) layer of powdered charcoal (powdered wood coal) and lime mixture around the earth plate of around the earth plate.
  8. Use thimble and nut bolts to connect tightly wires to the bed plates of machines. Each machine should be earthed from two different places. The minimum distance between two earth electrodes should be 10 ft (3m).
  9. Earth continuity conductor which is connected to the body and metallic parts of all installation should be tightly connected to earth lead.
  10. At last (but not least), test the overall earthing system through earth tester. If everything is going about the planning, then fill the pit with soil. The maximum allowable resistance for earthing is 1Ω. If it is more than 1 ohm, then increase the size (not length) of earth lead and earth continuity conductors. Keep the external ends of the pipes open and put the water time to time to maintain the moisture condition around the earth electrode which is important for the better earthing system.

SI specification for Earthing

Various specifications in respect to earthing as recommended by Indian Standards are given below. Here are few;

  • An earthing electrode should not be situated (installed) close to the building whose installation system is being earthed at least more than 1.5m away.
  • The earth resistance should be low enough to cause the flow of current sufficient to operate the protective relays or blow fuses. It’s value is not constant as it varies with weather because it depends on moisture (but should not be less than 1 Ohm).
  • The earth wire and earth electrode will be the same material.
  • The earthing electrode should always be placed in a vertical position inside the earth or pit so that it may be in contact with all the different earth layers.

Dangers Of Not Earthing A Supply System

As emphasized on earlier, earthing is provided in order

  • To avoid electric shock
  • To avoid risk of fire as a result of earth leakage current through unwanted path and
  • To ensure that no current carrying conductor rises to a potential with respect to general mass of earth than its designed insulation.

However, if excessive current is not earthed, appliances will be damaged without the help of fuse in place. You should note that excessive current are earthed at their generating stations which is why earth wires carries very little or no current at all. It therefore implies that it is not necessary to earth any of the wires (live, earth and neutral wires) contained in a PVC. Earthing the live wire is catastrophic.

I have seen a person killed simply because a live wire got cut from overhead pole and fell to the ground while the ground was wet. Excessive current is earthed at generating stations and if at all the earthing is not efficient due to fault, earth fault interrupters will be there to help. Fuse help only when the power transmitted is above the rating of our appliances, it blocks the current from reaching our appliances by blowing off and protecting our appliances in the process.

In our electrical appliances, if excessive currents are not earthed, we would experience severe shock. Earthing takes place in electrical appliances only when there is a problem and it is to save us from danger. If in an electronic installation, a metallic part of an electrical appliance comes in direct contact with a live wire that results from maybe failure of installation or otherwise, the metal will be charged and static charge will accumulate on it.

If you happen to touch the metallic part at that moment you will be zapped. But if the metallic part of the appliance is earthed, the charge will be transferred to earth instead of accumulating on the metallic part of the appliance. Current don’t flow through earth wires in electrical appliances, it does so only when there is problem and only to direct the unwanted current to earth in order to protect us from severe shock.

In addition, if a live wire touches accidentally (in a faulty system) to the metallic part of a machine. Now, if a man touches that metallic part of the machine, then the current will flow through their body to the ground, hence, he will get shocked (electrocuted) which may lead to serious injuries even to death. That’s why earthing is so important?

Electrical Grounding & Earthing….. To be continued…

Please subscribe below, if you want to get the upcoming post about Earthing/Grounding such as:

  • Calculate the size of Earth Continuity Conductor, Earthing Lead & Earth Electrodes for differnt electrical devices and equipment such motors, transformers, home wiring etc by Simple calculations
  • Earthing Circuit and Earth Fault Current
  • Protection of Earthing System and Additional devices used in the Earthing / Grounding System
  • Points To remember while Providing Grounding / Earthing
  • Important Instruction for Proper earthing system
  • Electricity rules about Earthing
  • How to Test Earth Resistance by Earth Tester
  • How to test Earth loop Resistance by Am-Meter & Voltmeter
  • Protective Multiple Earthing
  • And much more….
Enter your Email for Latest Updates like the above one!
Enter your email address:

From Schematic Drawing to PCB Production, Just Need One Tool
Cheap PCB Prototype: 10 pcs 2 layers only $10, quick delivery, 100% E-test.

About Electrical Technology

All about Electrical & Electronics Engineering & Technology. Follow , Facebook , Twitter , Instagram , Pinterest & Linkedin to get the latest updates or subscribe Here to get latest Engineering Articles in your mailbox. Also, Follow

Check Also

What is MCB (Miniature Circuit Breaker), its Construction, Working, Types & Applications

All about MCB, its Construction, Working, Types & Applications.

What is MCB (Miniature Circuit Breaker), its Construction, Working, Types & How to select proper …

25 comments

  1. Very informative article.

  2. Electricians Sydney

    Thanks for share great info with us. I will recommend you to prefer plate earthing than pipe earthing. Plate earthing is the best earthing.

  3. m jayachandran

    very useful guidance for earthing thanks

  4. Very helpful

  5. ” To avoid such instances, the power supply systems and parts of appliances have to be earthed so as to transfer the charge directly to the earth ”

    Not to transfer energy to earth but to ” short circuit live to earth together to operate the over current device to disconnect live wire instantly..so protect person or equipment.

  6. Outstanding blog, covering almost everything about the types of earthing! The importance of earthing, its types and fuse is very well explained. Thanks. Hope to see such informative blogs more.

  7. this is wonderful

  8. Eng stuart @ MRU Mengo

    such a phaburus guide, engineers read about it pliz!! me am always thea and have gained more.

  9. Is it ever under any circumstances dangerous to touch an earthed line?

    Also for grounding electrical components, does it make any difference on the type of metal used in the grounding wire?

  10. Biplab Chakraborty

    Respected Sir,
    In the existing theory of electrical earthing the fate of electrons after it reaches the earth through earthing/ground rod remain unidentified.
    We have shown that the electrons after reaching the earth/ground through the grounding rods are actually transported to the source through orientations of water molecules. Kindly see the links and post your valuable suggestion:
    1) “The Phenomenon of Electrical Earthing Explained”
    http://hpathy.com/scientific-research/phenomenon-electrical-earthing-explained-orientations-water-molecules/
    2) “Delocalization of hydrated electron conducts………”
    http://hpathy.com/scientific-research/delocalization-of-hydrated-electrons-conduct-electrical-energy-in-water-or-aqueous-solutions/

    Thanking you.
    Biplab Chakraborty

  11. Request if you can exclusively mention a pipe earthing for residential use for current ranging from 20 to 40 Amps.
    A schematic diagram labelling dimensions, parts, quantity of charcoal, lime and salt.
    Can we get effective earthing of 8 feet digging out of 4 to 6 feet digging by adopting any suitable means.

    Thanks

  12. Thank you for your tutorials. It is very useful for me. We are going to change an electricity at our house and also make new powerful grounding. We have already bought Dehn equipment for it and wanted to ask a master to help us. But with your tips I’m sure that I can do everything by myself! Thanks again!

  13. IS ALUMINIUM AS EARTH STRIP OK FOR EARTHING

  14. Hello, We are currently using a single earthing for our single phase Electricity connection.But we are not planning to go for 3 phase connection.The guys who are going to install a 3 phase told that we need a double earthing for 3 Phase connection.So do we need to install a new earthing for 3 phase connection?

  15. I got. Problem i checked and found 12 v in btwn nutral or earth wire is that right ??? Either not so how much volt seen in btwn that

  16. thanks it is very helpful i got much from it .

  17. Exelent explanations and diagrammd

  18. I have a doubt on providing the coal and lime around the rod or plate

  19. earthing grout plate for human body

  20. Thanks for the lecture, is a good indeed,you just upgraded my knowledge, thanks for the good good work,keep it up.

    Can I have the tutorial on inverter connection diagram, and battery connection sent to my box.

  21. very nice explanation

  22. the contents given above are very informative and useful for a common person interested with electrical installation and safety point of view. please clear for a residential building, how much distance should be kept apart from an earth pit with safety point of view.

  23. thanks it elaborates and teaches much about it

  24. Engineering Experts,
    I have a question regarding the Earth Continuity Conductor Sizing for a residential house.

    As you said here “The cross sectional area of the Earth Continuity Conductor should not be less than the half of the cross sectional area of the thickest wire used in the electrical wiring installation.”
    Per this, would the below statements be a safe design consideration for a residential house with 3 Ph Supply & load of 6kW with 40A main Isolator & ELCB.

    1. For 2 Ton AC Circuit & Load of 8 Amps. 4 mm flexible wire used for Phase & Neutral.
    Earthing Wire used is 2.5 mm

    2. For Power Socket with upto 1500W load. 2.5 mm wire used for Phase & neutral.
    Earthing Wire used is 1.5 mm

    3. For other circuits: 1.5 mm wire used for Phase & Neutral.
    Earthing Wire used is 1.5 mm

    Kindly help me with the earthing continuity conductor sizing query. thanks.

Leave a Reply

Your email address will not be published. Required fields are marked *