How to Size a Breaker and Wires in AWG with EGC for Load?
Proper Sizing of Breakers and Wires in AWG with Equipment Grounding Conductor (EGC) for Branch Circuits – Based on Load Current, Wattage, and Supply Voltage in Single-Phase and Three-Phase Systems
Sizing breakers and selecting the correct wire size in AWG is not rocket science. If you are unfamiliar with electrical codes, or simply tired of reading lengthy articles and doing complex calculations, you are in the right place. Even a beginner can figure it out without the help of an electrician or electrical engineer.
Bored with the introduction? No problem! we’ve got you covered. Below, you’ll find a comprehensive table that clearly shows the appropriate breaker size and wire gauge based on load current, wattage, and supply voltage for both single-phase and three-phase branch circuits.
Alright, that’s enough – let’s get started to find the branch circuit conductors with EGC and breaker size for overcurrent protection.
How to Size Breaker and Wire Size with EGC in AWG?
120V/240V – Single-Phase Circuit
Example:
What size of conductor and breaker should I use for a 1,920 W water heater operating at 120V single-phase?
Solution-1:
First, calculate the load current using Ohm’s Law:
I = P ÷ V
I = 1,920 W ÷ 120V
I = 16 – Amp
Now, refer to the following table (based on NEC Table 310.16) to determine the proper wire size and breaker rating. For a 16A load at 120V single-phase, the correct choice is a 20A single pole breaker with #12 AWG copper conductors, rated for 60°C (140°F) ambient temperature. Similarly the wire size for equipment ground conductor (EGC) is 12 AWG (based on NEC Table 250.122). This combination is sufficient to handle and protect the 1,920 W load.
But why use a 20A breaker and #12 AWG wire instead of a 15–16A breaker and #14 AWG wire?
According to NEC 210.19(A)(1), branch circuit conductors must be rated at 125% of the continuous load (a load running for 3 hours or more). This rule of thumb is also known as 125% rule.
This way,
= 16A × 1.25 = 20 – Amp
Therefore, the correct selection is a 20A breaker with #12 AWG wire.
For non-continuous loads (operating less than 3 hours, e.g., hair dryers), the breaker and conductor may be rated equal to the load current instead of applying the 125% rule.
Solution-2:
Alternatively, refer to the table. As per the table data, a 1,920-watt load requires a 20-ampere overcurrent device and #12 AWG copper conductors as well as #12 AWG copper for equipment grounding conductor (EGC).
480V – Three-Phase Circuit
Example:
What is the correct wire size and breaker rating for a 9,975 W induction cooktop operating at 240V, three-phase supply?
Solution 1:
The method is same as above i.e. use the three-phase power formula to calculate the load current in amps. Since this is a resistive load, power factor (P.F.) = 1.
P = √3 × V × I
I = P / (√3 × V)
I = 9,975W / (1.732 × 480V)
I ≈ 24 – Amp
Apply the NEC 125% rule for continuous loads.
24A × 125% = 30A.
Therefore, a 30A double pole breaker is required. Similarly, #10 AWG copper conductors (at 60°C (140°F) ambient temp.) are suitable for a 9,975 W load operating on a 30A, 240V three-phase supply. In addition, the same size is required for equipment grounding conductor (EGC) i.e. #10 AWG copper (NEC Table 250.122).
Solution 2:
Refer to the table and select based on either load wattage or current. For example, a 30A breaker with #10 AWG copper conductors and equipment grounding conductors can safely be used for a 24A (≈ 9,975 W) continuous load operating at 240V three-phase.
If you are still unable to manage the wiring installation, consult a licensed electrician to ensure it is done properly and in compliance with code requirements. The author(s) of this guide assume no liability for any damage to persons or equipment.
Table for Breaker & Wire Size with EGC
Sizing Breaker, Wire, and Equipment Grounding Conductor (EGC) for Single-Phase and Three-Phase Loads (Based on Load Current and Wattage)
| Breaker Size & Wire Size with EGC for Branch Circuit Current, Load Wattage, & Supply Voltage – 1-Phase & 3-Phase Circuits | ||||||||
| Load Current in Amp | Breaker Size (A) | Wire Size (AWG) | EGC Size (AWG) | Single – Phase | Three – Phase | |||
| 120V | 240V | 208V | 240V | 480V | ||||
| Max Watts | ≈ Max Watts | |||||||
| 10 | 15 | 14 | 14 | 1,200 | 2,400 | 3,605 | 4,155 | 8,315 |
| 12 | 15 | 14 | 14 | 1,440 | 2,880 | 4,325 | 4,990 | 9,975 |
| 15 | 20 | 12 | 12 | 1,800 | 3,600 | 5,405 | 6,235 | 12,470 |
| 16 | 20 | 12 | 12 | 1,920 | 3,840 | 5,765 | 6,650 | 13,300 |
| 20 | 25 | 10 | 10 | 2,400 | 4,800 | 7,205 | 8,310 | 16,625 |
| 24 | 30 | 10 | 10 | 2,880 | 5,760 | 8,645 | 9,975 | 19,950 |
| 30 | 40 | 8 | 10 | 3,600 | 7,200 | 10,810 | 12,470 | 24,940 |
| 35 | 45 | 6 | 10 | 4,200 | 8,400 | 12,610 | 14,550 | 29,100 |
| 40 | 50 | 6 | 10 | 4,800 | 9,600 | 14,410 | 16,630 | 33,255 |
| 45 | 60 | 4 | 10 | 5,400 | 10,800 | 16,210 | 18,705 | 37,410 |
| 50 | 70 | 4 | 8 | 6,000 | 12,000 | 18,010 | 20,785 | 41,565 |
| 60 | 80 | 3 | 8 | 7,200 | 14,400 | 21,615 | 24,940 | 49,880 |
| 80 | 100 | 1 | 8 | 9,600 | 19,200 | 28,820 | 33,255 | 66,505 |
| 90 | 125 | 1/0 | 6 | 10,800 | 21,600 | 32,420 | 37,410 | 74,820 |
| 100 | 125 | 1/0 | 6 | 12,000 | 24,000 | 36,025 | 41,565 | 83,135 |
|
||||||||
The tables below are available in image format for easy reference and download.
Click image or open in a new tab to enlarge
Related Resources, Tutorials & Wire Sizing Guides:
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How Size a Circuit Breaker for Different Load Applications
- How to Size a Branch Circuit Conductors with Protection?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- How to Size Earth Conductor, Earthing Lead and Earth Electrodes?
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
- What is the Correct Wire Size for 100A Breaker and Load?
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- Cable Size Calculation for LT & HT Motors
- How to Size Motors FLC, HP, Voltage, Breaker Size and Wire Size
- How to Size and Find the Numbers of Ceiling Fan in a Room?








