Automatic UPS / Inverter Wiring Diagram Using One Live Wire
Automatic UPS System Wiring Diagram (One Live Wire & Standard Wiring)
Automatic UPS / Inverter Connections
In case of a power outage when utility supply from the grid is unavailable, an automatic inverter/UPS system with batteries can be used to ensure uninterrupted power.
We will demonstrate two basic methods of wiring and connecting a UPS/Inverter with batteries to the home distribution system and main panel board:
- Automatic UPS/Inverter with Two Wires
- Automatic UPS/Inverter with One Live Wire
- Auto UPS / Inverter with Two Wires
- Automatic USP / Inverter Wiring with One Live Wire
- Related Wiring Tutorial: UPS / Inverter Wiring Diagram With Auto & Manual Changeover Switch System
Automatic UPS / Inverter Wiring with Two Wires
There is no complexity involved in this method. Simply connect the incoming Neutral and Live (Phase) wires to the UPS/Inverter input. Then, connect the two outgoing Neutral and Phase wires from the UPS/Inverter output to the appliances and electrical devices, as illustrated in Figure 1.
Click image or open in a new tab to enlarge
UPS / Inverter Wiring with a Single Additional Live Wire
As a basic principle, every load point requires both a Live (Phase) and a Neutral connection to operate properly. In this case, the Phase and Neutral supply from the power house (via the utility pole and distribution board) are already connected to each electrical appliance, such as fans, lights, etc. This is the standard practice in home wiring through the distribution board.
According to the UPS/Inverter wiring diagram shown below, you only need to connect an additional Phase wire from the UPS to the appliances. Since the Phase and Neutral wires from the power house and distribution board are already connected, you will effectively have two Phase wires available for those appliances (as shown in Figure 2).
Now, according to the UPS connection diagram below, connect an additional wire (Phase) to those appliances where we have already connected Phase and Neutral wires from the power house and distribution board (DB) (i.e., two wires as phase (Live), as shown in the figure below).
There is no need to connect an extra Neutral wire from the UPS, because the Neutral connection is already installed and in place. In simple terms, you only need one extra Live (Phase) wire to complete the UPS connection for the appliances.
Now, you may wonder: “Why add an extra Phase wire instead of a Neutral?” The explanation lies in the working principle and operation of this circuit, which will be discussed in the following section.
Click image or open in a new tab to enlarge

Working and Operation of UPS Connection
(1) When Utility Power is Not Available (Power Outage)
In the event of a power failure, the electric supply continues through the Phase wire from the UPS output, which is connected to the UPS and its batteries, and then delivered to the electrical appliances. The Neutral remains connected as before and does not require any changes.
The original Phase wire from the main board (connected before UPS installation) becomes inactive because the utility supply from the power house is unavailable. At this point, the connected appliances receive power exclusively from the UPS output Phase. In this way, the appliances consume the stored electrical energy in the batteries and remain operational without interruption.
(2) When Power Supply Restores from the Power Grid
When utility power is restored, the electric supply resumes through the Phase wire from the main board to the UPS (while the Neutral remains unchanged). In this mode, the UPS automatically switches back to utility power. It not only supplies the connected electrical appliances but also begins charging the batteries.
The second Phase wire from the UPS output becomes inactive in this condition, because the appliances are now receiving power directly from the grid through the UPS. Since it is an automatic UPS system, the batteries are no longer discharging, i.e. they are instead being recharged for the next power outage.
How to Connect a UPS / Inverter to the Main Panel / Consumer Unit?
Figure 3 below illustrates how to connect a UPS/Inverter with batteries to the Main Distribution Unit (MDU) to ensure continuous power supply during a utility power failure.
In this arrangement, additional wiring connections are made between the UPS/Inverter and the selected loads (such as appliances, lights, and fans) in different rooms of the house. For example, in the diagram, two rooms are shown as connected to the UPS supply.
This setup demonstrates the method of connecting an Automatic UPS/Inverter to the home supply system, ensuring that essential appliances remain powered without interruption during an outage.
Click image or open in a new tab to enlarge

Wiring Color Code:
Wiring Color Code
In the above given single phase wiring diagrams, the following colors have been used:
- Red = Live (Phase)
- Black = Neutral
- Green = Earth (Ground)
However, wiring color codes may vary depending on regional standards. The two most commonly followed standards are:
Single Phase 120V AC – NEC & CEC – US & Canada
- Black = Phase (Line or Hot)
- White = Neutral
- Green/Yellow or bare conductor = EGC Grounding conductor
IEC – UK, EU, etc.):
Single Phase 230V AC – UK, EU and IEC Following Countries
- Brown = Phase (Line)
- Blue = Neutral
- Green/Yellow = Earth (Ground)
Related Posts:
- How to Wire Solar Panels in Series, Parallel and Series-Parallel?
- How to Wire Batteries in Series, Parallel and Series-Parallel?
General Precautions When Working with Electricity
If you are still facing difficulties or do not fully understand the wiring diagram, feel free to leave a comment or explore the other step-by-step tutorials on UPS/Inverter wiring diagrams, connections, with working and operation.
Resources and Related Electrical Wiring Installation Tutorials.
- How to Wire Wire a Single-Phase Distribution Board [Consumer Unit]?
- How to Wire a Distribution Board with RCD – Single Phase ?
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- Single Phase & Three Phase Wiring Diagrams (1-Phase & 3-Phase Wiring)
- Home Electrical Wiring Installation Diagrams & Tutorials
- Single Phase Electrical Wiring Installation in Home – NEC & IEC
- Single Phase Electrical Wiring installation in a Multi-Story Building
- Three Phase Electrical Wiring Installation in Home – NEC & IEC
- Three Phase Electrical Wiring Installation in a Multi-Story Building
- How To Wire a Single Phase Energy meter?
- How To Wire a 3 Phase kWh meter?
- How to Control One Lamp From Three Different Places?
- Staircase Wiring Diagram – How to Control a Lamp from Two Places?
- Difference Between Inverter & UPS (Uninterruptible Power Supply)
- Difference Between Voltage Stabilizer and Voltage Regulator (AVR)
- How to Determine the Suitable Size of Inverter for Home Appliances?
- How to Wire Solar Panel to 120-230V AC Load and Inverter?
- How to Design and Install a Solar PV System? With Solved Example








what is the size of wire shoule be used in connecting fuse box to ups
It depends on your load requirements….in other words, your number of final sub circuits.
Hello what could be the possible reason as ,my house light is not working when there is supply from power grid but it works only when we turn on invertor. And inventor also not getting charging with main supply line.
kuldipyadav994@gmail.com
hello,
i have devices that i only want to turn on when there is no grid power and the inverter is “activated”. how to achieve this?
Can one makes use only change over for the connection
It is also available..Check in the above section..(Electrical Wiring)
Dear Wasim Khan<br />I am thankful to you for the UPS diagram on your blog. I have found it perfect for installation of my new UPS with the system.
Dear Mohammed Munir Akhtar <br />Thanx for your appreciation
Thx…. Much Appreciated<br />
Thanx Dear
So as per your diagram we connect only the live wire from the ups output to the loads we want to connect. There is no need to connect the neutral from ups output to the load circuits. My ups was connected like this earlier. But now I have shifted and when i reconnected at new place as before and switch off the main switch to check the attached load doesnot work. I was wondering from where the
Suman@<br />There are more UPS wiring diagrams under the " Electrical Wiring " Tab. ( You should Check)<br />in this case of above diagram, we have connected only live or Phase wire from UPS to the load, because Neutral wire already connected to the load ( from Distribution board) so no need to connect Neutral wire.<br />If you want to connect neutral wire, then Use this method.<br />
I have a doubt on live wire from ups connected to loads.I have two flats on the same building. one flat has single phase supply and an inverter/ UPS connected. I had the second floor also connected with the same UPS with a live wire from UPS. This was done When i had no power supply to the fllat. Now I have separate 3 phase connection for the second floor. I have disconnected the UPS and the charger supply to the battery to avoid any untoward incident. pl suggest suitably
Thanks
Welcome Dear
How about pc
Same Diagram can be used. Connect PC instead of Other Load.
What type of UPS it is in term of on-line or off-line UPS?
Dear..It is not On-Line…It is One Line…I.e Only Phase or Live Wire..As shown in above circuit diagram
Thanks for the Circuit. I Think, I can install my new UPS alone. But I have one doubt. If my House load is more than the capacity of the UPS means..? <br /><br />UPS will trip..? IF yes, After Electric board power comes, IT will not switch on right.? Then my house will not get power..?<br /><br />Please explain me.
Dear Parthib@ <br />As we know that Inverter should be greater 25% than the total Load<br />Suppose your Load = 800 Watts, than, <br />800 x (25/100) = 200<br />800+200 = 1000 Watts<br />This is the Rating of the UPS (Inverter)<br />So, before installation , Try to calculate the rating of UPS according the load.<br />Secondly@ Can you operate a 500W Motor on 110 W???? So that is the answer.
Thanks for the info,<br /><br />At present.<br /><br />I have 600VA mahindra Powerol Inverter and 150AH Amaron Battery.<br /><br />My full Home load is 4 light and 2 fans and 1 TV.<br /><br />So can i connect this type of wiring.?
Dear Parthib@ what is the rating of lights and Fan???<br />suppose, if we assume 40watts fr each then 40 x 4 W + 2 x 90 W (for fan) + 300W for TV = 560 W. <br />So you can use it but the backup time of battery would be low.<br />For More and Complete Detail. Read my This article <br />https://www.electricaltechnology.org/2013/05/a-complete-note-on-solar-panel.html
I have luminus sinwave invertor, i transfered to a new place , one elctrician came and connected it and it and not working , can u guide how i connect its out put and input in my mainswitch of my house.. shall bgr8ful<br />
I think this is very simple wiring diagram….but you can find more wind diagrams about UPS wiring above in Electrical Wiring Section…
sir i wan to ask that as i successfully installed ups as in your diagram. but can now iwant to use generator can we use same appliance wired for UPs on GENERATOR means live wire plug into generator is it works<br />
I am Using the same circuit diagram for Portable Gas Generator..
Sir I have two type of wiring one for ups and other for Wapda if I plug generator switch in Wapda switch not connected with ups and ups can shutdown then is it all appliance work properly which is. No connection from ups .thanks reply me also on email
Hello sir, i have an pure sine wave 850va inverter and i m using your circuit in which one live wire is connected from inverter/ups output.. my half home appliances runs from directly grid power and half are through inverter and i use the common nutral wire.. now my question is if i switch off the input it will go in backup mode but will it affect my inverter because we use only phase/live from
Did you read this Post.<br />Automatic UPS System Wiring Diagram in Case of some items depends on UPS and rest depends on Main Power at Office or Home.<br />https://www.electricaltechnology.org/2012/11/automatic-ups-system-wiring-diagram-in.html
ok i just saw it and the same thing i done at my home… now my questions are same as above… Pls answer it if you can Thank you for your kind Reply.
Grid Current in inverter Out put socket viva Phase/Live???????? but Why??.. You can use only the above diagram… Or just check in "Electrical Wiring…Home wiring…UPS Installation" Section…
(1). No. This circuit is designed for that specific operation.. So no need to worry. it will work and it will never damage your inverter.<br /><br />(2). Yes! you should do (for safety purpose)<br />
i think u can't understand what i m trying to say(i dont know much about these things so i think i m unable to express)… i did same thing just like one of your diagram https://www.electricaltechnology.org/2012/11/automatic-ups-system-wiring-diagram-in.html now i m trying to say is if i just switch off the inverter input then the stuffs(which are connected to inverter) will run from backup
I want to make a lightening arrester on day basis in the simplest manner.pl. Guide me.
Ali
do you have single phase amf diagram , can you post it? someday i want to try install it at my house. thanks
UPS’s are not expensive compared to the rest of a VoIP system, but unless they are budgeted for during the planning process they tend to be overlooked. When the UPS planning is done for the access closets, it is also important to make sure there is enough electrical power to the closets.<br />
i have a problem with the output socket of my inverter, it gives output through left Pin in the socket when connected to mains and then supply changes to right pin when mains off or runs with battery
I resolved my problem by Interchanging the input phase and neutral. Now the output is only from right pin
sir, when i switch off main breaker , my home neutral line getting power. why? we have installed inverter circuit same as above. <br /><br />note:all equipments working as usual for years with same inverter diagram. today simply checked neutral line, and got this problem.
Harish:-sir as per u r diagram the load is more as fans,lights ,chichen ites and ac's etc…are connected together on only one line…if the incoming power is switched off or shut down the load will drawn the all power charged in battery with in a seconds……so that we hav to drawn another one line for load…..
Thanks for such information sharing with us ….<br />i am still confuse with this diagram…<br /><br /><a href="http://www.adeptpower.co.uk" rel="nofollow"> ups system</a>
Respected sir,<br />i have complete UPS system in my house, UPS also charges the battery now i want to connect solar panels to charge the battery. one i/p from battery and other i/p from solar panels, Confused what should i do?<br /><br />Zubair Anwar
Dear.<br />Just read this article<br />https://www.electricaltechnology.org/2013/05/a-complete-note-on-solar-panel.html
What I would really like to know is who will be the <br />notes written to <a href="http://bluepromoyo.blogspot.com/" rel="nofollow">bluehost coupon code 2013</a> but <br />these forms of loans are normally only accessible to highly <br />experienced and successful developers taking care of projects over <br />$5,000,000.
i wanna ask that if the plug attatched to ups is plugged out of ups and put in the socket in main circuit where the charging plug was attatched after removing it??
???
Thank you very much for the simple connection diagram.<br /><br />But I have doubt. I think UPS is not connected to the Earth wire in this 'New Design With One Live Wire'.<br /><br />Is there any way the UPS could be earthed? Does the absence of earthing affect the safety/life of the UPS? Is this important at all?<br /><br />Please reply as I am looking forward to instal a home UPS in the
As you can see that Neutral wire is already connected to all appliances…so no need to connect another Neutral wire… <br />another thing …. That Neutral wire is not for safety purpose..just for completion the circuit..<br />Also you can connect Earth (grounding) wire only with UPS for safety purpose…
Respected sir..
If we disconnect the mains neutral for the circuit, then how can inverter completes its circuit? Actualy we did not taken the inverters neutral no…
Sorry for irrelevance . Just I was curious with how pre paid electric meters work and specifically how do they know the token entered is the one; is there a connection made with the electricity supplier HQ or they are incorporated with formulas to decipher the tokens or there is another way and in addition how do the remotes work.
This comment has been removed by the author.
Connect WAPDA Phase and Neutral wire in UPS inlet (Input)
This comment has been removed by the author.
This comment has been removed by the author.
Also check this one<br /><a href="https://www.electricaltechnology.org/2012/11/automatic-ups-system-wiring-circuit.html" rel="nofollow">Automatic UPS system wiring circuit diagram (Very simple) </a> <br />
Sir one more question, your diagram does not specify what to do with the main phase wire for e.g. if I connect a fan switch to the UPS, the UPS wire is connected to the switch, but what do I do with the existing WAPDA Phase wire that was connected to the fan switch before wiring the fan switch to the UPS? Do I jodo/twist the UPS and WAPDHA Phase together into that fan switch which I mentioned in
Dear Azaan Kaul@<br /><br />As you know, in your case, we had already connected Phase & Neutral (from WAPDA) to Electrical Appliances i.e. Fans, Light points etc… So according the above UPS Connection Diagram…connect an extra wire (phase) to those appliances where we have already connected phase and neutral from (wapda) (two wire as phase with same point). So no need to connect Neutral
Thanks a lot Wasim Sir! Can you also provide a tutorial on how to install tube lights, exhaust fans etc.? Try to put some stuff related to Air conditioning too! Anyways really good website! Simplifies things!
Dear Azaan Kaul<br /><br />We Will try our best,,Stay tune here….<br />And bundle of thanks for appreciation…
how can change automatically when power faliure
This job is done by Inverter (UPS)
Nice info thanks for sharing<br />
sir, diagram is ok. we have 3 phase connection. living hall on phase 1 and bed room on phase 2 and kitchen on 3 phase. if i connect my invertor on one single line from invertor to tubes and fans it will work. when all 3 phase current (grid) fails no problem. my invertor was connected to phase 1` for charging. during night phase 2 (bedroom) power supply from grid fails, how my invertor will
this is for ups but what about only 3 pin invetrer which contain 3 wire in a single cooted plastic cover which are responsible for input or output<br />
Great web site you have got here.. It's difficult to find <br />excellent writing like yours nowadays. I seriously appreciate people <br />like you! Take care!!<br /><br />Feel free to surf to my weblog <a href="http://www.charlieshandles.com/" rel="nofollow">poignées de portes</a>
I hope you may continue to keep in posting new posts thank you for sharing your great experience among us. distribution boards
can i use this diagram to power up an a/c small 200-400 watts refrigerator and a desktop computer?? your answer regarding this is much appreciated. thank you.
yes! you Can.
but considering the starting current of the refrigerator, don’t we need a 2kva inverter?
just one precaution… non- inverter airconditioner and refrigerator require high torque at the startup if that surpass your inverter capacity it will trip the system.
can i use this circuit diagram to run a small a/c 200-400 watts refrigerator and a desktop computer? I have 850va pure sine wave inverter.
Sir i want to connect 2kv stablizer and600VA inverter in my room.how it connect?
Check the above diagram. isn’t it helpful for you?
In my inverter I am getting phase in output in one pin when current is available and it is getting changed to other pin when there is no power…i am confused now which one to use for single wire.. if i interchange the single wire pin my appliances are only working either in power on mode or in power off mode, please help me to correct this prob
I am facing the exact same problem since yesterday after the inverter was taken off and reconnected again. Can someone help? One of the earlier comments suggested to swap the input phase with neutral. I tried that but it didn’t help – the inverter doesn’t recognize the input if done that way. Am I doing something wrong?
Did you check for leakage current or short distribution system? also check for insulation.
Dear author….u said while supply available from grid the pwr comes from main to ups to charge battery….then after ups to appliances.. what u said at starting is 2nd phase wire i.e from ups is inactive if it is inactive how pwr reaches from main to appliances…i asked because there os no direct phase connection from main to appliances
It is automatic process in UPS. Read again or clear your question. Thanks
can we take out put from phase terminal only for house wiring.
Ya Sure… We are doing the same
hello sir,
you have a marvellous site here. I’ve learnt quite a bit, almost enough to attempt a diy installation of an inverter! I have planned for a 1500va system with 2 batteries. here comes the daft question. I’d like to make it whole house. I’ve no major power hungry equipment. lots of 10 watt LEDs, two laptops, a small set top box with LED TV. I do however plan to get a. induction stove at some point,though there will not be a need to run it off an inverter. almost forgot my question. could I just connect the ups to the fuse panel directly and call it a day, or am I being silly?
thanks in advance!
Hi my question is when wiring the light switch/point with the UPS and mains wire, in which terminal of the switch do I have to put the UPS wire, is it in the input MAINS PHASE terminal of the switch from where you get the MAINS or the output phase terminal of the switch which is connected directly with the load. Could you please show a diagram if you can?
In simple words in the pin of the switch in which you put the MAINS phase, do I have to put the UPS wire on that very same MAINS phase pin of the switch, or do I connect the UPS wire to the Output of the Switch, which is directly connected to the load such as fan, light etc.
Please show a diagram if you can:
http://img.bhs4.com/3a/2/3a2455de36bb27d562fc6a6e2eb037294131ac34_large.jpg
Can you make something like this as a diagram in detail please?
Apart from electrical give connection detail about Electronic system
by my mail
Sir, if we gives input supply to the inverter which is charge the battry but same condition output wire also connected to same point that is live wire……..it meanxe both have current supply……. So in that position can inverter will work or not?
Hi this site is very precious for me
thanks
when power cuts how the power from inverter can’t go back to power grid i.e from service wire to electric poles and poles to transformer ….
how inverter wiring prevents power to go back from house to electric poles and vice versa when no power supply from grid….
other question brother how it take neutral when i unplug inverter from socket…
how neutral will take as no need of neutral wiring when we connect only phase wiring to the output socket in inverter…..
please explain me no need of neutral wiring and how power can’t pass from inverter to electric poles ,to the transformer……
I am waiting for your reply…
Do i have to know the Amp we used and compare it with the UPS we installed?
How to connect same fan from main power and inverter power,send me the diagram
Hi Sir,
could you please confirm whether my inverter (Microtec 850VA EB Model) is compatible with the above diagram.
Thanks and awaiting reply.
Thank you so much for the selfless service of providing such a perfect diagram, which can be understood and applied even by layman.
A person necessarily assist to make seriously articles I’d
state. That is the very first time I frequented your web page
and thus far? I surprised with the analysis you made to create this particular publish amazing.
Magnificent job!
Very nice circuit diagram Wasim….it helped me in installation of inverter…please put provision of bypass also if we dont want to connect inverter circuit to heavy load appliances like AC, fridge…Just tell me for bypassing i m using direct live connection to appliances bypassing inverter but nonlive wire common…is it ok??
Thnak you sir, i got my all ans from above comments
output phase is getting change on my UPS. when main power will not cutoff then its gives phase from right side, after cutoff phase will change on left side pin. why this is happening??? please sir give me the reason and solution off it. thank you
Hi,
When power house goes off & my inverter is connected with common neutral (Single line wire) then how inverter supplies power to load as both phase & neutral from power house got disconnected & how circuit will complete in this case?
AOA. I would like your help with a problem I have recently encountered with my UPS used at home. Yesterday, the UPS began to switch from AC Charging mode to Battery mode repeatedly and electricity started fluctuating with it. I thought there was something wrong with its input, so I changed the socket to which UPS is connected to, and installed a new one. As soon I connected my UPS to the AC input, immediately there was an electrical surge and then my UPS failed to function after that. Now after the replacement of MOSFETs I got my UPS working but when I connected to the input again my UPS stopped working immediately after that. Please any help me. I would be grateful!
Have you checked the Transistor and relays as well?… also, check the overload conditions.
can we connect live wire from grid as well as ups to the same load… I want llights should be ON on both grid n ups…plz guid..
please post connection of a selector switch or changeover using MCB
Hi I have connected mu UPS to my lights circuit breaker and one plug circuit breaker. During load shedding it worked for an hour and half and then tripped. There was a red light with a continuous beep. When the power (load-shedding) was restored I was not able to put my lights on nor was there any power going to the on plug circuit. I have been told that I must unplug my three pin from the UPS and plug into any other plug point for my lights to work on Eskom power. Is there any other way.
Thanks
Our UPS is exact with this diagram at our home.
when we switch on electric water pump motor, ups behaves as WAPDA main light is off. and starts showing to dischargin (i.e. there is no light incoming to ups )
Same case for complete discharging and suddenly light comes, we on fans connected with UPS. UPS then again showing offline (even main WAPDA light is present)
Please let me know a dealer in Chennai who will undertake to carry out the installation of an automatic UPS System for my home use, as per the diagram that you have published.
thanks and regards.
how can i make a separate connection for my inverter and my refrigerator, please give diagrams
Hi thanks allot, i have a question if we want to connect invertor in a home which has three phase connection, then what will the automatic circuit diagram
thanks very helpful diagram ..purchased new inv & battery yesterday..i will install it myself.
give me information how to connect a inverter of house wairing…… plzz short cut solution
How to connect a switch board to both inverter and main line .when power is not available then inverter use and power is available then power use.
I want information about symbol on ups
This is some what useful but still don.t understand.
I have inverter connection in my home ,when raw power goes down,inverter come up automatically.
When raw power is there it will show charging.
I want to know below
When i remove power plug to inverter from raw power,all the power is going down.
after battery fully charges ,i want to remove charging to battery.
How can i do this,need immediate help
I have APC bx600ci-in ups (600v-300w) & it is old while changing battery I got electric shock from battery wire, even I have tested with Tester itcis showing current in battery wires when it is charging…itvis suppose to be DC vote then why I am getting shock while touching..is it problem with ups or itvis normal & I’m trying to connect external battery what max amp of battery I can connect to UPS..
thaks in advance…
vijay
I have APC bx600ci-in ups (600v-300w) & it is 3year old , while changing battery I got electric shock from battery wire, even I have tested with Tester it is showing current in battery wires, when it is charging…it is suppose to be DC volt then why I am getting shock while touching..is it problem with ups or is it normal & I’m trying to connect external battery what max amp of battery I can connect to UPS..
thaks in advance…
vijay
kindly put some diagram of inserting wire in plug ( inside the plug)
Dear please send me your contact no. i want to discus something about ups with you
UPS not working during load shading. I’ using neutral directly from main supply and controlling phase from UPS. It works efficiently when main supply is available but when main supply breakdown, UPS also get off.
Please advise your precious opinion.
It looks like your Phase is not connected to the UPS as well. When Supply is off, Make sure the Phase from UPS is connected to the load as shown in the fig above.
Sir,
I am asking some of the electrians in my area, most of them are not recommend the Method as they said it will be not safe because of common neutral line as it will produce inverter neutral feedback which can cause severe damage.
Is it true?
What happens if Inverter fails or not working condition …..
Thank you very much for your good intimation about generator wiring diagram to main supply!!!!!!!!!!!
Sir pleas show me a invertor conection through a two way switch
Very informative and helpful information sharing through your blog.
very informative and helpfull . but i have a question here
for two out put wiring for UPS .
can the neutral will be common…. i mean if i use a single point for neutral IN for UPS and the neutral Out from UPS also attach to that point . will it cause any problem or not ?
In the one live wire connection, I understand that we’re not taking the neutral from the inverter output(because the neutral is connected to supply neutral). But if there’s a power failure, the devices won’t get neutral connection, right? Then how will this work?
In case of power failure, Battery will supply electricity to the appliances. You can see the neutral is already installed as before which is only a return path for current.
But there is only one wire running from the output of the inverter to the appliances, right? And one end of the appliances is connected to the neutral,(which is open , in case of a fault). The appliance needs phase and neutral, right?
Just imagine, In case of power failure, We connect a battery as a source to the load. As you know that main power supply is disconnected,,,, Now where is the neutral ? From Battery ?
Very nice information. Its highly appreciated.
BUT i need a guideline that i have one load output wire from UPS. My electrician has made a change now that he joined two wires (Red and Black) with that UPS load output wire. He attached one wire (Red) with MCB breaker (for home load) and other wire (black) with Neutral main wire. Now currently, my single UPS output wire has both Neutral and phase joined with each other.
Is it fine?
Previously, there was only one wire as home load.
It seems like that he made a change to UPS by extracting neutral output wire as well . so currently your UPS have load(red) out put and neutral(black) out put . am i right ?
if i am right then load (red) wire from ups goes in to breaker and neutral (black) goes to the neutral wire , which is totally fine.
or it will be easy if you upload any pic of the wiring …..
Thanks for this
Please which CAD software was used for the diagram.
Aoa
Dear how are you??
I want to know about solar system installation of 2000watt load capacity with 24v battery charging.. how can I do it
Please I would like to in the one live common neutral connection, when the utility power is back is the load using utility while the battery is charging
I want to know
is it possible to connect 2 or more inverters in parallel? In order to supply differents loads sharing the neutral cable.
Regards
Why is the black wire connected before RCD in the last diagram. I think it should be connected after the RCD? I also think the power Line from the utility pole i.e. the live wire must be connected to the common busbar segment? let me know if i am wrong? Thank You for the awesome post…