Electrical DesignElectrical WiringHow ToMotorsProtection

Part 8 – Sizing Motor Feeder Protection and OCPD’s Devices

How to Determine the Size of Feeder Protection Supplying Several Motors?

In the previous section, we discussed sizing feeder conductors for multiple motors. This section will explain the step-by-step process for selecting protective devices, such as fuses and circuit breakers, for a feeder supplying multiple motors. Remember, general feeder circuits and motor feeders serve different purposes and follow different calculation methods.

Sizing Motor Feeder Protection

Sizing Feeder Protection Supplying Multiple Motors

Feeder protection safeguards feeder conductors from overcurrent due to short circuits and ground faults. Branch circuit protection protects branch circuit conductors from the same hazards. Overload protection, installed near the motor, protects the motor circuit itself. For more details, refer to Figure 430.1 in the NEC to understand the different parts of a motor circuit with associated protection.

A feeder must be protected using a protective device. The device’s rating must not exceed the largest rating of the branch-circuit short-circuit and ground-fault protective device. Additionally, when determining the protective device rating, the sum of the full-load currents (FLC) of other motors connected to the same phase must be included (430.62(A)).

Feeder conductors for motors are sized based on NEC 430.24. The maximum allowable rating for a specific protective device is determined by 430.52 or 440.22(A).

When a feeder supplies two or more branch circuits where the same branch-circuit short-circuit and ground-fault protective device rating is used, one of these devices is considered the largest for calculation purposes. However, an exception applies under 340.90, where a single protective device provides both overcurrent and overload protection for the motor control circuit.

Good to Know:

  • Motor feeder conductors are protected against overcurrent caused by short circuits and ground faults.
  • The feeder protective device does not protect against motor overload. A separate overload protective device is required for overload protection.

According to 430.63, when a feeder supplies both motor loads and other load circuits, the rating of the feeder’s protective device must not be less than the sum of the other loads plus the following:

  • The rating permitted by 430.52 for a single motor.
  • The rating permitted by 440.22 for a single hermetic refrigerant motor-compressor.
  • The rating permitted by 430.62 for two or more motors.

Example 1 – Sizing Feeder Protection Supplying Multiple Motors

Determine the required size of inverse-time breaker as a feeder protection device. The feeder supplying the following two single phase motors operated at 230V.

  • 1.5 HP
  • 2 HP

Solution:

1: Determine FLC of Each Motor

The full load current (FLC) of single phase motors are determined using Table 430.248. The FLC of 1-phase motors at 230V supply:

  • FLC of 1.5 HP Motor = 10A
  • FLC of 2 HP Motor = 12A

2: Size the the Branch Circuits (Optional Step)

Sizing of branch circuit for motor is determined using Tables 430.147 through 430.150 based on FLC and Table 310.16. for conductor sizing.

  • 10A × 125% = 12.5   ……   (for 1.5 HP Motor)
  • 12A × 125% = 15A   ……   (for 2 HP Motor)

Referencing to the Table 310.16, the wire size at 60°C for both branch circuits supplying 1.5 HP and 2 HP motors is #14AWG Cu. or #12AWG Al.

3: Determine the Branch Circuit Protection

The branch circuit protection for both motors are sized in accordance with 430.52(C)(1), Table 430.52, & 240.6(A) as follow:

  • 10A × 2.5 = 25A   ……   (for 1.5 HP Motor)
  • 12A × 2.5 = 30A   ……   (for 2 HP Motor)

4: Size the Feeder Conductors (Optional Step)

The ampacity of feeder circuit supplying multiple motors can be calculated in accordance with 430.24(A). Since the largest motor is 30A based on FLC;

30A × 1.25 = 37.5A.

Now, sum app with the FLC of other motor(s).

37.5A + 10A = 47.5A.

The size of feeder conductor is determined using Table 310.16. For 47.5A, the size of feeder conductor is #8AWG cupper or aluminum (THHN) at 75°C.

5: Determine the Size of Feeder Protection

As stated above, the rating or setting of protective device should be less than the size of the branch circuit protection used for the largest motor (30A) plus the FLA of other motor(s) (25A). (430.62).

Hence (continue from step 2);

30A + 25A = 45A.

Since, the size of protection device for feeder conductors should be less than the above calculated value, the next down available size of standard breaker is 40A.

Feeder Protection Breaker = 40A

Good to Know:

You may notice that we have selected the next size down for overcurrent protection instead of the next size up. This is because the NEC requires that feeder conductor protection must not exceed the branch circuit protection rating.

Motor feeder protection is different from motor overload protection:

  • Motor feeder protective devices protect only against short circuits and ground faults, not overload.
  • Motor overload protection is handled separately (discussed in previous part).

Note:

When sizing a feeder protection supplying multiple motors, only the motors on the same phase should be considered for additions of FLCs. This is why our calculations include four motors instead of all seven.

The same rule applies when sizing feeder conductors supplying multiple motors, as they must be protected against motor overload and overcurrent caused by short circuits, and ground faults (Discussed in the previous part).

Series Overview: Motor Circuit Calculations

Resources & Tutorials:

Wire Sizing Guides

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button