How to Size Equipment Grounding Conductor (EGC)?

What is Equipment Grounding Conductor? Sizing EGC for Grounding Systems

The Equipment Grounding Conductor (EGC) is a main part of the electrical bonding and grounding system, ensuring the safe dissipation of fault currents. It protects both people from electric shock and equipment from damage. The sizing of the EGC is governed by Article 250.122 of the NEC and is determined based on the rating of the overcurrent protection device (OCPD).

For a proper grounding system, the following step-by-step guide can be used to determine the suitable size of Equipment Grounding Conductor (EGC) based on NEC 2023 (Article 250.122 and Table 250.122).

What is EGC?

The equipment grounding conductor (EGC) is an essential component of an electrical grounding system that provides a low-impedance path for fault currents. It is used to bond all non-current-carrying metallic parts of electrical equipment to the grounding system, ensuring safety and proper operation of overcurrent protective devices and circuits.

According to the National Electrical Code (NEC), an Equipment Grounding Conductor (EGC) is a conductive path designed to carry ground-fault currents. It connects normally noncurrent-carrying metal parts of electrical equipment to the grounded conductor, the grounding electrode conductor, or both, ensuring a safe return path for fault currents.

GEC and EGC in Grounding System

In a solidly grounded system, a main bonding jumper (MBJ) is used to connect the equipment grounding conductor (EGC) to the neutral of the supply at a single point (e.g., in the main panel or disconnect). This connection ensures that in the event of a fault, especially when a phase (hot) conductor accidentally contacts an exposed metallic part of the equipment, the fault current can flow through a low-impedance path via the EGC, equipment grounding conductor, and grounding electrode to the physical earth. Hence, it minimize the risk of equipment damage and electric shock hazards to personnel.

The permitted and acceptable types of equipment grounding conductor are copper, aluminum, or copper-clad aluminum conductor. Additionally, rigid metal conduit, intermediate or flexible metal conduit, electrical metallic tubing can also be used as EGC. NEC 250.118.

Identification of EGC

equipment grounding conductor can be bare, covered, or insulated. Green or green with yellow stripe(s) are used as color codes for EGC.

Green colored or  hexagon shaped terminal “G” is used for equipment grounding conductor (EGC) in receptacles and cords. The EGC terminal is labeled as “G,” “GR,” “GRN,”, “GRND” or “⏚” mark in accordance with NEC – 250.126 and 406.9(B).

The GEC must be identified by either having it stripped the entire accessible length, or to me marked / colored green at the termination or green adhesive labels at the termination. Refer to NEC – 250.119(A), 250.119 B (2) & C (1,2,3), 250.62 and 250.64.

Good to know:

Equipment grounding conductor (EGC) is also known as “Grounding Conductor”, “Equipment (EGC)” is used to perform bonding between electrical equipment.

In the U.S. (NEC), the Equipment Grounding Conductor (EGC) is referred to as the Earth Continuity Conductor in BS 7671 and IEC-compliant countries. The function and purpose are the same; only the terminology differs.

Warning:

Purpose of the EGC

The primary purpose of an Equipment Grounding Conductor (EGC) is to provide a reliable path for fault currents to return to the source and facilitate the operation of overcurrent protective devices such as circuit breakers and fuses. This ensures that in case of a fault, the excessive current is safely directed to the ground, preventing electric shock and fire hazards. This also applies for the same purpose of bonding of equipment using EGC. (NEC 250.4(A)(3)).

Good to Know:

The Equipment Grounding Conductor (EGC) is sometimes confused with the Grounding Electrode Conductor (GEC). While both are grounding conductors, they serve different purposes.

Related Post: How to Size the Earth Conductor, Earthing Lead & Earth Electrodes?

Sizing Equipment Grounding Conductor

The NEC 2023 provides guidelines for sizing the EGC based on the overcurrent protective device rating for the circuit.

According to NEC 2023, Section 250.122, the EGC must be sized based on the rating of the overcurrent protective device (OCPD) that protects the circuit conductors. The standard sizes are provided in Table 250.122.

To properly size an EGC, follow these steps:

  1. Determine the Overcurrent Protective Device (OCPD) Rating: This includes circuit breakers or fuses protecting the circuit.
  2. Identify the Circuit Conductor Material: Copper or Aluminum.
  3. Refer to NEC Table 250.122: This table provides the minimum size requirements for EGC based on the rating of the OCPD.
  4. Apply Adjustments for Special Conditions: In cases where conductors are installed in parallel, larger conductors may be required.

How to Size Equipment Grounding Conductor (EGC)

Note:

Related Post: Design of Grounding / Earthing System in a Substation Grid

Special Conditions and Exceptions for EGC

There are special conditions where the EGC sizing may be affected:

EGC Sizing Table

The minimum size of the equipment grounding conductor (EGC) is determined using NEC Table 250.122. This table provides the minimum size of an EGC based on the rating of the overcurrent device (breaker or fuse).

OCPD Rating Copper EGC (AWG) Aluminum or Copper-Clad Aluminum EGC (AWG)
15 14 12
20 12 10
30 10 8
40 10 8
60 10 8
100 8 6
200 6 4
300 4 2
400 3 1
500 2 1/0
600 1 2/0
800 1/0 3/0
1000 2/0 4/0
1200 3/0 250 kcmil
1600 4/0 350 kcmil
2000 250 kcmil 400 kcmil
2500 350 kcmil 600 kcmil
3000 400 kcmil 750 kcmil
4000 500 kcmil 1000 kcmil
5000 700 kcmil 1250 kcmil

🔹Note: If the conductors are upsized for voltage drop compensation, the EGC must be proportionally increased as per 250.122(B).

Here is the EGC sizing table in the image format for reference.

NEC Table 250.122 - Sizing Equipment Grounding Conductor - EGC
NEC Table 250.122 for Sizing EGC – Copyright of NFPA – NEC – 2023

Examples of EGC Sizing and Calculations

Example 1: What is the suitable size of EGC for a 15 and 20 -Amp circuit breakers?

Solution:

The rating of overcurrent devices used for the most common household applications are 15-amp and 20-amp.

Refereeing to the NEC table 250.122;

For 15-Amp Circuit

For 20-Amp Circuit

Example 2: What is the required size of EGC for a 60-Amp circuit breaker?

Solution:

Example 3: A 100A breaker is used in an installation. What is the suitable size of EGC to use with installation?

Solution:

Example 4: What is the appropriate EGC size for a 200-Amp breaker?

Solution:

If the ungrounded conductors are increased by one size, the EGC must also increase by one size (from 6 AWG to 4 AWG).

Example 5: What is the suitable EGC size for a 400A service with parallel conductors?

Solution:

NEC Requirements for EGC

According to NEC, the following requirements apply to EGCs:

Resources and Related Posts:

Exit mobile version