How to Wire OFF-Delay Timer for 120V and 240V Load Circuits?

Wiring the AH3-3 OFF-Delay Timer for 120V and 240V Circuits

Timers are essential components in various residential, industrial and automation applications. They help control the timing of processes and equipment, ensuring that actions occur in a precise sequence or for a specified duration. One commonly used timer is the AH3-3 Timer, which can be wired for OFF-Delay, ON-Delay or as a relay which allows you to control the delay time before a connected load turns off or on. In this article, we will guide you how to wire an AH3-3 timer to control OFF-Delay operation for both 120V and 240V load circuits.

What is AH3 Timer?

The AH3 Delay timer is a versatile and reliable timer that can be used in a wide range of applications. It is designed to delay the de-energization of a load (e.g., a motor, relay, or solenoid) after a triggering input is removed or released. The timer is available in different voltage ratings, including 120V and 240V AC and 24V DC etc., to suit various power supply requirements.

Timers like AH3-3, H3CR, H3BA ,SA3PA-B etc. can be used for different applications such as OFF-Delay, ON-Delay and relay switching or all of them at once.

Following are the labels of terminals printed on AH3 timer nameplate.

Before proceeding with the wiring instructions, it’s crucial to understand the timer’s key components:

  1. Control Voltage: This is the voltage that powers the timer and controls its operation. It can be either 120V or 240V AC or 24VDC connected to the 2 and 7 terminals, depending on your application.
  2. Delay Adjustment: The timer allows you to adjust the OFF/ON delay time using a potentiometer or dial. This setting determines how long the load will remain energized after the trigger signal is removed.
  3. Trigger Input: The timer starts counting down its delay time when it receives a trigger input. This input can be a momentary switch (two-way, three-way, pushbutton) or any other signal that you want to use as a trigger.
  4. Load Output: The load output is where you connect your load to the NO or NC terminals (depends on the circuit deign and requirement), such as a motor, attic fan or relay further connected to the another load. It remains energized for the specified delay time after the trigger signal is removed.

Terminals Connections of AH3-3 Timer:

The following fig shows the base terminals and its pins connections of AH3 relay timer.

8-PIN Timer - Terminals & Connections

Feature and Rating of the Delay Timer

How to Wire AH3-3 OFF-Delay Timer for 120V & 240V Circuits?

Follow these steps to wire the AH3-3 OFF-Delay Timer for a 120V or 240V single-phase load points:

Wiring AH3-3 Timer for OFF-Delay

Good to Know: Wiring the AH3-3 timer for a 240V load circuit is similar to the 120V setup but with the appropriate voltage rating and wiring the second line wire to the 7 number of terminal instead of Neutral in 120V circuit.

In simple words.

Timer Connection in 120V

Timer Connection 1n 240V

Wiring the AH3-3 OFF-Delay Timer using 2-Way Switch

In the following basic wiring diagram, we have used a single-pole switch to control the attic/exhaust fan operation through OFF-delay mechanism using AH3-3 timer. You may have noticed a fuse and fuse holder on phase wire to the two-way switch. It is because to protect the 18-gauge wire incase of overload or short circuit.

Suppose the circuit is fed-up by 20A breaker while we know that the 18-gauge wire is not suitable for 20 amps (12-gauge is rated for 20A). If a short circuit happens on 20A circuit, the whole 20-A will go through the 18-gauge wire used for switch. This may lead to overheat and cause fire. To prevent this scenario, use 5-10A fuse on anywhere on18-gauge small wire to the timer.

Click image or open in new tab to enlarge

How to Wire OFF-Delay Timer using 2-Way Switch

You may use a single-pole switch (a single-pole (two-way) switch like a rocker) instead of 3-way switch. If you do:

Wiring the AH3-3 OFF-Delay Timer for Pump using 3-Way Switch

In the following wiring circuit, we have used a 3-way switch with a water pump (which can be any load such as an attic fan, light bulb, buzzer, etc.) for OFF-delay operation.

Click image or open in new tab to enlarge

How to Wire OFF-Delay Timer for 120V & 240V Circuits?

Any position of the three-way switch (either UP or DOWN) will activate the circuit, i.e., the timer will activate, and the load circuit will turn OFF after the delay time set on the timer. Using  the 3-way switch:

Wiring the AH3-3 OFF-Delay Timer using 3-Way Switch & Pushbuttons

We have modified the above wiring circuit by adding additional NC (normally closed) push buttons for remote control operation. This means the circuit of recirculation pump remain ON continually until an operator presses the push button, which will break the power supply to the circuit.

Conversely, NO (normally open) push buttons (similar to doorbells, etc.) will activate the circuit when you press them and break the circuit when you release the pressure.

Wiring the AH3-3 OFF-Delay Timer using 3-Way Switch and Pushbuttons

As the circuit is always ON (in either the UP or DOWN position of the three-way switch), when the power supply is interrupted to the circuit, it restores itself to its initial stage. The three-way switch is the primary control, while the push buttons are installed at different locations for remote operation. You may add multiple NC push buttons to control the circuit from various remote locations.

Wiring the AH3-3 OFF-Delay Timer using Only Pushbuttons

Let’s modify the above circuit diagram to make it even simpler by removing the 3-way switch. This way, the AH3 timer is controlled only by NC (normally closed) push buttons. We have used a light bulb as an example load in the circuit, but you may add other appliances such as an attic fan or recirculation pump for a water heater, etc.

Wire OFF-Delay Timer using Only Pushbuttons

You may install as many NC push buttons in different locations (e.g., each bathroom). Here is the working and operation of the circuit:

  1. When the operator presses the ON button, the circuit activates, and the delay timer starts to count.
  2. The light bulb or recirculation pump starts and runs.
  3. Hot water from the water heater circulates to each bathroom.
  4. When the delay time comes to an end, the recirculation pump (or any other connected load) switches OFF.
  5. When the operator presses the NC push button, the circuit breaks, cutting power to the timer, and the pump stops immediately.
  6. When the operator releases the NC push button, the circuit connects again, providing power to the timer. The delay timer starts to count down, and the recirculation pump turns ON once again.
  7. When the delay time period ends, power is still ON at the timer, but the connected load to the timer is OFF.