Parallel Connection of Batteries to the PV Panel
In our previous solar panel wiring installation tutorials, we showed how to wire solar panels and batteries in series, parallel and combination of series-parallel configuration according to our system needs and design. In today’s post, we will learn how to wire two or more batteries in series to the solar panel and other related appliances such as an inverter, charge controller and load points etc.
Suppose, we have a 12V system and we have to connect a 12V, 180W photovoltaic panel to the two 12V, 100Ah batteries. The only possible solution is that we will connect the two batteries in series and connect to the charge controller.
Related Post:
- How to Wire Batteries in Series to a Solar Panel and UPS?
- How to Wire Batteries in Series-Parallel to a Solar Panel?
The storage energy in the batteries can be used later in night/shading to the direct DC load or AC load via UPS/Inverter. During the sunshine/day, The PV panel can be used to charge the batteries as well as power up both AC and DC load. The solar panel rating should be according to the load rating and proper design to prevent the overload condition as well as reduce the charging time of batteries.
To connect the two batteries in parallel, you will have to connect the negative terminal of the first battery to the negative terminal of the second battery and vice versa as shown in fig. In other words, same terminals of batteries should be connected for parallel connection
Note that the parallel connection of batteries will only increase the current capacity of batteries as voltage remains the same in parallel connection.
Related Posts:
- How to Design and Install a Solar PV System? With Solved Example
- A Complete Note on Solar Panel Installation with Calculation & Examples
Batteries Current in Parallel
I1 + I2 …… + In
i.e.
100Ah + 100Ah = 200Ah
It shows that two 12V, 100Ah batteries connected in parallel will increase the Ampere-hour rating i.e. battery capacity while the voltage level is the same as for single battery i.e. 12V.
Batteries Voltage in Parallel
The voltage of batteries in parallel.
V1 = V2 …… = Vn
i.e.
12V = 12V = Total 12V
It shows that two 12V batteries connected in parallel will remain the same i.e. 12V.
Related Posts:
- How to Wire Solar Panel to 120-230V AC Load and Inverter?
- How to Wire Solar Panel to 12V DC Load and Battery?
The following solar panel and battery wiring diagram shows how to wire a 12 V Solar Panel to two 100Ah, 12V batteries in parallel with an automatic UPS system.
Good to know:
- Current is additive in parallel connection of batteries.
- Voltage is the same in parallel connection of batteries.
- To connect batteries in series or parallel, the voltage rating must be the same.
- A 12V battery can only be connected in series or parallel with another battery having the same level of voltage i.e. 12V.
- Do not connect a 12V battery in series or parallel connection to a 6V, 9V or 24V battery.
Related Solar Panel Wiring & Installation Diagrams:
- How to Wire Solar Panel & Batteries in Series for 24V System?
- How to Wire Solar Panel & Batteries in Parallel for 12V System?
- How to Wire Solar Panels & Batteries in Series-Parallel Connection?
- How to Wire Solar Panels in Series & Batteries in Parallel? 12/24/48V System
- How to Wire Solar Panels in Parallel & Batteries in Series? 24V System
- Basic Components Needed for Solar Panel System Installation
- How Much Watts Solar Panel You Need for Home Appliances?

Australia Cuts Gas & Power Prices with Renewables & Batteries
How to Wire a Countdown Timer Switch – 15 Mins to 12Hrs
U.S. Develops Small Nuclear Reactors for AI Data Centers
China Plans Tesla-Inspired Laser Power Network for the Moon
How to Wire a Digital & Smart Fan Speed Controller Switch
US Largest SunZia 3,650 MW Wind Farm Powers 1 Million Homes