ControlElectrical DesignElectrical WiringHow ToMotorsProtection

Part 11 – Sizing Disconnecting Means for Motor & Controller

How to Size Disconnecting Switch, Fuse & Breaker for Motors and Controllers

Disconnecting Means for Motors & Controllers

Although we know that the motor disconnecting means can be sized based on the full load current using NEC Tables 430.247, 430.248, 430.249, and 430.250. The similar approach is used to size the motor’s conductors, short-circuit, and ground-fault protection. Aside from the similarity, the NEC has specific requirements for sizing, selecting, and installing disconnects for motor circuits.

Sizing Disconnecting Means for Motor & Controller

Good to Know:

Each motor and motor controller must have a disconnect switch within sight of the motor and its controller, respectively – 430.101 & 430.75(A). If the controller’s disconnect is within sight of the motor, it can also serve as the disconnect for the motor (430.102(B)). Additionally, both the motor and motor controller must be easily accessible (430.102 & 430.107).

The disconnecting means should be within sight of the motor. If the disconnecting means is not within sight of a motor rated at 1,000V or less, a second disconnecting means is required within 50 feet (15 m) and within sight of the motor, with a lockable feature – 430.102(B)(1).

According to 430.110, one of the following seven types of disconnects listed in 430.109(A)(1) through (7) can be used for a motor or motor controller (starter/contactor):

  1. Motor-circuit switch rated in HP
  2. Molded-case circuit breakers
  3. Molded-case switches
  4. Instantaneous-trip circuit breaker
  5. Self-protected combination motor controller
  6. Manual motor controller (fuses, HP-rated plug and receptacle)
  7. System isolation equipment

For stationary motors rated 1⁄8 HP or less, the branch circuit overcurrent protective devices (OCPDs) is permitted to be used as the disconnecting means (430.109(B)).

As per 430.109(C), if a stationary motor is rated 2 HP or less and operates at 300V or less, one of the following can serve as a disconnect for the motor circuit:

  • A general-use AC snap switch (not a DC or AC-DC switch) with an ampere rating of at least twice the motor’s full-load current (FLC).
  • The motor’s FLC must not exceed 80% of the switch’s ampere rating. In other words, the switch’s ampere rating must be at least 125% of the motor’s FLC, as listed in Tables 430.247 through 430.250. – 480.83(C)(2)
  • A listed manual motor controller, marked “suitable for motor disconnect,” with an HP rating not less than the motor’s HP.

According to 430.109(F), additional disconnecting means (such as a plug and receptacle, cord connector, or flanged surface inlet) can be used as a motor disconnect if they are HP-rated, meaning their rating must be at least equal to the motor’s HP.

As per 430.110:

  • The current rating and interrupting capacity of the disconnecting means for single motor shall be at least 115% of the full-load current (FLC) of the motor circuit rated for 1,000V nominal or less. This rule does not apply to a listed unfused motor-circuit switch with a horsepower (HP) rating equal to the motor HP – 430.110(A).
  • For torque motors, the disconnecting means shall have a rating of 115% of the nameplate full-load amperes (FLA) – 430.110(B).
  • For two or more motors, or a combination of a motor and other loads controlled by a single disconnecting means, the current and horsepower ratings of the combined load shall be determined in accordance with 430.110(C)(1), (2), and (3).

Good to know:

  • If the rating of small motors is not covered by Tables 430.257 through 430.250, the locked rotor current (LRC) should be assumed to be six times the full-load current (FLC) of the motor.
  • A switch or circuit breaker can serve as both the disconnecting means for motors and the control device if it meets the requirements of 430.111(A) and is one of the specified types listed in 430.111(B).

The controller disconnect can also serve as the disconnect for the control circuit conductors if the control circuit conductors are tapped from it (430.102(A)). However, if the control circuit conductors are not tapped from the controller disconnect and are instead supplied by a Class 1 control circuit, a separate disconnect must be installed adjacent to the controller disconnect.

Motor controllers can include molded-case circuit breakers, molded-case switches e.g. contactors, and starters with overload relays (430.83(A)). Any other device used as a motor controller must have an HP rating equal and suitable for the specific motor.

If a general-use snap switch is used as a motor controller, the motor controller’s ampere rating must not exceed 80% of the switch’s ampere rating. In other words, the switch’s ampere rating must be at least 125% of the motor’s full-load current (FLC).

The ampere rating of a general-use switch used as a controller shall be at least twice the full-load amperes (FLA) of stationary motors rated at 2 HP and 300V or less – 430.83(C).

The continuous-duty, full-load current rating of the motor controller shall be at least equal to the nameplate full-load amperes (FLA) of the motor. If the FLA is not marked, the equivalent current rating should be determined using the horsepower (HP) values listed in Tables 430.247 through 430.250. – 430.83(D).

How to Size Disconnects and Switches for Motor and Controller

When selecting disconnects and switches for motors and controllers, you must consider factors such as the full-load current (FLC) of the motor, the type of disconnecting means, and compliance with NEC 2023 regulations.

The switch use as disconnect must be rated for the motor’s operating voltage and be capable of safely handling short-circuit, overcurrent, and overload protection and associated currents in accordance with NEC 430.52 for circuit breakers or fuses.

Example 1: Sizing Disconnecting Means For a Motor

What is the suitable size of disconnecting means in HP to disconnect the three-phase, 460V, 25 HP Motor?

Solution:

As the rating of disconnect switch for 3-phase motor is required in HP, Hence, according to the 430.109(A)(1).

The rating of disconnect shall equal to 25 HP.

Example 2: Sizing Fuse & Circuit Breaker as Disconnecting Means for Motors

What is the suitable size of fuse and circuit breaker for 30HP, 460V, 3-phase motor

Solution:

Determine the full load current (FLC) for 30HP, 460V, 3-phase motor using Table 430.250.

40A

Fuse Size Selection:

Refer to the Table 430.52(C)(1) to find the multiplier value for dual element (time delay) and non-time delay fuse. Multiply the it with FLC.

FLC × Value of Multiplier

  • Non-Time Delay Fuse

40A × 300%  = 120A

  • Dual Element Time-delay Fuse

40A × 175%  = 70A.

Therefore, a 120A non-time delay fuse or 70A dual element time delay fuse are suitable to use for 30HP, 460V, 3-phase motor.

Circuit Breaker Size:

Similarly, refer again to the Table 430.52(C)(1) to find the multiplier value for inverse time breaker (which is 250) and do the same calculation as above.

40A × 250%

= 100A

Hence, a 100A inverse time breaker can be used for 30HP, 460V, 3-phase motor.

If the calculated value does not match a standard fuse or breaker size, round up to the next standard size.

Example 3: Sizing Disconnecting Means for Both Motor & Controller

What is the required size of disconnecting means to disconnect 40HP, 460V, 3-phase motor and associated controller?

Solution:

Calculate the FLC current for 40HP, 3-phase, 460V motor using Table 430.350.

52A

Apply the derating factor (of 115%) from 430.110(A).

52A × 1.15

59.8A

Based on the above calculations

  • A 60A, 600V-rated fusible NEMA disconnect switch is an appropriate choice for a 40HP, 460V, 3-phase motor.
  • If a non-fusible disconnect is used, it must be rated for at least 60A and must comply with UL 98 for motor controllers.

Example 4: Control Circuit Disconnect Sizing

Determine the suitable size of disconnect for 8Amp control circuit operated at 120V.

Given:

  • Control voltage: 120V AC
  • Control circuit current: 8A
  • Disconnect requirement: NEC 430.74 & 430.75 applies

Solution:

  • A 15A, 120V-rated disconnect switch is suitable.
  • A lockable disconnect is recommended for safety compliance (OSHA & NEC 110.25).

Series Overview: Motor Circuit Calculations

Resources & Tutorials:

Wire Sizing Guides

Electrical Technology

All about Electrical and Electronic Engineering & Technology. Join us on WhatsApp at Electrical Technology Official Channel, to receive the latest content, articles, and updates. You can also like and follow our social media networks below, or subscribe with your email to receive premium engineering articles in your mailbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button