What is the Right Wire Size for a 30A Breaker and Outlet?
How to Determine the Suitable Wire Size for a 30A Breaker and Outlet Based on NEC?
Selecting the appropriate wire size and breaker for a 30A circuit is crucial for ensuring safety of the operator, efficiency and protection of the device, and compliance with National Electrical Code (NEC) – NFPA 70 standards.
A 10 AWG copper wire is generally the most suitable choice for a 30-amp circuit. In case of aluminum, the right wire size is 8 AWG.. Understanding the factors involved in wire selection and the applications of a 30A circuit will help ensure that electrical installations are both safe and effective.
What is the Suitable Wire Size for a 30A Breaker and Outlet?
When installing a 30-amp breaker and outlet, it is essential to select the correct wire size to ensure safety, efficiency, and compliance with the National Electrical Code (NEC) – NFPA 70 standards.
The NEC specifies that the minimum wire size for a 30A breaker is 10 AWG (American Wire Gauge) copper or 8 AWG aluminum.
Based on NEC Table 310.16, the ampacity of the #10 AWG copper and # 8AWG aluminum wire size respectively are:
#10 AWG Copper
- 30 amps at 60°C (140°F)
- 35 amps at 75°C (167°F)
- 40 amps at 90°C (194°F)
#8 AWG Aluminum
- 35 amps at 60°C (140°F)
- 40 amps at 75°C (167°F)
- 45 amps at 90°C (194°F)
Copper conductors are preferred for most residential and commercial applications due to their lower resistance and better conductivity. Therefore, the suitable wire size for a 30-amp circuit is 10 AWG copper wire. Other than copper, an 8 AWG aluminum wire is necessary because it has higher resistance than copper, requiring a larger conductor size to safely carry the same current.
According to the NEC – 310-16, add 20% of additional ampacity for every 100 feet (30.50 meters) of distance (for example between main panel and subpanel) to counter the voltage drop.
How to Select the Right Wire Size for a 30A Breaker and Outlet?
Selecting the right wire size involves considering several factors, including the type of conductor material (copper or aluminum), the length of the circuit, ambient temperature, and the installation environment (e.g., in conduit or free air).
Suppose you have a 2-pole, 30A breaker installed in the main panel, and you want to wire it to a 30A outlet or load circuit. Follow these steps to find the correct wire size for 30A breakers and outlets for continuous and non-continuous load circuits according to the NEC guidelines, which is based on the breaker, not the outlet or load circuit.
Example:
Continuous Load Circuit
The general rule of thumb or 125% rule (also known as the continuous load rule) in the NEC states that the rating of the maximum overcurrent protection device (MOCP) e.g. fuse or circuit breaker should handle 125% of the continuous load. As a safety factor, no more than 80% of the continuous load should be connected to the Overcurrent Protection Device (OCPD) i.e. fuse or breaker.
30A × 80% = 24A
Based on the calculation, no more than 24A of continuous load circuit should be connected to the 30A breaker. The same applies to a 30A outlet.
When the minimum circuit ampacity (MCA) i.e. load circuit’s amperes are 24A, to find the correct breaker size for this circuit:
24A × 125% = 30A
According to NEC Table 310.16, the 10 AWG wire size can carry 30A at 60°C (140°F) and 35A at 75°C (167°F).
Non-continuous Load Circuit
For non-continuous loads (e.g., lighting circuits), the conductor size should be no less than 100%. The same applies to overcurrent protection devices (OCPDs).
Hence, a 30A breaker can be used for a maximum of 30A circuits (e.g., outlets and lighting points) while considering the ambient temperature rating [Refer to 110.14(C) and 310.15(B)(2)].
How Many Amps Can a 30A Breaker Handle Safely?
A 30-amp breaker is designed to handle a maximum of 30 amps current safely. The NEC specifies that breakers should not be loaded to more than 80% of their rated capacity for continuous loads (defined as a load that lasts for three hours or more).
30A × 80% = 24A
For a 30A breaker, this equates to 24 amps of continuous load. For short, non-continuous loads, the breaker can handle up to 30 amps safely.
- Use a 30A breaker and outlet for a 24A continuous load circuit.
- Use a 30A breaker and outlet for a 30A non-continuous load circuit.
The above ratings of the breaker and outlet, and the ampacity of the wire size, comply with the National Electrical Code (NEC) – Sections 210.19(A), 215.2, and 230.42(A) for continuous and non-continuous loads, and 110.14(C) for ambient temperature.
The above calculations are based on NEC Table 310.16 and 240.4(A) through (G), illustrating that the 10 AWG copper wire size can carry 30A at 60°C (140°F) and 35A at 75°C (167°F).
How Many Watts Can a 30A Breaker and Outlet Hold?
To calculate the power capacity of a 30-amp breaker, use the following formula.
120V Circuit
In a standard 120V circuit, a 30A breaker can hold the maximum power:
30 A × 120 V = 3600 W
If we apply the safety factor of 80% of the load to a rated breaker and outlet:
30A × 80% = 24A
It shows that no more than 2,880 watts of load should be connected to a 30A breaker and outlet:
24A × 120V = 2,880 watts
It means, you may use 30A breaker with a 120V, 2.5kW water heater element.
240V Circuit
A 30A breaker in 240V circuit can hold the maximum power:
30 A × 240 V= 7200 W
Applying the safety factor of 80% of the load to a rated breaker and outlet:
30A × 80% = 24A
Based on the above calculation, no more than 5,760 watts of load having 24A of current should be connected to a 30A breaker and outlet:
24A × 240V = 5,760 watts
For example, you may use a 30A breaker with a 240V, 5kW or 5.5kW water heater element.
These calculations assume that the breaker is not continuously loaded to 100% of its capacity. For continuous loads, the safe wattage is 80% of these values:
- 120V Circuit (Continuous Load): 2,880 W
- 240V Circuit (Continuous Load): 5,760 W
How Many Outlets Can be Installed on a 30A Breaker?
Generally, a 30A breaker can support 8 to 12 outlets, especially when multiple general-purpose outlets are used on the circuit.
The NEC does not specify a maximum number of outlets that can be installed on a 30-amp circuit. However, for practical purposes, it is common to install only a few outlets on such a circuit, especially when it is dedicated to high-demand appliances. For example, a 30A circuit might be used to supply a single appliance, like a large air conditioner, or several outlets in a workshop where heavy-duty tools are used.
It is important to note that general-purpose circuits in residential settings (like those for standard outlets and lights) typically use 15A or 20A breakers. A 30A breaker should be reserved for circuits that require high current, and only outlets rated for 30 amps should be connected to it.
For more details, refer to the NEC table – 210.21(B)(3) for receptacles rating for various size circuits which clarify the circuit rating and receptacle rating in amperes.
Suitable Types of Cables for a 30-Amp Breaker and Outlet
For a 30-amp breaker, the suitable cable types include:
- NM-B Cable (Non-Metallic Sheathed Cable): Commonly used in residential wiring, NM-B cable with 10 AWG copper wire is suitable for 30A circuits. It should only be used in dry, indoor environments.
- THHN/THWN Wire: This type of wire is used in conduit and is suitable for both indoor and outdoor installations. THHN/THWN wire with 10 AWG copper conductors is suitable for a 30A circuit.
- UF-B Cable (Underground Feeder): UF-B cable is suitable for direct burial and outdoor use. A 10 AWG copper UF-B cable is appropriate for a 30A circuit.
Applications of a 30-Amp Breaker and Outlet
A 30-amp breaker and outlet are typically used for specific high-demand applications, such as:
- HVAC Systems: Central air conditioning units, heat pumps, and other HVAC equipment often require a dedicated 30A circuit.
- Electric Water Heaters: Many electric water heaters require a 30A breaker.
- Heavy-Duty Appliances: Clothes dryers, large air compressors, and other heavy-duty electrical appliances may need a 30A circuit.
- Workshops: A 30A circuits are commonly used in workshop setting for general applications.
Good to Know:
Resources:
Wire Sizes for Standard Breakers, Outlet and Branch Circuits
- Wire Size for 15A Breaker and Outlet
- Wire Size for 20A Breaker and Outlet
- Wire Size for 25A Breaker and Load
- Wire Size for a 30A Breaker and Outlet… (You are Here)
- Wire Size for a 35A Breaker and Load
- Wire Size for a 40A Breaker and Load
- Wire Size for 45A Breaker and Load
- Wire Size for 50A Breaker and Outlet
- Wire Size for 55A Breaker and Load
- Wire Size for 60A Breaker and Outlet
- Wire Size for 70A Breaker and Load
- Wire Size for 80A Breaker and Load
- Wire Size for 90A Breaker and Load
- Wire Size for 100A Breaker and Load
Sizing Wires for for General Wiring Installations
- Right Wire Size for100A Service Entrance and Load in AWG for 120V/240V Panel
- What is the Right Wire Size for a 4.8kW, 240V Range: #10 or #12?
- How to Find the Proper Size of Circuit Breaker?
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Size a Breaker and Wires in AWG with EGC for Load?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Size a Branch Circuit Conductors with Protection?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- How to Size Motor Starter & Contactor – NEMA & NEC
- How to Size Motor Branch Circuit Conductors and Cables
- How to Determine the Number of Circuit Breakers in a Panelboard?
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- American Wire Gauge “AWG” Chart – Wire Size & Ampacity Table
- American Wire Gauge “AWG” Calculator – AWG Size Chart & Table
- Standard Wire Gauge “SWG” Calculator – SWG Size Chart & Table
- AWG/SWG to mm/mm2, inch/inch2 & kcmil Calculator & Conversion
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- How to Wire an Outlet Receptacle? Socket Outlet Wiring Diagrams
- Wire and Cable Size Calculator in AWG
- Electrical Wire and Cable Size Calculator (Copper & Aluminum)
Wiring 30A Outlets with 30A Breakers
- How to Wire a 30A – 120V Outlet – NEMA 5-30 Receptacle
- How to Wire a 30A – 240V Outlet – NEMA 6-30 Receptacle
- How to Replace a 30A – 120/240V Outlet – NEMA 10-30R?
- How to Wire a 30A – 125/250V Outlet – NEMA 14-30 Receptacle
- How to Wire a 30A – 125V Outlet – NEMA TT-30 Receptacle








Watts = Amps X Volts
Only with resistive loads. Ex. a motor would need the formula of
Watts = Amps X Volts X Power Factor
That is already mentioned in the “Good to know” section. The formula is only applicable to resistive load circuits. For inductive and capacitive circuits, refer to the related tables and sections in NEC.