Part 13 – How to Size DOL Starter for Three-Phase Motors?
Sizing Direct-On-Line Starter with Contactor, Fuse, Circuit Breaker and Overload Relay for 3-Phase Motors – NEC & IEC
DOL Starter
A DOL starter (also known as Direct-On-Line or across the line starter) is a basic motor starting device that directly connects the motor to the power supply when the start button is pressed, applying full voltage across the motor terminals. Direct On-line starter consists of a main contactor, protective devices (like circuit breakers or fuses), and often an overload relay.
The contactor is an electromagnetic switch that energizes the motor when the start button is pressed, completing the circuit and allowing the motor to draw current. Overload relays protect the motor from damage by shutting down the power supply if the motor draws excessive current or if it overheats.
As the name suggests, DOL means directly connecting the motor terminals to the line voltage in one step through the starter. The single-step connection makes sure to safely ON and OFF the motor without intermediate accelerating positions. (IEC 60947-4-1 and 60050-441).
In the previous part, we learned that why we use a starter and controller with a motor, it’s components selection , sizing calculation for protection and smooth operation. In this part, we will simply explain with a solved example showing how to size a Direct-On-Line starter (DOL) with it main components e.g. contactor, circuit breaker, fuse, thermal overload relay for three phase motors.
Example 1 – Sizing DOL Starter for Synchronous Motor
How to determine the correct size of DOL starter including OL and OCPD devices for a 5 HP, 480V, 3-Phase synchronous motor having the nameplate FLA = 6A and service factor 1.15?
Solution:
Sizing Fuse & Breaker for Starter
overcurrent proactive devices (OCPD) such as fuse and circuit breaker in the starter are used to protect the motor from the high starting current in the initial stage as well as the main breaker protects the circuit conductors from short circuit and ground faults. This is because the starting current of inductive load such as squirrel cage induction motors is 6-8 times more than the normal running current. It is good to know that these devices won’t protect against overload conditions.
The value of full load current (FLC) of 3-phase motors is determined using NEC Table 430.50 which is 7.6A for 5HP motor.
FLC : 7.6A
As per NEC 430.52 and Table 430.52(C)(1), the OCPD (i.e. fuse and circuit breaker) rating for short circuit and ground fault protection is rated at 250% of the full load current (FLC) for inverse time circuit breaker, 175% for dual element time delay fuses and 800% for instantaneous circuit breakers .
- Fuse Size= 7.6A × 175% = 13.3A
- Inverse Time Breaker Size = 7.6A × 250% = 19A
- Instantaneous circuit Breaker Size = 7.6A × 800% = 60.8A
Good to Know:
- In an inverse time circuit breaker, the tripping time is inversely related to the magnitude of the overcurrent. This means the breaker trips faster for higher overcurrents and slower for lower overcurrents. Essentially, it provides a delay that shortens as the current level increases.
- Inverse time circuit breakers are designed to respond to overcurrents with a delay, but the delay decreases as the overcurrent increases. This is different from instantaneous circuit breakers, which trip immediately when the current exceeds a certain threshold.
Sizing Overload Relay for Starter
As we know that fuses and circuit breakers are used to protect against short circuit and ground faults, similarly, overload relay doesn’t provide protection against short circuit currents. In short, thermal OL relay only protects the motor wiring against overload conditions.
The overload relay are rated at 125% of the motor’s FLA with marked service factor of 1.15 or greater or temperature rise 40°C or less as per NEC 430.32(A)(1). The overload protective device is sized at 115% of the full load amperes for general motors.
Overload Setting = 6A × 125% = 7.5A
This way, the ampere rating of relay setting should not be more than 7.5A.
Sizing Contactor
Anything other than fuse and circuit breaker, the rating of contactor and controller should not less than the full load current of motor or HP rating.
Based on the NEMA ICS 2: Table 2-4-1 for sizing contactor and starter based on HP and RLA, the suitable contactor for 5 HP, 480V, 3-phase motor is NEMA Size 0.
- NEMA Contactor: Size 0 – Min. 5 HP
- Size of Main Contactor = 100% × FLA (Line)
- Size of Main Contactor = 100% × 6A = 6A
Example 2 – Sizing Direct-On-Line Starter for Induction Motors
What is the suitable size of Direct On-line (DOL) starter with contactor, OCPD and overload relay for a 10 HP, 3-Phase squirrel cage Induction motor having 25kA perspective current and rated current (ln) is 13A?
Solution:
Overcurrent Protection:
To avoid the unwanted tripping, the rated current of short-circuit protective device (SCPD) should be 6 – 7 times greater than the rated current of the motor (ln). i.e.
- 7 × ln
- 7 × 13A
- 91A
Hence, the next available size for short circuit protective device is 100A. Keep in mind that the SCPD only protects against short circuit and ground faults, and not against overload condition.
Overload Protection
As we know that OCPD does not provide protection against overload, we need to add a thermal overload relay in the starter for this purpose.
Trip Setting
The trip setting is calculated at 720% of the full load current (FLA) based on trip class. The trip classes are classified in 5, 10, 20 and 30. This shows the OL should trip when overcurrent starts to flow in the circuit for more than 5, 10, 20 and 30 seconds.
Typically, Class 5 is used for quick tripping while Class 10 are used with little thermal capacity i.e. submersible and water pumps. Class 10 and Class 20 are more common for general purpose application. Class 30 are used to eliminate the unwanted tripping for motors having load with considerable inertia.
Generally, the OL trip setting is calculated based on 720% times the full load current (FLA).
- 720% × ln
- 7.2 × 13A
- 93.6A
The class type of OL relay is based on specific applications. For example, if we use a Class 20, it means the OL will trip when it detects overcurrent flowing in the circuit for more than 20 seconds.
Size of OL Relay
The size of thermal overload relay shall not more than 100% of the full load current
- 100% × FLA
- 100% × 13A
- 13A
In this case, the rating of overload relay should not more than 13A.
- Minimum OL Setting = 70% × 13A = 9.1A
- Max OL Setting = 120% × 13A = 15.6A
Contactor Selection
As required, the Contactor Class is AC-3 for squirrel-cage induction motor. The making and breaking capacity is for AC-3 is 10.
Contactor Class: AC-3 – For Squirrel Cage Motor
Size of Main Contactor:
- 100% × FLA
- 100% × 13A
- 13A
Making & Breaking Capacity of the Contactor:
- 10 × FLA
- 10 × 13A
- 130A
Series Overview: Motor Circuit Calculations
- Part 1 – Motor Load Circuits: NEC Terms and Basic Terminologies
- Part 2 – NEC Requirements for Motor Circuits
- Part 3 – Understanding NEMA Motor Nameplate Data
- Part 4 – Calculating Locked Rotor Current (LRC) for Motors
- Part 5 – Sizing Motor Branch Circuit Conductors
- Part 6 – Sizing Motor Feeder Conductors
- Part 7 – Sizing Motor Overcurrent Protection and OCPD’s Devices
- Part 8 – Sizing Motor Feeder Protection
- Part 9 – Sizing Motor Overload Protection
- Part 10 – Overcurrent Protection for Motor Control Circuits
- Part 11 – Sizing Disconnecting Means for Motor & Controller
- Part 12 – Sizing Motor Starter & Contactor – NEMA – NEC
- Part 13 – Sizing Direct-On-Line (DOL) Starters/Contactors for Motors (*Bonus) … (You are Here)
- Part 14 – Sizing Star-Delta Motor Starters/Contactors for Motors (*Bonus)
Resources & Tutorials:
- Difference Between NEMA and IEC Motor Starters & Contactors
- Difference Between Direct-On-Line (DOL) and Star Delta Starter
- Cable Size Calculation for LT & HT Motors
- Three Phase Motor Power & Control Wiring Diagrams
- What is Motor Efficiency & How to improve it?
- Star Delta 3-phase Motor Automatic starter with Timer
- How to Run a Three-Phase Induction Motor on a Single-Phase Power Supply?
- How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
- How to Wire Twin Timer in Repeat Cycle & One-Shot Mode for 120V/240V Motors?
- How to Control a Single-Phase Motor from Multiple Locations?
- Wiring of DOL Starter for Automatic / Manual Control Using Digital Timer
- How to Start & Stop a 3-Phase Motor Using Direct-On-Line (DOL) Starter?
- Automatic & Manual Control of Motor Using VFD & DOL Starter
- How to Reverse and Forward a Three-Phase Motor Using a VFD?
- How to Wire a VFD with Motor, PLC, Switches & External Devices
- Sequential Motor Control Circuit Using LOGO! V8 PLC
- Automatic Reverse Forward Motor Control Circuit Using Delta – DVP-14SS PLC
- Reverse Forward Motor Control Circuit Using PLC – ZEN Programming Relay
- Motor Protection – Types of Faults and Protection Devices
Wire Sizing Guides
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Size a Branch Circuit Conductors with Protection?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
- How Size a Circuit Breaker for Different Load Applications