Can We Replace a 110/220 Turns Transformer with 10/20 Turns?

1:2 Turn Ratio for 110:220? The Turn Ratio is Same, Shall its Rating be Same?

A step up transformer which has 110/220 turns. Can we replace it with 10/20 turns or 1:2? Turns ratio is same, shall its rating be same? Give appropriate reasons?

No. Because we know that flux is directly proportional to the ampere turns (Φ ∝ At). So if we reduce the number of turns i.e. turns ratio, flux will be also reduced which leads to reduce the induced EMF because EMF is directly proportional to the flux (EMF ∝ Φ). If we go about the transformation formula, the calculated value may be right but if we use the EMF equation of the transformer, it shows a different story. Let’s see what happens when we reduce the number of turns in the transformer windings.

Transformer Rating & Parameters

Can We Replace a 110-220 Turns Transformer with 10-20 Turns or 1-2 Turn Ratio

When Turn Ratio is 110/220

To find E2, we know that

E2/E1 = N2/N1

E2 = (N2/N1) x E1

Putting the values

E2 = (220/110) x 220V

 E2 = 440V 

When Turn Ratio is 10/20

Now, if we use 10/20 Turns ratio instead of 110/220.

E2 = (N2/N1) x V1

E2 = (20/10) x 220V

 E2 = 440V 

We can see that the value of step up voltage is same in both case whether we use 10/20 or 110/220 turns.

But I’m lying. It’s not true.

Let’s turn around to the EMF equation of the transformer.

E1 = 4.44 x f x N1 Φm ……….. (Primary)

E2 = 4.44 x f N2 Φm ……….(Secondary)

In case of turn ratio of 110/220

E1 = 4.44 x 50 x 110 x 9.01 mW 

 E1 = 220V 

E2 = 4.44 x 50 x 220 x 9.01 mW 

 E2 = 440V 

In case of turn ratio of 10/20

E1 = 4.44 x 50 x 10 x 9.01 mW 

 E1 = 20V 

E2 = 4.44 x 50 x 20 x 9.01 mW 

 E2 = 40V 

Hmm. That is a huge different. That’s why we can’t use 10/20 turns ratio instead of 110/220 because flux is directly proportional to the ampere turns (Φ ∝ At). If we reduce the number of turns (turns ratio of the transformer), the amount of produced flux will be reduced because of lower ampere turns which causes to reduce the amount of inducted EMF too i.e. induced EMF is directly proportional to the flux (Φ ∝ EMF).

In short, If we reduce the turn ratio of a transformer from 110/220 to 10/20 or 1:2, The following may occurs.