Overhead LinesPower SystemTransformer

What is Shunt Reactor – Types, Construction & Applications

Why to use Shunt Reactors? Different between Power Transformer & Shunt Reactor

What is Shunt Reactor?

Shunt reactor is same as power transformer but it has only one winding per phase as compared to power transformer. Shunt reactors are used to increase the power and energy system efficiency as it absorb & compensate the reactive power in cables and long high voltage transmission lines. It can be directly connected to the power line or tertiary winding of three winding transformer.

What is Shunt Reactor - Types, Construction & Applications
123kV, 100 MVAr Shunt Reactor

Different Between Shunt Reactor & Power Transformer

Both Shunt reactor and power transformer are same in construction but there are some main difference as well such as:

  • Shunt reactor has only single winding while Power transformer has three windings.
  • Shunt reactor provide lagging VArs (Or it may consume and absorb reactive power) to increase the system efficiency while power transformer is meant to be operated to transform voltage (i.e. step up or step down)
  • In shunt reactor, primary AT (Ampere Turns) are equal to secondary AT due to the absence of other windings while in case of power transformer, Primary AT is the sum of exciting  AT and Secondary AT.
  • Shunt reactor may be designed without air or iron core to prevent the hysteresis loss as there are large amount of magnetizing current as compared to power transformer.
  • Shunt Reactors are rated in MVAr while power transformer rated in kVA.
  • Shunt reactor are used in high voltage systems and cables network to improve the system efficiency while power transformer are used to transfer the level of voltage.

Related Post: Transformers Insulation Materials in Oil-Immersed & Dry Type T/F

Why to use Shunt Reactor ? Applications of Shunt Reactors

Apart from resistance real electrical circuits have a inductive and/or capacitive component, which causes a phase shift between voltage and current, as shown in Figure 1, and reactive power (unit: VAr) will flow in the circuit.

Phase shift
Figure 1 – Phase shift

If inductance (XL = 2πfL = ωL) prevails current will be lagging (Figure 2) and reactive power is called inductive power.

Where:

XL (Ω – ohm): Inductive reactance. f (Hz – hertz) : frequency. L (H – henry): Inductance. ω = 2πf: Rotational speed (rad/s or rpm – radians per second or revolutions per minute)

Current lagging
Figure 2 – Current lagging

This is the case of long overhead lines. The consequence of lagging currents is well known (low power factor), as well as the way to increase power factor (installation capacitor banks).

If capacitance prevails (XC = 1/2πfC = 1/ωC ), which is the case of networks with long underground cables.Current will be leading (Figure 3) and reactive power is called capacitive power.

Where:

XC(Ω– ohm): Capacitive reactance. C (F – farad): Capacitance.

Current leading
Figure 3 – Current leading

This situation is also harmful for power transformers and mainly for generators.

Power transformers may be subjected to ferroresonance, an over-voltage phenomenon that can damage the transformers and/or the surge arresters .In weak networks, functioning as an island and not integrated in a large and complex electrical network, generators are requested to supply the excessive capacitive power, situation that will cause overheating and malfunctioning of generators, which will decrease the useful life of the equipment.

That excessive reactive power must be compensated, using shunt reactors, equipments that shall be in accordance with IEC Standard 60076-7, of which an example is shown in Figure 4.

Shunt reactor
Figure 4 – Shunt reactor

Construction of Shunt Reactor

As mentioned above, Shunt reactors are similar to power transformers, but they have only one winding per phase.

Those three windings are star connected with the neutral point accessible (YN). The neutral point is connected to the earthing system of the installation through the tertiary winding of a power transformer or directly. Figure 5 shows a typical connection diagram of a shunt reactor.

Typical connection diagram of a shunt reactor
Figure 5 – Typical connection diagram of a shunt reactor

Shunt reactors may be oil-immersed type with conservator or dry type.

The built-on protections are the same used in power transformers (Buchholz relay and oil pressure and temperature sensors for oil-immersed type; windings temperature probes for dry type). Accessories are also similar to those used in power transformers, mainly in oil-immersed type, in which it must be emphasized the oil pressure relief valve and the air breather.

Types of Shunt Reactors

Common shunt reactors have a fixed rating ( MVAr ; kVAr ) and they may be permanently connected to the network, or switched in and out, depending on the load and of the capacitance of the underground cables in service. This functioning and the switching in and out are similar to what is done with capacitor banks.

The more recent technology calls, depending of the characteristics of the network and the variability of the load, for the use of variable shunt reactors (VSR), which rating can be changed by steps. Common shunt reactors are mainly used in medium voltage networks (up to 36 kV).

VSR are mainly used in extra high and high voltage networks (rated voltage of the network ≥  60 kV).

Maximum rated voltage of shunt reactors is nowadays 800 kV and rated power goes up to 300 MVAr.

Same like power transformers, shunt reactors may be designed like Oil-immersed and Dry type transformer as well.

About the Author: Manuel Bolotinha

About the Author: Manuel Bolotinha

-Licentiate Degree in Electrical Engineering – Energy and Power Systems (1974 – Instituto Superior Técnico/University of Lisbon)
– Master Degree in Electrical and Computers Engineering (2017 – Faculdade de Ciências e Tecnologia/Nova University of Lisbon)
– Senior Consultant in Substations and Power Systems; Professional Instructor
Upated by: Electrical Technology

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

4 Comments

  1. Shunt reactor
    the sending end voltage is 132 kV and due to ferranti effect the receiving side(132/33 kV, 48 MVA S/S) is 152 kV on no load. so the department plans to install a shunt reactor
    Kindly suggest as to what value of reactor should be used along with the justification thereof.
    thank you

  2. Dear Sir / Madam,
    we are furnishing below all the details available with us for your needful action & sending us most suitable advise to solve our problem of more consumption of rkvah (lead) . details are as under.
    one of our plant is commissioned recently around six month back & plant is not yet in operation (except some plant lighting load) due to some commercial problem. recorded details from mseb metering is as under.
    average per day ( 24 hrs) kwh consumption ———————————— 100 units
    average per day (24 hrs) rkvah – lag consumption ———————— 0 unit
    average per day (24 hrs) rkvah – lead consumption ———————– 150 units
    since recorded consumption of rkvah ( lead) is much more though there are no capacitive load & it seems there are generation of capacitive power through laid l.t. cable from 11 kv / 440 volt 500 kva transformer to l.t.main distribution board ( around 2 km long x 2 nos of 400 sq mm l.t. cable)
    kindly look in to it & send your most suitable advise for required modification by which rkvah ( lead) consumption can be compensated.

  3. Hi,
    I have three units of dry type single phase shunt reactors rated at 22KV connected to the three phase substation system. One of the reactors has a problem on insulation hence can’t able to put back on the system since circuit breaker tripped due to that ground fault, is it possible to bypass that shunt reactor so two (2) remaining reactors can be used?
    Hoping for your advice.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button