What is the Difference Between 15-Amp and 20-Amp Outlet?
Difference Between 15-Amp and 20-Amp Outlets and Receptacles
Electrical wiring installations, equipment, devices, and other electrical systems for residential and commercial applications in the United States differ significantly in complexity and design from those used in the rest of the world. For example, the U.S. electric power distribution system commonly uses standard voltages of 120V, 240V, 208V, 277V, and 480V for both single-phase and three-phase systems. In contrast, most countries that follow IEC (International Electrotechnical Commission) standards typically use 230V for single-phase and 415V for three-phase systems.
Similarly, the types of outlets and receptacles used in the U.S. followed by NEMA and NEC (National Electrical Code) vary by voltage (e.g., 120V, 240V) and are quite different from the standardized socket outlets used in IEC-compliant countries.
Before differentiating between 15-amp and 20-amp receptacles, let’s first understand their identification features, terminal configurations, and load-bearing capacities in watts for different types of loads.
- Related Post: Difference Between Socket, Outlet and Receptacle?
What is a 15-Amp Outlet?
A 15-amp outlet is a standard electrical receptacle that is rated to handle a maximum of 15 amperes of current at 120 or 240V volts AC. It is the most commonly used outlet type in residential wiring and is typically installed on 15-amp branch circuits such as lighting points, fans, phone chargers etc.
A 15A circuit is designed to handle a continuous load of 12 amps (80% of its 15A rating) and a maximum non-continuous load of 15 amps. This means you can run a device that draws 12 amps continuously or 15-amps non-continuously for several hours without overloading the circuit. This guideline is in accordance with NEC Articles 210.19(A), 210.20(A), 215.2(A), 215.3, and 230.42(A), which require branch circuits and feeders to be sized based on the continuous and non-continuous load conditions.
Identification of 15-Amp Outlet
The 15-amp outlet is easily recognizable by its two vertical for 120V and horizonal for 240V slots and a grounding hole:
- Left vertical or horizontal slot (Longer or Wider) – Neutral
- Right vertical/horizontal slot (Narrow or Shorter) – Hot
- Round or U-shaped hole below – Ground
Related Post: What is the Right Wire Size for 15A Breaker and Outlet?
15-Amp – 120V Outlet
Both slots for Hot and Neutral are straight and vertical and often labeled “15A, 125V” on the back or side during installation.
Example: NEMA 1-15, and 5-15 receptacles.
A 15-amp receptacle at 120V can be wired to handle a maximum of 1,800 watts for non-continuous loads (15 amps × 120 volts). For continuous loads, the same 15-amp outlet should be limited to 12 amps, which equals a maximum of 1,440 watts (12 amps × 120 volts), following the NEC 80% rule.

15-Amp – 240V Outlet
Both slots for Hot 1 and Hot 2 are horizontal “T” shape and labeled “15A, 250V” on the back, side or front during installation.
A 15-Amp receptacle at 240V can be wired for a maximum non-continuous load of 3600 Watts. For a continuous load, 15-Amp outlet at 240V can be used for a maximum of 2880 Watts.
Example: NEMA 2-15, and 6-15 receptacles. NEMA 14-15 with all three horizonal slots is used with 3-pole, 4-wire system for both 125V/250V.

Related Post: Why is the Neutral Prong or Slot Wider on a Plug or Outlet? A 15-amp outlet is ideal for locations with low electrical load demands. These include: Per NEC requirements, 15-amp outlets can be used in most general-purpose branch circuits as long as the total current draw does not exceed the circuit capacity. A 20-amp outlet is a heavy-duty receptacle capable of handling up to 20 amperes of current at 120 volt or 240 volt AC. It is typically installed in locations where higher power consumption is expected such as garage, kitchen, laundry, workshops etc. A 20-amp circuit is designed to safely handle a continuous load of up to 16 amps (which is 80% of its rated capacity) and a maximum non-continuous load of 20 amps. This means you can operate a device drawing up to 16 amps continuously, or up to 20 amps for a non-continuous (intermittent) load, without overloading the circuit. (As per NEC 210.19(A), 210.20(A), 215.2(A), 215.3, and 230.42(A) for 125% OCPD or 80% load for sizing branch circuits and feeders in continuous and non-continuous load conditions. The 20-amp outlet is easily recognizable by its vertical for Hot and “T” shaped for Neutral for 120V and horizonal for 240V slots and a grounding hole: The slot for HOT or Line 1 is vertical while the “T” shaped slot is for HOT 2 or Neutral in case of 125V. The nameplate sticker shows the printed value as “20A-125V”. Example: NEMA 5-20 receptacle. On the other hand, NEMA 10-20 in 2-pole, 3-wire, 10-20 in 3-pole, 3-wire 125V and 14-20 in 3-pole, 4-wire are used for both 125V and 250V applications. A 20-amp receptacle at 120V can be wired to handle a maximum of 2,400 watts for non-continuous loads (20 amps × 120 volts). For continuous loads, the same 20-amp outlet should be limited to 16 amps, which equals a maximum of 1,920 watts (16 amps × 120 volts), in accordance with the 80% rule specified by the NEC. The horizontal slot is for Hot or Line 1, while the “T”-shaped slot is used for Hot 2 (in 240V applications) or Neutral (in 120V applications). The nameplate label typically shows the printed rating as “20A–250V”. Example: NEMA 6-20 receptacle. NEMA 2-20 (with a horizontal and vertical slot) is used in 2-pole, 2-wire system, NEMA 10-20 is used in 2-pole, 3-wire in 125/250V. NEMA 14-20 is used in 3-pole, 4-wire applications. A 20-amp receptacle operating at 240 volts is rated for a maximum non-continuous load of 20 amperes, which equates to 4800 watts. When dealing with continuous loads, this same 20-amp receptacle at 240 volts should not exceed 16 amperes, or 3840 watts.
A 20-amp outlet is required or recommended in areas where heavier electrical loads are expected: In these locations, 20-amp circuits and outlets help prevent nuisance tripping and overheating due to high power draw. While 15-amp outlets are suited for standard household use, 20-amp outlets are better equipped for demanding appliances and workspaces. Beside the terminals and slots identification, following are the key differences between a 15-amp and 20-amp outlets and receptacles.
Related Posts: Resources & Tutorials:
Where to Use 15-Amp Outlet
What is a 20-Amp Outlet?
Identification of 20-Amp Outlet
20-Amp – 120V Outlet

20-Amp – 240V Outlet

Where to Use 20-Amp Outlet
Differences Between 15-Amp and 20-Amp Outlet
Feature
15-Amp Outlet
20-Amp Outlet
Maximum Current Rating
15 Amperes
20 Amperes
Common Wire Size
14 AWG Cu.
12 AWG Cu.
Neutral Slot
Vertical
T-shaped (horizontal + vertical)
Plug Compatibility
Only accepts 15-amp plugs
Accepts both 15-amp and 20-amp plugs
Typical Applications
General household use
High-power appliances and tools
Circuit Type
15-Amp Branch Circuit
20-Amp Branch Circuit
Code Compliance
Used in general rooms
Required in kitchens, garages (per NEC 210.11(C))







