Part 6 – Sizing Motor Feeder Conductors and Cables

How to Determine the Correct Wire Size for Feeder Supplying Multiple Motors?

In previous sections on motor circuit calculations, we determined conductor sizing, overcurrent protection, and overload protection with solved examples for a single-motor circuit. In this section, we will determine the sizing of a feeder circuit supplying multiple motors on the same phase.

Sizing Feeder Conductor Supplying Multiple Motors

NEC 430.53 permits two or more motors on the same branch circuit in accordance with 430.53(A) through (D). According to 430.25, the ampacity of conductors supplying multi-motor and other load circuits must not be less than the marked ampacity on the equipment nameplate, as specified in 430.7(D). If the nameplate rating is unavailable, the conductor ampacity must be determined based on 430.24.

According to the 430.24, the ampacity of conductors supplying multiple motors must not be less than:

According to 430.26, If all motors do not operate simultaneously (all motor running at a time), feeder demand factors may be applied to reduce the calculated ampacity per NEC 430.24. However, the conductors must have sufficient ampacity to handle the maximum load based on the size and number of motors.

Sizing Motor Feeder Conductors and Cables

Example 1 – Sizing Feeder Conductors for Single Phase Motors

Determine the required feeder conductor size (THHN) with a 75°C terminal rating for a system supplying two 230V single-phase motors: one rated at 2 HP and the other at 10 HP.

Solution:

1: Determine FLC of Each Motor

Based on Table 430.248, the full-load current in amperes for single-phase AC motors at 230V are as follow:

2: Determine the Total Ampacity

The ampacity of feeder circuit supplying multiple motors can be calculated in accordance with 430.24(A). Since the largest motor is 50A based on FLC;

50A × 1.25 = 62.5A.

Now, sum app with the FLC of other motor(s).

62.5A + 12A = 74.5A.

2: Determine the Size of Feeder Conductors

The suitable wire size can be selected from the Table 310.16. For a feeder supplying 74.5A of current with a 75°C terminal rating, the right size of feeder conductor is #4AWG cupper or #6AWG aluminum (THHN).

Example 2 – Sizing Feeder Conductors for Multi-phase Motors

What is the required size of feeder conductor (THHN) at 75°C terminal rating supplying the following multiphase motors?

Solution:

1 – Find the Full Load Current of Each Motor

The full load current (FLC) can be determined using Table 430.248 and 430.150 for single-phase and three-phase AC motors respectively.

2 – Calculate the Total Ampacity

As previously stated, the ampacity of conductors supplying multiple motors must not be less than 125% of the full-load current (FLC) of the highest-rated motor (per NEC 430.6(A) and 430.24). Additionally, the FLC values of all other motors connected to the same phase must be added to the FLC of highest-rated motor multiplied by 1.25 (per NEC 430.6(A)).

Thus, the total ampacity is calculated as follows:

(52A×1.25) + 44A + 44A + 20A = 173A.

3: Size The Feeder Conductors

The size of feeder conductor supplying 173A of multiple motors circuits with a 75°C terminal rating, Table 310.16 suggests (THHN) conductors for the feeder:

Note:

When sizing a feeder conductor supplying multiple motors, only the motors on the same phase should be considered for additions of FLCs. This is why our calculations include four motors instead of all seven.

The same rule applies when sizing protection for feeder conductors, as they must be protected against motor overload and overcurrent caused by short circuits, and ground faults (Discussed in the next part).

Series Overview: Motor Circuit Calculations

Resources & Tutorials:

Wire Sizing Guides

↑
Exit mobile version