ELCB (Earth Leakage Circuit Breaker) – Construction, Types & Working

What is an ELCB? Types, Working, and Application of Earth Leakage Circuit Breaker

ELCB or Earth Leakage Circuit Breaker is a protection device that protects against earth leakage. Initially, the earth leakage circuit breaker were voltage detection devices, now they are switched to current sensing devices. The current ELCB is renamed as RCCB or RCD while the voltage ELCBs are still known as ELCB but they are obsolete.

In this article, we are going to discuss ELCB in detail with both types.

What is Earth Leakage?

The electrical current that flows from the live conductor to the earth through an unintended path is called earth leakage. It may flow between their poor insulation or through a person’s body and cause electrical shock. The consequence of electrical shock may prove fatal if the leakage current exceeds the only 30mA. Therefore, protection devices are used to disconnect the power source when such current leakage is detected

Causes of Earth Leakage?

Earth leakage can occur due to various reasons. It can occur due to damaged insulation of the live conductor or broken conductors. It can also occur when the live conductor comes in contact with the body of the equipment (if the equipment is not properly grounded). Upon touching the conductor or the equipment, the current can pass to the earth through the person’s body.

What is an Earth Leakage Circuit Breaker?

ELCB or Earth Leakage Circuit Breaker is a type of circuit breaker that is used for protection against leakage current. it breaks the circuit and disconnects the power supply to the load when it senses the leakage current. The earth leakage can cause electrical shocks that can be fatal.

ELCB is mainly used for protection against electrical shock. They do not offer protection against overloading or short circuit. Therefore, they must be used in series with an MCB (miniature circuit breaker).

What is ELCB (Earth Leakage Circuit Breaker) ?

Function of ELCB

ELCB is a safety device whose main function is to prevent electrical shock. It monitors the leakage current that flows out of the circuit through any unintended path. It cannot protect against overloading or short circuit current.

Operation of ELCB

Under normal conditions, the current from the source flows into the load through the live wire and flows out of the load through the neutral wire. In fact, both currents are equal in amount. If the current leaks through any unintended path, an imbalance between the live and neutral wire occurs. The ELCB can sense the imbalance using a current transformer and break the contacts using an electromagnetic relay.

Construction of Earth Leakage Circuit Breaker - ELCB

Types of ELCBs

There are two types of ELCB classified based on its operation principle;

Both types of ELCBs detect the leakage current but their sensitivity and the level of protection they offer are different. Voltage ELCB was invented before the current ELCB. voltage based ELCB is inferior to current ELCB. Therefore, to avoid confusion, the voltage ELCB is renamed ELCB while the current ELCB is renamed RCCB or RCD.

Voltage ELCB

Voltage ELCB operates on the voltage level between the earth and the body of the equipment. The voltage difference is used to detect the leakage current and instantly break the circuit.

Voltage ELCB

It has terminals for both phases and neutral on both supply and load sides. It has two extra terminals that connect with the equipment’s body and the earth. These terminals are actually connected with the electromagnetic relay and they play a vital role in breaking the circuit during current leakage.

Working Principle

One of the terminals of the relay coil is directly connected to the earth while the other terminal is connected to the body of the equipment. The coil can sense the voltage difference between the earth and the body of the equipment.

If the live wire breaks or its insulation fails and comes in contact with the body of the equipment, a voltage difference appears across the terminals of the coil. As a result, the current starts to flow through the coil and it is energized. The relay starts to generate electromagnetic force. When the current exceeds a certain limit, the relay produces sufficient force to pull the latch. By doing so, the latch break opens the contacts and disconnects the power supply to the equipment and prevents electrical shock.

Therefore, the earth connection is necessary as the relay only operates when the leakage current flows through it. if the current leaks through any other parts of the circuit and flows through any other unintended path, it will not break the circuit as the current must flow through the relay in order to break the circuit.

Advantages

Here are some of the advantages of voltage ELCB

Disadvantages

Here are some of the disadvantages of voltage ELCB

It has far more disadvantages than advantages and they are obsolete. Therefore, if you have installed any old voltage ELCBs in your home, replace them with current ELCB or RCCB. They are more efficient, reliable and best at providing protection against any kind of leakage current.

Current ELCB (RCCB or RCD)

Current ELCB or commonly known as RCD (Residual Current Device) or RCCB (Residual Current Circuit Breaker) is another type of ELCB that breaks the circuit upon sensing any leakage current. It operates on the current difference between the phase and neutral line. The difference appears when the current leaks from the phase line. Therefore, RCCB can provide protection against any kind of current leakage.

Current ELCB or RCD or RCCB

It has four terminals having two input and two output terminals for phase and neutral. The phase-in and neutral in are connected to the supply while phase-out and neutral out are connected to the load. It does not have that extra terminal for earth connection.

Working Principle

The RCCB working is based on the current imbalance between the phase and neutral line. It continuously monitors the phase and neutral current. Under normal conditions, both phase and neutral current are equal because it is the same current flowing back from the load. If, the current leaks through any unintended path, the neutral current reduces and causes imbalance. When the imbalance exceeds a certain limit, the RCCB breaks the contacts and disconnects the power supply.

RCCB works on the principle of Kirchhoff’s current law, according to which the amount of current entering the load through the hot wire must be equal to the amount of current leaving the load through the neutral wire. The difference between the two currents known as residual current should be zero. If there is a difference then the current is leaking somewhere that causes the imbalance.

RCCB includes a zero-sequence current transformer that has three coils i.e. phase coil, neutral coil and search coil. It is used for detecting the imbalance or difference between two currents. The phase coil and neutral coil is wounded around the toroidal core in such a way to cancel out each other’s flux.

if the currents are equal as should be under normal conditions, the resultant flux will cancel out each other and there will be no induced current in the search coil. suppose, there is a leakage current, the current difference will produce flux that will induce a voltage in the search coil. as the search coil is connected to the relay trip mechanism, it will break the contacts and disconnect the power supply to the load.

Advantages

Here are the advantages of the current ELCB or RCCB

Disadvantages

Here are the disadvantages of the current ELCB or RCCB

Related Post: Difference Between MCB, MCCB, ELCB & RCD

Types based on Poles

According to the poles of circuit breakers, the ELCB is classified into three types.

2-Pole ELCB: it is used for protection in a single-phase system. It has 2 ingoing and 2 outgoing terminals having phase and neutral connections.

3-Pole ELCB: It is used for protection in a three-wire three-phase system. It has three ingoing and three outgoing terminals.

4-Pole ELCB: It is used for protection in a four-wire three-phase system.

Advantages and Disadvantages of ELCBs

Advantages

Disadvantages

Applications of ELCBs

ELCB is used for protection against current leakage. The current leakage causes electrical shock and faults in the system. It breaks the circuit instantly to prevents damage to the connected circuits. They are essential in wet locations having increased risks of electrical shocks.