Basic ElectronicsDigital ElectronicsEE SymbolsLogic GatesNotes - Articles

Digital Logic NAND Gate – Universal Gate

Universal Digital Logic NAND Gate

What is Logic NAND Gate?

NAND Gate is a digital logic gate (Also known as Universal gate) produces logic LOW State “0” only and only when there is HIGH State “1” at all of the inputs.

NAND gate is opposite /Invert of AND gate, in other words, if we connect NOT gate to the output of AND gate it will become NAND gate.

Usually, NAND gate has two inputs and 1 output but it can have as many inputs as you want according to your design. It is the reversal of AND Gate.Logic NAND gate

NAND Gate Logic Symbol, Boolean Expression & Truth Table

NAND Gate Symbol

There are 3 types of symbols used for NAND gate all over the world.

American National Standards Institute (ANSI)/ MILITARYDigital Logic NAND Gate Symbol and Boleen Expression

International Electrotechnical Commission (IEC)/EUROPEAN

Deutsches Institut für Normung (DIN)/GERMANY

Boolean Expression

OUT       =             (IN1 . IN2)’           or                OUT           =             (IN1 & IN2’)

or NAND Gate Boolean Expression

Truth Table

NAND Gate Truth Table

NAND Gate Logic Flow Schematic Diagram

NAND Gate LOGIC FLOW SCHEMATIC

Digital Flip-Flops – Types & Operation of Flip-Flops

NAND Gate Construction And Working Mechanism

Resistor-Transistor Logic (RTL)

In Resistor-Transistor logic (RTL), Bipolar junction transistors (BJTs) are used as switching unit. NAND gate schematic in RTL logic is given in the figure below.

In this schematic two NPN BJTs are used in the series configuration.

NPN transistors are active high, which means they will turn on when there is high state “1” at its base input and it will start conducting current. When there is logic LOW state “0” input then it will turn-off.

According to this schematic, when there is logic HIGH state “1” at both input lines, the transistor will switch on and the path from GND to output will be complete, thus resulting in logic LOW state “0” output.

When there is logic LOW state “0” at any or both input lines, then the NPN (one or both) will switch-off, cutting the path to the output and the only path remaining will be Vcc to output. Which will result in logic HIGH state “1” at output.

The truth table of the described schematic is given below.

NAND Gate Truth Table

MOS Logic

In MOS logic, MOSFETs are used as the main switching unit.

Contrary to RTL logic, MOS logic uses MOSFETs instead of BJTs. MOS logic schematic of NAND gate is given below.

NMOSFET is active high, which means it switch-on when there is high state input at its gate and it starts conducting current. And its witches off when its gate input is logic LOW state “0”.

According to this schematic, when there is HIGH state “1” at its both input lines, these both NMOSFETs will switch on, resulting in creating a path from GND to output. Which will result in logic LOW state “0” as output.

When there is a single logic LOW state “0” at its input or both of the inputs are logic LOW state “0” then the NMOSFETs will switch off, resulting in breaking the path from GND to output. And the only path that remains will be the Vdd to output. So the output will become logic HIGH state “1”.

the Truth table of the following design is also given below.

MOS Logic NAND GateNAND Gate Truth Table

NAND Gate From Other Gates

NAND gate function can be achieved with the combination other gates. Some of them are given below.

  1. Invert of AND gate is NAND gate. Thus connecting a NOT gate to the output of AND gate will result in NAND gate as shown in the figure.
  2. NOR is a universal gate i.e. It can be made into NAND gate with specific configuration given in the figure below.

NAND gate function from NOR Gate

NAND Gate is a Universal Gate. The universal gate is a gate which can be implemented into any other logic gate or logic function. Some of the basic gate‘s implementations are given below.

NAND from NOT Gate

NAND gate can be used as NOT gate if we combine its input together into a single input.

In NAND gate all high state inputs lead to LOW output, and all LOW state inputs lead to HIGH input, Which is exactly the same as a NOT gate. NOT gate implementation from NAND gate diagram is given below.

NAND from AND Gate

NAND gate is opposite/invert of AND gate and vice versa. So inverting output of NAND gate will result in AND gate. To invert NAND gate‘s output, we have to use NAND gate with combined inputs which work as Inverter/NOT gate. The figure of implementation of AND gate from NAND gates is given below.

NAND from OR Gate

To better understand the implementation of OR gate using NAND gate one need to know about Boolean algebra and De Morgans law.

Conversion of NAND to OR gate Boolean Algebraic expression is given below.

OUT = (IN1 + IN2)

OUT‘ = (IN1 + IN2)‘                                       taking complement on both sides.

OUT‘ = (IN1‘&IN2‘)                                        De Morgans law

OUT‘‘ = (IN1‘&IN2‘)‘                                      taking complement on both sides.

OUT = {(IN1&IN1)‘&(IN2‘&IN2‘)}‘                  IN1= (IN1&IN1)

So the end result is in the form of NAND gate. As you can see IN1,IN2is NAND (operation) with themselves and then they are NAND (operation) with each other. To better understand observe the figure given below.

OR Gate from NAND Gates

NAND from NOR GATE

NOR gate is invert of ORgate.OR gate design will be the same as illustrated above. There will be an Inverter/NOT gate at the output of OR gate as shown in the figure given below.

Multiple Input NAND Gate

As we have established before that NAND gate’s output will be logic LOW state “0” only and only when there is logic HIGH state “1” at its all input lines.

Multiple Input NAND Gate Truth Table

NAND gate truth table with ‘n’ inputs is given below.

MULTIPLE INPUT NAND GATE Truth Table

 

NOTE: In the table given above “X” means “don’t care”. It can be “1”and it can be “0”. Which means, as long as there is a single input carrying “0”, the output will be always “1” so there is no reason to put a check on other inputs, that’s why it’s called “don’t care X”.

RTL

As you know, BJTs are the switching unit in RTL and they are connected with separate input lines. Hence connecting another NPN BJT in the series configuration can increase the input lines.

A 3-input NAND gate schematic in RTL is shown in the figure given below.

MOS Logic

In MOS logic, input lines are directly connected with NMOSFETs, So increasing the number of NMOSFETs connected in series can potentially increase the number of input lines.

A 3-input NAND gate schematic in MOS logic is given below.

3-input MOS logic NAND gate

From Cascading NAND Gates

Multi-Input NAND gate can be made from cascade setup of 2-input NAND gates.

OUT                =          (IN1&IN2& IN3)‘

OUT                =          ((IN1&IN2)’’ & IN3)’

3-Input NAND Gate Cascaded Setup

Since  (IN1&IN2)‘‘ = (IN1&IN2)

OUT                =          (IN1& IN2& IN3& IN4)’

OUT                =          ((IN1&IN2)’’ & (IN3& IN4)’’)’

4-Input NAND Gate Cascaded Setup

TTL and CMOS Logic NAND Gate IC’s

Commercially up to 8-input NAND gate’s IC are available in the market. Some of the commonly used IC’s details are given below.

TTL Logic NAND Gates

  • 74LS00 Quad 2-input
  • 74LS10 Triple 3-input
  • 74LS20 Dual 4-input
  • 74LS30 Single 8-Input

CMOS Logic NAND Gates

  • CD4011 Quad 2-input
  • CD4023 Triple 3-input
  • CD4012 Dual 4-input

4011 CMOS and 7400 TTL NAND Gate IC (Two-Inputs)

Pinout for 7400 TTL NOR Gate IC

PIN Number Description
1 Input Gate 1
2 Input Gate 1
3 Output Gate 1
4 Input Gate 2
5 Input Gate 2
6 Output Gate 2
7 Ground
8 Output Gate 3
9 Input Gate 3
10 Input Gate 3
11 Output Gate 4
12 Input Gate 4
13 Input Gate 4
14 Positive Supply Voltage VCC

4023 CMOS and 7410 TTL NAND Gate IC (Three-Inputs)

Three-Inputs IC NAND Gate

4012 CMOS and 7420 TTL NAND Gate IC (Four-Inputs)

4068 CMOS and 7430 TTL NAND Gate IC (Eight-Inputs)

Eight Inputs IC NAND Gate

NAND Gate Applications

Logic NAND gate can be used in the following appliances and systems.

  • Security Devices (Burglar or thief alarm system etc)
  • Freezer warning buzzer
  • Light activated systems
  • Automatic watering system
  • Safety thermostat configuration
  • Push Button locks
  • Storage devices like flash drive
  • Cellphones, Computers, Calculators, LCD  & Industrial controllers

You may also read more about Digital Logic gates

Logic NOT Gate – Digital Inverter Logic Gate
Digital Logic OR Gate
Digital Logic AND Gate
Exclusive-NOR (XNOR) Digital Logic Gate
Digital Logic NOR Gate

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button