Can You Use 15A Breaker on 20A Circuit and Vice Versa?
Is It Permissible to Use a 15-Amp Breaker on a 20A-Amp Circuit, or a 20-Amp Breaker on a 15A-Amp Circuit?
We often receive multiple queries regarding basic electrical wiring installations and DIY tasks at home. Today, we received a question (which can be confusing for a layperson) asking whether a 20-Amp breaker can be used on a 15-Amp circuit, and vice versa. Let’s now discuss this issue and the possible consequences of such setups in these specific cases.
While it is technically possible to use a 15-amp breaker on a 20-amp circuit or a 20-amp breaker on a 15-amp circuit, it is not recommended due to safety concerns and non-compliance with electrical codes. The second case (20A breaker on 15A circuit) is more dangerous which can cause serious damage and electrical fire hazards. Let’s see how?
Using 15-Amp Breaker on a 20-Amp Circuit
Possible, but not ideal! A 15-amp breaker can be used on a 20-amp circuit with 12-gauge wire rated for 20 amps. The breaker protects the branch circuit wires, and since 12 AWG can handle 20A, a 15A breaker won’t overload it. In case of overcurrent, the breaker will trip at 15 amps, which is below the wire’s capacity. This setup is safe but limits the circuit’s capacity, as the breaker will trip before the circuit can handle its full 20-amp potential.
Why It is Not OK – Possible Issues and Risks:
- The circuit is designed for 20A loads, so a 15A breaker may trip unnecessarily under normal usage (e.g., multiple devices drawing 16A).
- You won’t be able to use the full capacity of the circuit (e.g., appliances or devices requiring more than 15 amps will cause the breaker to prematurely trip).
- The National Electrical Code (NEC), requires the breaker to match the circuit’s design capacity. NEC 210.21(B) requires receptacles on a 20A circuit to be 20A-rated (or a mix of 15A/20A if multiple outlets exist (210.21(B)(3) or cord and plug connected load to receptacles as per 210.21(B)(2)). If you downgrade to a 15A breaker, you may violate code if the receptacles are 20A-only.
- It could cause confusion for future electricians working on the system.
Hence, it is recommended to use the right size breaker to based on wire size in accordance with Table 310.16 to protect the branch circuit conductors and prevent nuisance and unwanted tripping of the breaker.
Using 20-Amp Breaker on a 15-Amp Circuit
While technically possible, but highly dangerous and violates code (NEC 240.4(D)). Hence, Not Allowed!
14 AWG wire is only rated for 15A. A 20A breaker won’t trip before the wire overheats, creating a fire risk.
If you use a 20-amp breaker on a circuit wired for 15 amps (typically 14 AWG wire), the breaker may allow more current than the wire can safely handle. This can cause the wires to overheat, potentially leading to electrical fires.
Installing a 15-amp breaker on a circuit designed for 20 amps (usually using 12 AWG wire) may cause frequent tripping even under normal load, as the breaker is not rated to handle the expected current.
Why it is Not Allowed?
A 20-amp breaker should not be used on a 15-amp circuit (with 14-gauge wire rated for 15 amps). The breaker will allow up to 20 amps of current to flow, which exceeds the wire’s capacity. In addition, it doesn’t makes sense as the 20-Amp breaker won’t be able to protect the 15-Amp branch circuit conductors. Consequently, this practice can potentially cause overheating, fire hazards, or damage to connected devices.
Receptacles on a 15A circuit must be 15A-rated (NEC 210.21(B)(1)). The NEC requires the breaker to match or be less than the ampacity of the circuit’s wiring to prevent overheating. Using a 20-amp breaker on 14-gauge wire violates this rule. Therefore, never use a 20A breaker on 15-Amp, 14 AWG wiring circuits.
To be on the safe side, use the correct breaker size for the wire and load wattage and ampere rating for general-purpose circuits. This way, use a 15-amp breaker for a 15-amp circuit (14-gauge wire) and a 20-amp breaker for a 20-amp circuit (12-gauge wire).
Circuit Ampacity
Minimum Wire Gauge
Correct Breaker Size
15 Amps
14 AWG
15 Amp Breaker
20 Amps
12 AWG
20 Amp Breaker
Precautions and Best Practices
- Match the breaker to the wire size and intended load.
- If you need a 20A circuit, use 12 AWG wire + 20A breaker + 20A receptacles.
- If you have a 15A circuit, use 14 AWG wire + 15A breaker + 15A receptacles.
- 15A breaker on 12 AWG (20A wire) = Safe but not ideal (may cause nuisance tripping).
- 20A breaker on 14 AWG (15A wire) = Unsafe & violates code.
-
If you need to replace a breaker, verify the wire gauge and circuit design to ensure compatibility.
- Always follow NEC guidelines and consult a licensed electrician for any modifications or if you’re unsure about the circuit’s configuration.
Related Posts & Tutorials:
- Can We Use AC Circuit Breaker for DC Circuit & Vice Versa?
- Can an AC Device Operate on DC Supply, and Vice Versa?
- Can I Use a 1-Phase Breaker on a 3-Phase Supply & Vice Versa?
- Can I Run 1-Phase Load on 3-Phase Supply and Vice Versa?
- Difference Between 15-Amp and 20-Amp Outlet?
- Difference Between Socket, Outlet and Receptacle?
- Why is the Neutral Prong or Slot Wider on a Plug or Outlet?
- Why Do Prongs in Electrical Plugs Have Holes in Them?
- Why is Earth Pin Thicker and Longer in a 3-Pin Plug?
- What Will Happen If You Connect a Male-to-Male Plug Between Outlets
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
- How to Find the Voltage Ampere Rating of Plugs & Outlet & Receptacle?
- How to Find the Number of Outlets on a Single Circuit Breaker?
- Why is AC Commonly Used in Households Instead of DC?
- Why are High-Power Devices Not Designed to Run on DC Voltage?
- How Do Some Devices Operate on Both AC and DC Supplies?








Its not always permissible as a 20 amp circuit can be wired in 6 or 4mm cable where 15 amp covers up to 2.5 mm cable. If you don’t know don’t do it
Both can wired in 2.5 mm and will take a lot more than 15 amps.4 mm or 6mm if long runs or cable installed in certain ways
The breaker protects the wire, so you can upsize the wire all you want for a given breaker size. A larger breaker will not protect a smaller gauge wire, though.
The 15A breaker will easily trip when there is a short circuit in the 20A circuit
While the 20A breaker will take time before it trips when using a 15A circuit
Yes and no on the vice versa. If you don’t mind trip on 3/4 load use it. But on vice versa trip will be on too big an overload and hence dangerous.
A 15 amp breaker can be used on a 20 amp circuit due to the #12 wire being able to carry up to 20 amps. However you cannot use a 20 amp breaker on wiring only rated to carry 15 amps. This could result in a load that overheats the wiring resulting in damage or destruction of the wiring and creating a fire hazard.