Air Circuit Breaker (ACB) – Construction, Operation, Types and Uses

ACB (Air Circuit Breaker) – Construction, Operation, Types, Advantages and Applications

What is a Circuit Breaker?

A circuit breaker is a device, which is capable to:

A circuit breaker is used for switching mechanism and protection of the system. Other associated devises and components are also used for this purpose associated with circuit breakers like fuses, relays, switches etc.

Circuit breakers are widely used in industries as well as power system for controlling and protection of different parts of the circuit like switchgears, transformers, motors, generators/alternator etc., which leads the system stable and reliable.Circuit Breaker Symbols

There are different types of air circuit breakers available in the market and we will discuss one by one in detail.

What is an Air Circuit Breaker (ACB)?

Air Circuit Breaker (ACB) is an electrical protection device used for short circuit and overcurrent protection up to 15kV with amperes rating of 800A to 10kA. It operates in air (where air-blast as an arc quenching medium) at atmospheric pressure to protect the connected electric circuits. ACB has completely replaced by oil circuit breaker because it is still a preferable choice to use an ACB because, there is no chance of oil fire like in oil circuit breaker.

An air circuit breaker:

Construction of Air-Circuit Breaker

The following fig shows the main and external parts of an ACB. (ABB EMax Low Voltage, Current Limiting and Selective (Non-Current Limiting) Air Circuit Breaker).

Delixi Air Circuit Breaker External labels (Rated Current and Voltage = 1kA, 415V)
Delixi Air Circuit Breaker External labels (Rated Current and Voltage = 1kA, 415V)
  1. OFF button (O)
  2. ON button (I)
  3. Main contact position indicator
  4. Energy storage mechanism status indicator
  5. Reset Button
  6. LED Indicators
  7. Controller
  8. “Connection”, “Test” and “isolated” position stopper (the three-position latching/locking mechanism)
  9. User-supplied padlock
  10. Connection “,” Test “and” separation “of the position indication
  11. Connection (CE) Separation, (CD) Test (CT) Position indication contacts
  12. Rated Name Plate
  13. Digital Displays
  14. Mechanical energy storage handle
  15. Shake (IN/OUT)
  16. Rocker repository
  17. Fault trip reset button

The following fig shows the Internal Construction of Air Circuit Breaker

Air Circuit Breaker Construction (ABB EMax Low Voltage Current Limiting Air Circuit Breaker and Selective (Non-Current Limiting) Air Circuit Breaker)
(ABB EMax Low Voltage Current Limiting Air Circuit Breaker and Selective (Non-Current Limiting) Air Circuit Breaker)

Principle of Operation of ACB

The working principle of Air Circuit breaker is rather different from other types of circuit breaker. The main aim of circuit breaker is to prevent reestablishment of arcing after current zero where the contact gap will withstand the system recovery voltage. It does it same work, but in a different manner. During interruption of arc, it creates an arc voltage instead of supply voltage. Arc voltage is defined as the minimum voltage required for maintaining arc .The circuit breaker increases the voltage in three different ways:

It is operated within voltage level up to 1 KV. It contains two pairs of contact. The main pair carries the current and the contact made of copper. An additional pair of contact is made of carbon. When the breaker is opened, the main contact opens first. During opening of the main contact, the arc contact remains in touch with each other. The arcing gets initiated when arc contacts are separated. The circuit breaker is obsolete for medium voltage.      

Types of Air Circuit Breakers (ACBs)

There are four types of ACBs used in the control and protection to maintain and stable operation of switch gears and indoor medium voltage.

Related Post: MCCB (Molded Case Circuit Breaker) – Construction, Types & Working

Plain Air Circuit breaker or Cross-Blast ACB

The circuit breaker is fitted with a chamber surrounding the contact. The chamber is known as “arc chute”. The arc is made to drive in it. The arc chute will help in achieving cooling. Arc chute is made from some refractory material. The inner walls of arc chute are shaped in such a way that arc is not only forced into close proximity, but will drive into the serpentine channel projected on arc chute wall.

The arc chute is divided into a number of small compartments by using metallic separation plates. Metallic separation plates are arc splitters and each of small compartments behave as a mini arc chute. Initial arc will split into a series of arcs this will make all arc voltages higher than system voltage. They are preferable choice in low voltage application.

Plain air circuit breaker or Cross-Blast Air Circuit Breaker

Air Chute Air Break ACB

In air chute air circuit breaker, there are two types of contacts namely “main contact” and “auxiliary or arcing contacts”. The main contacts are made of copper and the silver plates having low resistance and conducts the current in closed position. Auxiliary or arcing contacts are made of copper alloy as they are heat resistance and used to prevent from damaging the main contacts due to arcing and can be easily replaced when needed in case of wear and tear. During the circuit breaker operation, the arcing or auxiliary contacts are closed before and open after the main contacts of the circuit breaker.

Magnetic Blowout Type Air Break ACB

Magnetic blowout air circuit breakers provide magnetic control over the arc moment to make arc extinction within the devices. The arc extinction is controlled using magnetic field provided by the current in blowout coils connected in series with the circuit being interrupted. These coils are known as “blow out the coil”. Magnetic field does not control and extinguish the arc made in the breaker, but it moves the arc into chutes where the arc is lengthened, cooled and extinguished accordingly. These types of circuit breakers are used up to 11kV.

Air Blast Circuit Breaker:

This type of circuit breaker is used for system voltage of 245 KV, 420 KV and even more.

Air blast circuit breaker has further divided into three categories:
  • Axial blast breaker
  • Axial blast with sliding moving contact.

Related Post: Tripping Curves of Circuit Breakers – B, C, D, K and Z Trip Curve

 Axial Blast Breaker

The moving contact is in contact. There is a nozzle orifice in fixed contact at normal closed condition of breaker. When a fault occur high pressure is introduced into the chamber. High-pressure air will flow through nozzle orifice voltage is sufficient to sustain.

Schematic diagram of axial blast air circuit breaker

Axial Blast with Sliding Moving Contact

 The moving contact is fitted over a piston supported by a spring. The blast transfers arc to arcing electrode.

Schematic diagram of Axial Blast Air Circuit Breaker with Side Moving Contact

Related posts: Difference Between MCB, MCCB, ELCB and RCD Circuit Breakers

Advantages & Disadvantages of Air Blast Circuit Breaker

Advantages

Related post: HRC Fuse (High Rupturing Capacity Fuse) and its Types

Disadvantages

Application and Uses of Air Circuit Breakers