How to Calculate the Suitable Capacitor Size in µ-Farads & kVAR for P.F Improvement

How to Find the Right Size Capacitor Bank Value in both kVAR and Microfarads for Power Factor Correction – 3 Methods

As we got lots of emails and messages from the audience to make a step by step tutorial which shows how to calculate the proper size of a capacitor bank in kVAR and micro-farads for power factor correction and improvement in both single phase and three phase circuits.

This article will show how to find the right size capacitor bank in both Microfarads and kVAR to improve the existing “i.e. lagging” P.F to the targeted “i.e. desired” as corrected power factor has multiple advantages. Below, we showed three different methods with solved examples to determine the exact value of capacitance of a capacitor for P.F correction.

How to Calculate the Suitable Capacitor Size in µ-Farads & kVAR for P.F Improvement

 

Now let’s begin and consider the following examples…

How to Calculate the Capacitor Value in kVAR?

Example: 1

A 3 Phase, 5 kW Induction Motor has a P.F (Power factor) of 0.75 lagging. What size of Capacitor in kVAR is required to improve the P.F (Power Factor) to 0.90?

Solution #1 (Simple Method using the Table Multiplier)

Motor Input = 5kW

From Table, Multiplier to improve PF from 0.75 to 0.90 is 0.398

Required Capacitor kVAR to improve P.F from 0.75 to 0.90

Required Capacitor kVAR = kW x Table 1 Multiplier of 0.75 and 0.90

= 5kW x 0.398

= 1.99 kVAR

And Rating of Capacitors connected in each Phase

= 1.99kVAR / 3

= 0.663 kVAR

Solution # 2 (Classic Calculation Method)

Motor input = P = 5 kW

Original P.F = Cosθ1 = 0.75

Final P.F = Cosθ2 = 0.90

θ1 = Cos-1 = (0.75) = 41°.41; Tan θ1 = Tan (41°.41) = 0.8819

θ2 = Cos-1 = (0.90) = 25°.84; Tan θ2 = Tan (25°.50) = 0.4843

Required Capacitor kVAR to improve P.F from 0.75 to 0.90

Required Capacitor kVAR = P (Tan θ1 – Tan θ2)

= 5kW (0.8819 – 0.4843)

= 1.99 kVAR

And Rating of Capacitors connected in each Phase

1.99 kVAR / 3 = 0.663 kVAR

Note: Tables for Capacitor Sizing in kVAr and microfarads for PF Correction

The following tables (given at the end of this post) have been prepared to simplify kVAR calculation for power factor improvement. The size of capacitor in kVAR is the kW multiplied by factor in table to improve from existing power factor to proposed power factor. Check the others solved examples below.

Example 2:

An Alternator is supplying a load of 650 kW at a P.F (Power factor) of 0.65. What size of Capacitor in kVAR is required to raise the P.F (Power Factor) to unity (1)? And how many more kW can the alternator supply for the same kVA loading when P.F improved.

Solution #1 (Simple Table Method using Table Multiple)

Supplying kW = 650 kW

From Table 1, Multiplier to improve PF from 0.65 to unity (1) is 1.169

Required Capacitor kVAR to improve P.F from 0.65 to unity (1).

Required Capacitor kVAR = kW x Table 1 Multiplier of 0.65 and 1.0

= 650kW x 1.169

= 759.85 kVAR

We know that P.F = Cosθ = kW/kVA . . .or

kVA = kW / Cosθ

= 650/0.65 = 1000 kVA

When Power Factor is raised to unity (1)

No of kW = kVA x Cosθ

= 1000 x 1 = 1000kW

Hence increased Power supplied by Alternator

1000kW – 650kW = 350kW

Solution # 2 (Classic Calculation Method)

Supplying kW = 650 kW

Original P.F = Cosθ1 = 0.65

Final P.F = Cosθ2 = 1

θ1 = Cos-1 = (0.65) = 49°.45; Tan θ1 = Tan (41°.24) = 1.169

θ2 = Cos-1 = (1) = 0°; Tan θ2 = Tan (0°) = 0

Required Capacitor kVAR to improve P.F from 0.75 to 0.90

Required Capacitor kVAR = P (Tan θ1 – Tan θ2)

= 650kW (1.169– 0)

= 759.85 kVAR

How to Calculate the Capacitor Value in Microfarad & kVAR?

The following methods show that how to determine the required capacitor bank value in both kVAR and Micro-Farads. In addition, the solved examples also show that how to convert the capacity of a capacitor in microfarad to kVAR and kVAR to microfarad for P.F. This way, a right size capacitor bank can be installed in parallel to each phase load side to obtain the targeted power factor.

Example: 3

A 500 volts 60 c/s single phase motor takes a full load current of 50 amp at P.F 0.86 lagging. The motor power factor has to be improved to 0.94 by connecting capacitor bank across it. Calculate the required capacity of capacitor in both kVAR and μ-Farads?

Solution:

(1) To find the required capacity of Capacitance in kVAR to improve P.F from 0.86 to 0.94 (Two Methods)

Solution #1 (Table Method)

Motor Input = P = V x I x Cosθ

                              = 500V x 50A x 0.86

                              = 21.5kW

From Table, Multiplier to improve PF from 0.86 to 0.94 is 0.230

Required Capacitor kVAR to improve P.F from 0.86 to 0.94

Required Capacitor kVAR = kW x Table Multiplier of 0.86 and 0.94

= 21.5kW x 0.230

= 4.9 kVAR

Solution # 2 (Calculation Method)

Motor Input = P = V x I x Cosθ

                              = 500V x 50A x 0.86

                              = 21.5kW

Actual or existing P.F = Cosθ1 = 0.86

Required or target P.F = Cosθ2 = 0.94

θ1 = Cos-1 = (0.86) = 30.68°; Tan θ1 = Tan (30.68°) = 0.593

θ2 = Cos-1 = (0.95) = 19.94°; Tan θ2 = Tan (19.94°) = 0.363

Required Capacitor kVAR to improve P.F from 0.86 to 0.95

Required Capacitor kVAR = P in kW (Tan θ1 – Tan θ2)

= 21.5kW (0.593 – 0.363)

= 4.954 kVAR

(2) To find the required capacity of Capacitance in Farads to improve P.F from 0.86 to 0.97 (Two Methods)

Solution #1 (Table Method)

We have already calculated the required Capacity of Capacitor in kVAR, so we can easily convert it into Farads by using this simple formula

Required Capacity of Capacitor in Farads/Microfarads

Putting the Values in the above formula

= (4.954 kVAR) / (2 x π x 60Hz x 5002V)

= 52.56 μF

Solution # 2 (Calculation Method)

kVAR = 4.954 … (i)

We know that;

IC = V / XC

Whereas XC = 1 / 2π x f x C

IC = V / (1 / 2π x f x C)

IC = V x 2π x f x C

= (500V) x 2π x (60Hz) x C

IC = 188495.5 x C

And,

kVAR = (V x IC) / 1000 … [kVAR = ( V x I) / 1000 ]

= 500V x 188495.5 x C

IC = 94247750 x C … (ii)

Equating Equation (i) & (ii), we get,

94247750 x C = 4.954 kVAR x C

C = 4.954 kVAR / 94247750

C = 78.2 μF

Example 4

What value of Capacitance must be connected in parallel with a load drawing 1kW at 70% lagging power factor from a 208V, 60Hz Source in order to raise the overall power factor to 91%.

Solution:

You can use either Table method or Simple Calculation method to find the required value of Capacitance in Farads or kVAR to improve Power factor from 0.71 to 0.97. So We used the table method in this case.

P = 1000W

Actual Power factor = Cosθ1 = 0.71

Desired Power factor = Cosθ2 = 0.97

From Table, Multiplier to improve PF from 0.71 to 0.97 is 0.741

Required Capacitor kVAR to improve P.F from 0.71 to 0.97

Required Capacitor kVAR = kW x Table Multiplier of 0.71 and 0.97

= 1kW x 0.741

= 741 VAR or 0.741 kVAR (required Capacitance Value in kVAR)

Current in the Capacitor =

IC = QC / V

= 741kVAR / 208V

= 3.56A

And

XC = V / IC

= 208V / 3.76 = 58.42Ω

C = 1/ (2π x f x XC)

C = 1 (2π x 60Hz x 58.42Ω)

C = 45.4 μF (required Capacitance Value in Farads)

Capacitor kVAR to μ-Farad & μ-Farad to kVAR Conversion

The following formulas are used to calculate and convert capacitor kVAR to Farads and Vice Versa.

Required Capacitator in kVAR

Convert Capacitor Farads & Microfarads in VAR, kVAR and MVAR.

Required Capacitor in Farads/Microfarads.

Convert Capacitor kVAR in Farads & Microfarads

Where:

Good to Know:

Following are the important electrical formulas used in Power factor improvement calculation.

Active Power (P) in Watts:

Apparent Power (S) in VA:

Reactive Power (Q) in VA:

Power Factor (from 0.1 to 1)

And

Related Posts:

Capacitor Bank Sizing & PF Correction Calculators

If the above two methods seem a little bit tricky (which should not at least), you may then use the following online power factor kVAR and microfarads calculators made by our team for you.

Capacitor Sizing Chart & Table for Power Factor Correction

The following power factor correction chart can be used to easily find the right size of capacitor bank for desired power factor improvement. For example, if you need to improve the existing power factor from 0.6 to 0.98, just look at the multiplier for both figures in the table which is 1.030. Multiply this number with the existing active power in kW. You can find the real power by multiplying the voltage to the current and the existing lagging power factor i.e. P in Watts = Voltage in volts x Current in Amps x Cosθ1. This easy way, you will find the required value of capacitance in kVAR which is needed to get the desired power factor.

How to Calculate the Suitable Capacitor Size in Farads & kVAR for Power factor Improvement (Easiest way ever)
Table – from 0.01 to 0.25
Capacitor Bank Sizing Chart and Table
Table – from 0.26 to 0.50
Power Factor Improvement Table
Table – from 0.51 to 0.75
Power Factor Correction Table
Table – from 0.76 to 1.0

Here is the whole table if you need it to download as a reference.

Table for How to Calculate the Suitable Capacitor Size in µ-Farads & kVAR for P.F Improvement
The whole Table – from 0.10 to 1.0 (Click image to enlarge)

Related Posts

↑
Exit mobile version