What is the Suitable Wire Size for a 35A Breaker and Load?

How to Find the Correct Wire Size for a 35A Breaker and Outlet Based on NEC?

Selecting the correct wire size for a 35A breaker and load circuit is crucial for both the safety of the appliance and the operator. The wire size must also comply with the National Electrical Code (NEC) NFPA – 70, IEC, IEEE, or other local codes to pass inspections.

A 35-amp breaker is available in standard sizes but is not as common as 15, 20, 30, and 40-amp breakers. They are used for high-power devices such as A/C condensers. For example, to avoid the unwanted tripping of a 30-amp breaker used with a 3,000W, 120V water heater element, you may upgrade to a 35-amp breaker to resolve the issue if it is related to ampacity or wire size.

A #8 AWG (copper or aluminum) wire is generally suitable for a 35-amp circuit. Understanding the factors involved in wire size selection and the specific applications of a 35A breaker and load circuit will ensure safe and effective electrical installations.

Correct Wire Size for 35-Amp Breaker and Outlet

Suitable Wire Size for a 35A Breaker and Circuit

When installing a 35-amp breaker and load circuit, selecting the correct wire size is essential to ensure safety, efficiency, and compliance with NEC standards.

The NEC specifies that the minimum wire size for a 35-amp breaker is #8 AWG (American Wire Gauge), either copper or aluminum.

Based on NEC Table 310.16, the ampacity of #8 AWG wire is as follows:

#8 AWG Copper

#8 AWG Aluminum

Copper conductors are preferred for most residential and commercial applications due to their lower resistance and better conductivity compared to aluminum. Therefore, the correct wire size for 35-amp circuit is #8 AWG.

 

Good to know:

Selecting the Right Wire Size for a 35A Breaker

Selecting the correct wire size involves considering several factors, including the conductor material (copper or aluminum), circuit length, ambient temperature, and installation environment (e.g., in conduit or free air). The following example illustrates this:

Example:

Suppose you have a 1-pole or 2-pole 35A breaker installed in the main panel, and you need to wire it with a maximum of 35A load circuit. Follow these steps to find the correct wire size for a 35A breaker and load point, considering both continuous and non-continuous load circuits according to NEC guidelines.

Continuous Load Circuit

The NEC’s 125% rule states that the maximum overcurrent protection device (MOCP) should handle 125% of the continuous load. As a safety factor, no more than 80% of the continuous load should be connected to the Overcurrent Protection Device (OCPD).

35A × 80% = 28A

Based on this calculation, no more than 28A of continuous load should be connected to a 35A breaker.

When the minimum circuit ampacity (MCA) i.e. load circuit’s amperes are 28A, to determine the correct breaker size for this circuit:

28A × 125% = 35A

According to NEC Table 310.16, the #8 AWG wire size can carry 40A at 60°C (140°F) and 50A at 75°C (167°F).

Non-continuous Load Circuit

For non-continuous loads (e.g., general lighting circuits), the conductor size should be no less than 100% of the load. The same applies to overcurrent protection devices (OCPDs).

A 35A breaker can handle a maximum of 35A non-continuous load circuits, such as outlets and lighting points, while considering ambient temperature rating (Refer to 110.14(C) and 310.15(B)(2)).

How Many Amps Can a 35A Breaker Handle Safely?

A 35-amp breaker is designed to safely handle a maximum of 35 amps of current. The NEC specifies that breakers should not be loaded to more than 80% of their rated capacity for continuous loads (defined as a load lasting three hours or more). Therefore, a 35A breaker should be used for a maximum of 28A continuous load circuits.

35A × 80% = 28A

For short, non-continuous loads, the breaker can handle up to 35 amps safely.

These ratings comply with NEC Sections 210.19(A), 215.2, and 230.42(A) for continuous and non-continuous loads, and 110.14(C) for ambient temperature.

The above calculations are based on NEC Table 310.16 and 240.4(A) through (G), illustrating that the 8 AWG copper wire size can carry 40A at 60°C (140°F) and 50A at 75°C (167°F) which is the suitable size to use with a 35-Amp breaker.

How Many Watts Can a 35A Breaker and Outlet Hold?

The power capacity of a 35-amp breaker can be calculated using the formula:

120V Circuit

In a standard 120V circuit, the max power a 35A breaker can hold:

35 A × 120 V = 4,200 W

Applying the safety factor:

35 A × 80% = 28 A

Based on this calculation, you may put 3,360 watts of load on a 35A breaker.

28A × 120V = 3,360 watts

It means, you may use 35A breaker with a 120V, 3kW water heater element.

240V Circuit

A 2-P, 35A breaker in 240V circuit can hold the maximum power:

35 A × 240 V = 8,400 W

Applying the safety factor:

35 A × 80% = 28 A

No more than 6,720 watts of load should be connected to a 35A breaker and outlet:

28A × 240V = 6,720 watts

For example, you may use a 35A breaker with a 240V, 6kW water heater element.

These calculations assume that the breaker is not operating at 100% of its capacity simultaneously for continuous load circuits. For continuous loads, the safe wattage is 80% of these values:

How Many Outlets Can be Installed on a 35A Breaker?

35A breaker are used as dedicated circuit for high wattage load circuits. It is not against the code and not recommended to use multiple general-purpose outlets such types of circuits. Mathematically, a 35-Amp circuit breaker can support 18 outlets.

The NEC recommends that a circuit should not be loaded to more than 80% of its capacity to allow for safety margins. For a 35A breaker, the maximum continuous load should be:

35A × 0.8 = 28A

If each outlet is assumed to draw 1.5A, you can estimate the number of outlets by dividing the maximum continuous load by the per-outlet load:

28 A ÷ 1.5 A ≈ 18 outlets

This is a rough estimate and assumes that the outlets will not be heavily loaded. If heavier appliances are expected, fewer outlets should be used.

A 35A circuit might be used to supply a single appliance. For example, large air conditioner, or several outlets in a workshop for heavy-duty tools and machines.

Refer to NEC Table 210.21(B)(3) for receptacle ratings for various circuit sizes.

Suitable Types of Cables for a 35-Amp Breaker and Outlet

Applications of a 35-Amp Breaker and Outlet

A 35-amp breaker and corresponding outlets are typically used in scenarios where moderate to high power demands are required. Here are some common applications:

Good to Know:

Resources:

Wire Sizes for Standard Breakers, Outlet and Branch Circuits

Sizing Wires for for General Wiring Installations

Wiring 30A Outlets with 30A Breakers

↑
Exit mobile version