Electrical DesignElectrical WiringHow ToProtection

How to Size a Breaker and Wires in AWG with EGC for Load?

Proper Sizing of Breakers and Wires in AWG with Equipment Grounding Conductor (EGC) for Branch Circuits – Based on Load Current, Wattage, and Supply Voltage in Single-Phase and Three-Phase Systems

Sizing breakers and selecting the correct wire size in AWG is not rocket science. If you are unfamiliar with electrical codes, or simply tired of reading lengthy articles and doing complex calculations, you are in the right place. Even a beginner can figure it out without the help of an electrician or electrical engineer.

Bored with the introduction? No problem! we’ve got you covered. Below, you’ll find a comprehensive table that clearly shows the appropriate breaker size and wire gauge based on load current, wattage, and supply voltage for both single-phase and three-phase branch circuits.

How to Size a Breaker and Wires in AWG with EGC for Load

Alright, that’s enough – let’s get started to find the branch circuit conductors with EGC and breaker size for overcurrent protection.

How to Size Breaker and Wire Size with EGC in AWG?

120V/240V – Single-Phase Circuit

Example:

What size of conductor and breaker should I use for a 1,920 W water heater operating at 120V single-phase?

Solution-1:

First, calculate the load current using Ohm’s Law:

I = P ÷ V

I = 1,920 W ÷ 120V

I = 16 – Amp

Now, refer to the following table (based on NEC Table 310.16) to determine the proper wire size and breaker rating. For a 16A load at 120V single-phase, the correct choice is a 20A single pole breaker with #12 AWG copper conductors, rated for 60°C (140°F) ambient temperature. Similarly the wire size for equipment ground conductor (EGC) is 12 AWG (based on NEC Table 250.122). This combination is sufficient to handle and protect the 1,920 W load.

But why use a 20A breaker and #12 AWG wire instead of a 15–16A breaker and #14 AWG wire?

According to NEC 210.19(A)(1), branch circuit conductors must be rated at 125% of the continuous load (a load running for 3 hours or more). This rule of thumb is also known as 125% rule.

This way,

= 16A × 1.25 = 20 – Amp

Therefore, the correct selection is a 20A breaker with #12 AWG wire.

For non-continuous loads (operating less than 3 hours, e.g., hair dryers), the breaker and conductor may be rated equal to the load current instead of applying the 125% rule.

Solution-2:

Alternatively, refer to the table. As per the table data, a 1,920-watt load requires a 20-ampere overcurrent device and #12 AWG copper conductors as well as #12 AWG copper for equipment grounding conductor (EGC).

480V – Three-Phase Circuit

Example:

What is the correct wire size and breaker rating for a 9,975 W induction cooktop operating at 240V, three-phase supply?

Solution 1:

The method is same as above i.e. use the three-phase power formula to calculate the load current in amps. Since this is a resistive load, power factor (P.F.) = 1.

P = √3 × V × I

I = P / (√3 × V)

I = 9,975W / (1.732 × 480V)

I ≈ 24 – Amp

Apply the NEC 125% rule for continuous loads.

24A × 125% = 30A.

Therefore, a 30A double pole breaker is required. Similarly, #10 AWG copper conductors (at 60°C (140°F) ambient temp.) are suitable for a 9,975 W load operating on a 30A, 240V three-phase supply. In addition, the same size is required for equipment grounding conductor (EGC) i.e. #10 AWG copper (NEC Table 250.122).

Good to Know: For non-continuous loads (operating less than 3 hours), you may size the breaker directly to the load current. In other words, a 25A breaker with #10 AWG wire would be acceptable.

Solution 2:

Refer to the table and select based on either load wattage or current. For example, a 30A breaker with #10 AWG copper conductors and equipment grounding conductors can safely be used for a 24A (≈ 9,975 W) continuous load operating at 240V three-phase.

Caution:

If you are still unable to manage the wiring installation, consult a licensed electrician to ensure it is done properly and in compliance with code requirements. The author(s) of this guide assume no liability for any damage to persons or equipment.

Table for Breaker & Wire Size with EGC

Sizing Breaker, Wire, and Equipment Grounding Conductor (EGC) for Single-Phase and Three-Phase Loads (Based on Load Current and Wattage)

NOTE:

  • See the notes below the table. They apply to continuous load points. For non-continuous load points (such as lighting circuits), the 125% (or 80%) rule does not apply. Therefore, you can use the full circuit rating – for example, a 15A breaker for a 15A circuit, and so on.
  • The following table should not be used for motor circuits. Motor circuits, controllers, and wire sizing requirements differ from those of lighting circuits. A separate and detailed 14-part series on motor circuits is published on this site
 
Breaker Size & Wire Size with EGC for Branch Circuit Current, Load Wattage, & Supply Voltage – 1-Phase & 3-Phase Circuits
Load Current in Amp Breaker Size (A) Wire Size (AWG) EGC Size (AWG) Single – Phase Three – Phase
120V 240V 208V 240V 480V
Max Watts ≈ Max Watts
10 15 14 14 1,200 2,400 3,605 4,155 8,315
12 15 14 14 1,440 2,880 4,325 4,990 9,975
15 20 12 12 1,800 3,600 5,405 6,235 12,470
16 20 12 12 1,920 3,840 5,765 6,650 13,300
20 25 10 10 2,400 4,800 7,205 8,310 16,625
24 30 10 10 2,880 5,760 8,645 9,975 19,950
30 40 8 10 3,600 7,200 10,810 12,470 24,940
35 45 6 10 4,200 8,400 12,610 14,550 29,100
40 50 6 10 4,800 9,600 14,410 16,630 33,255
45 60 4 10 5,400 10,800 16,210 18,705 37,410
50 70 4 8 6,000 12,000 18,010 20,785 41,565
60 80 3 8 7,200 14,400 21,615 24,940 49,880
80 100 1 8 9,600 19,200 28,820 33,255 66,505
90 125 1/0 6 10,800 21,600 32,420 37,410 74,820
100 125 1/0 6 12,000 24,000 36,025 41,565 83,135
  • Table is Based on NEC Table 310.16 for Wire & Breaker Size.
  • The Table Shows the Wire & Breaker Size for Continuous Load (Lasts More than 3-Hrs) Mentioned in NEC – 210.19. For This purpose, 1.25 Safety Factor is used with Amps for Breaker Size & Wire Size.
  • For Non- Continuous Load (Runs Less than 3-Hrs), You May Use the Exact Current in Amps Rating for Wire & Breaker Size Mentioned in Columns (A).
  • The Table Shows the Data for Pure Resistive Load e.g. Lighting Circuits, Water Heater Elements, Stoves etc. No Power Factor for Inductive and Capacitive Load involved.
  • Sizing Equipment Grounding Conductor (EGC) is Based on NEC Table 250.122.
  • Use Proper Ambient Temperature Factor in 310.15(B)(1)(1) & Other Applicable Correction Factors.

The tables below are available in image format for easy reference and download.

Click image or open in a new tab to enlarge

Breaker Size and Wire Size with EGC for Branch Circuit Current, Load Wattage, & Supply Voltage – 1-Phase & 3-Phase Circuits

Related Resources, Tutorials & Wire Sizing Guides:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button