What is the Main Bonding Jumper (MBJ) and How to Size it?

What is a Main Bonding Jumper – Sizing MBJ and Where Can It Be Found in an Electric Panel?

Main Bonding Jumper (MBJ)

In an electrical panel or load center, the Main Bonding Jumper (MBJ) is the conductive connection that bonds (connects) the grounded conductor (neutral) to the equipment grounding conductor and the metal enclosure of the panel.

This connection ensures that the neutral busbar and the grounding system are electrically tied together at the service disconnect, which creates an effective fault-current path.

Definition:

The Main Bonding Jumper (MBJ) is a screw, strap, or conductor that connects the neutral busbar to the metal enclosure (panel cabinet) and grounding busbar at the main service equipment (service disconnecting means).

According to NEC Article – 100, a Main Bonding Jumper is the connection between the grounded conductor (neutral), and the equipment grounding conductor, and the service disconnect enclosure.

A bonding jumper (bonding conductor) is used for electrical connectivity between the metallic bodies of two equipment. This process is known as electrical bonding.

Good to Know:

Purpose of the Main Bonding Jumper

The MBJ performs several important safety functions:

It creates a fault current path to allow ground-fault current to return to the source so the circuit breaker trips quickly. It bonds metal parts together i.e. the panel enclosure, neutral conductor, and grounding conductors are connected at one point.

MBJ helps to establishes the neutral conductor at earth potential and eliminates the risks associated with the faults current. Without the bonding jumper, fault current may not be high enough to trip the breaker.

Thank to the main bonding jumper, that’s why you can safely touch the metal enclosures and panel box without being electrically shocked.

Good to Know: Don’t confuse between Main bonding and main bonding jumper in a panel. The main bonding is a connection using metal strap between ground and neutral busbars in the main panel. The main bonding jumper is used to electrically connect the metallic body of electric panel to the grounded circuit (ground busbar).

Where the Main Bonding Jumper is Located

In a main service panel, the grounded terminal bar (neutral busbar) is connected to all grounding wires, i.e. equipment grounding conductors (EGCs), the grounding electrode conductor (GEC) i.e. the wire that runs between the ground rod and the neutral/ground busbar, and the metallic enclosure of the panel through the main bonding jumper.

The MBJ is installed only in the main service equipment, such as:

It is not installed in subpanels.

Typical forms of MBJ in an electric panel (as shown in the following fig) include:

Main Bonding Jumper (MBJ) and How to Size it
Locations of Main Bonding Jumper (MBJ) in an Electric Panel

Good to Know:

Sizing Main Bonding Jumper

The size of the Main Bonding Jumper is based on the largest ungrounded service-entrance conductor or the equivalent area for parallel conductors. The Main Bonding Jumper (MBJ) must be sized according to NEC 250.28(D) and Table 250.102(C)(1) as follows:

Example:

What is the suitable size of main bonding jumper for a 120/240V single-phase main panel installation having 3/0 AWG copper service entrance conductors.

Solution:

Identify the largest ungrounded conductor (hot or live wire). In our case,  the largest service conductor is 3/0 AWG copper.

Now, refer to the NEC Table 250.102(C)(1) which shows the minimum required size of MBJ is 4 AWG copper for 1/0 – 3/0 AWG copper as largest ungrounded conductor.

Therefore, the minimum Main Bonding Jumper size = 4 AWG Copper

Similarly, the size of MBJ for a 350–600 kcmil copper as a hot conductor in the panel is 1/0 AWG copper.

MBJ Sizing Table

The MBJ can be sized based on largest ungrounded conductor (not the breaker rating) and the values are given in NEC – Table 250.102(C)(1).

Largest Ungrounded Conductor or Equivalent (Copper/Aluminum or Copper-Clad Aluminum) Size of Grounded Conductor or Bonding Jumper
Copper Aluminum or Copper-Clad Aluminum Copper Aluminum / Copper-Clad Aluminum
2 AWG or Smaller 1/0 AWG or smaller 8 AWG 6 AWG
1 or 1/0 AWG 2/0 or 3/0 AWG 6 AWG 4 AWG
2/0 or 3/0 AWG 4/0 or 250 kcmil 4 AWG 2 AWG
Over 3/0 AWG through 350 kcmil Over 250 kcmil through 500 kcmil 2 AWG 1/0 AWG
Over 350 kcmil through 600 kcmil Over 500 kcmil through 900 kcmil 1/0 AWG 3/0 AWG
Over 600 kcmil through 100 kcmil Over 900 kcmil through 1750 kcmil 2/0 AWG 4/0 AWG
Sizing Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, &  Supply-Side Bonding Jumper – NEC – Table 250.102(C)(1).

Here is the MBJ sizing table in the image format for reference.

Sizing Main Bonding Jumper - MBJ. NEC-Table 250.102(C)(1)
NEC-Table 250.102(C)(1) – Sizing Main Bonding Jumper – MBJ

NEC Requirements for Main Bonding Jumper

Precautions:

Disclaimer: Electrical work is dangerous. The author assumes no responsibility for any loss, injury, or damage resulting from the use or misuse of this information, including improper circuit installation.

Resources:

Related Posts:

Sizing & Rating

Wiring Tutorials

↑
Exit mobile version