Electrical DesignElectrical WiringHow ToProtection

How to Wire 1-P & 2-P, 1-Phase & 3-P, 3-Phase GFCI Breakers

Wiring Installation of 1-Pole and 2-Pole, Single-Phase and 3-Pole, 3-Phase GFCI Circuit Breakers with & without Neutral

A Ground-Fault Circuit Interrupter (GFCI) is a safety device designed to protect people from electrical shock by monitoring the electrical current flowing through a circuit. It detects imbalances between the hot and neutral wires, which can indicate a ground fault where electricity is leaking out of the circuit.

If a ground fault is detected, the GFCI quickly cuts off the electrical power to prevent shock and potential electrocution. GFCIs are commonly installed in areas with higher risk of electrical hazards, such as bathrooms, kitchens, and outdoor spaces.

The following fig shows the different wiring connections of 1-Pole, 2-Pole and 3-Pole GFCI breakers with Neutral and without Neutral.

Click image or open in a new tab to enlarge

How to Wire 1-Pole & 2-Pole , 1-Phase GFCI and 3-Pole, 3-Phase GFCI Breakers
Wiring 1-Pole, 2-Pole & 3-Pole GFCI Breakers

GFCI and RCD or RCCB are Same.

In North America, it is commonly known as GFCI (Ground Fault Circuit Interrupter) or GFI (Ground Fault Interrupter) or ALCI (Appliance Leakage Current Interrupter).

In America, it is commonly known as GFCI “Ground Fault Circuit Interrupter” or “GFI “Ground Fault Interrupter” or ALCI “Appliance Leakage Current Interrupter”.

In Europe and Australia, the same device is known as RCD (Residual Current Device) or RCCB (Residual Current Circuit Breaker). When an overcurrent protection device such as an MCB is combined with an RCD (RCD + MCB), it is known as an RCBO (Residual Current Circuit Breaker with Overcurrent Protection). These devices are also referred to as safety switches.  RCDs are modern devices used nowadays, which is actually a Current Operated ELCB, replacing the old-school Voltage Operated ELCBs.

  • GFCI is the abbreviation of “Ground Fault Circuit Interrupter
  • RCD is the short form of “Residual Current Device
  • RCCB stands for “Residual Current Circuit Breaker“.
  • ELCB is known as “Earth Leakage Circuit Breaker”.

Voltage-operated ELCBs have been replaced with the latest RCD devices due to some disadvantages of ELCBs (such as their reliance on a proper earth connection).

Good to Know: At present, only 15A and 20A GFCI receptacles rated for 120V are available, typically in NEMA 5-15 and 5-20 configurations. In other words, for 240V circuits, you must use GFCI breakers, as 240V GFCI receptacles are not available.

GFCIs and RCDs are designed to protect against electric shock caused by ground faults and leakage currents by automatically tripping the circuit. According to IEC and NEC requirements, the use of these protective devices is mandatory in locations exposed to moisture or water, such as laundries, kitchens, spas, bathrooms, and outdoor installations.

It is important to understand that the key difference between standard single-pole or two-pole circuit breakers and a GFCI breaker is the built-in white pigtail wire on the backside of the GFCI breaker. This pigtail must be connected to the neutral busbar in the main panel; otherwise, the GFCI will not operate correctly and will fail to provide proper protection. While there is a built-in white pigtail in the AFCI breaker, you may refer to the previous post for a detailed comparison between GFCI and AFCI breakers.

The following fig shows differences and terminal wiring of 1-pole and 2-pole standard breakers and GFCI breakers.

Difference between 1-Pole & 2-Pole Standard Breakers and GFCI Breakers - Terminals & Wiring

Related Post: How to wire a GFCI Outlet? – GFCI Wiring Circuit Diagrams

Requirement of GFCI in NEC

The current codes have been updated with new requirements for GFCI protection in the National Electrical Code (NEC) for 250V outlets and receptacles in specific locations in dwelling units.

According to 210.8(A), for Dwelling Units, all 120-240V outlets installed in the locations specified in 210.8(A)(1) through (A)(11) and supplied by single-phase branch circuits rated 150V or less to ground shall have ground-fault circuit-interrupter (GFCI) protection for personnel:

  • Outdoors applications except receptacles supplied by a branch circuit that are not readily accessible in accordance with 426.28 or 427.22 (if applicable)
  • Indoor damp and wet locations
  • Bathrooms
  • Boathouses
  • Bathtubs or shower stalls
  • Laundry areas
  • Garages
  • Crawl spaces
  • Kitchens
  • Sinks
  • Basements except receptacles supplying only a permanently installed fire alarm or burglar alarm system

Non-Dwelling Units:

  • Commercial Kitchens
  • Bathrooms:.
  • Rooftops
  • Outdoor Areas
  • Sinks

Specific Locations and Equipment:

  • Boathouses
  • Receptacles in Damp or Wet Locations.
  • Hydromassage Bathtubs
  • Electric Drinking Fountains:

Now that you have an idea, we will show different wiring circuit diagrams for single-pole, two-pole, three-pole, and four-pole (both single-phase and three-phase) GFCI circuit breakers.

box type=”info” align=”” class=”” width=””]

  • The NEC – 210.8(A)(1) through (A)(11) for dwelling and non-dwelling unites mandates GFCI protection for circuits in bathrooms, garages, kitchens, laundry areas, crawl spaces, unfinished basements, and outdoor areas, as well as for certain appliances like dishwashers or sump pumps. A GFCI breaker ensures compliance for the entire circuit in these areas.
  • GFCI protection is required for various applications in compliance with the following NEC Articles: 210.8, 406.3, 424.44, 426.28, 427.22, 511.12, 517.17, 517.20, 525.23, 530.44, 547.28, 555.35, 620.6, 625.54, 680.5, 680.21, 680.22, 680.23, 680.27, 680.32, 680.43, 680.44, 680.51 through 680.59, 680.62, and 680.71.[/box]

Wiring Single Pole GFCI Breakers

Wiring 15A – 120V GFCI Breaker

The following wiring diagram shows a 15A, 120V ordinary outlet wired and protected by a single-phase 15A, 120V, single-pole GFCI circuit breaker.

As shown in the figure, the built-in white wire in the GFCI should be directly connected to the neutral bar in the main panel board.

The Line (Hot, Live, or Phase) is connected directly to the GFCI input, and the output is connected to the line terminal of the ordinary outlet/receptacle. The silver screw labeled “N” on the GFCI is connected to the silver screw on the outlet via the output neutral wire from the GFCI to the outlet. The ground terminal (green screw labeled “G”) of the outlet is connected to the ground bar in the main distribution board.

This way, the 15A, 120V outlet is GFCI protected by the 15A GFCI breaker. You may use #14 AWG wire between the outlet and the GFCI. According to the 80% load rule in the NEC, no more than a 12A load should be connected to this 15A GFCI-protected outlet.

15A × 80% = 12A

You may safely connect up to 1440 watts load appliances to the 14A, 120V GFCI protected outlet.

Click image or open in a new tab to enlarge

How to Wire a Single Pole GFCI Circuit Breaker
Wiring a 15A/120V, Single-Pole GFCI Circuit Breaker

Wiring 20A – 120V GFCI Breaker

The same wiring configuration can be applied to a 20A, 120V circuit by using the correct wire size, an appropriately rated circuit breaker, and properly rated switches and outlets. As shown in the figure below, this includes wiring a 2-pole, 20A–120V GFCI breaker with a 20A–120V outlet (NEMA 5-20R).

Click image or open in a new tab to enlarge

How to Wire 20A - 120V, 1-Pole GFCI Breaker
Wiring 20A-120V, 1-P GFCI Breaker

Wiring 30A – 120V GFCI Breaker

Similarly, the following wiring diagrams shows a TT-30 (Travel Trailer) receptacle is protected by using 1-P, 30A – 120V GFCI breaker.

Wiring NEMA TT-30 Receptacle for RVs using 1P GFCI Breaker

Wiring 2-Pole GFCIs without Neutral

Wiring 15A – 240V GFCI Breaker

The following wiring configuration shows a 20A, 240V receptacle wired and protected by a single-phase, 20A, 240V, double-pole GFCI circuit breaker.

Similar to the wiring diagram for a 1-pole GFCI circuit breaker, the built-in white wire on the back of the two-pole GFCI must be connected to the neutral bar in the main panel. The 2-pole GFCI should be installed in the two hot slots in the main panel. This configuration allows HOT 1 and HOT 2 to provide the 240V input supply to the GFCI.

The two output line wires (HOT 1 and HOT 2) from the GFCI are connected to the line terminals (L1 and L2) of the 20A, 240V outlet/receptacle. Finally, the ground wire from the ground terminal bar is connected to the ground screw on the outlet.

This setup ensures that the 20A, 240V outlet is protected by the 20A GFCI circuit breaker. You may use #8 to #10 AWG wire between the outlet and the GFCI. According to the 80% load rule in the NEC, no more than a 24A load should be connected to this 20A GFCI-protected outlet.

20A × 80% = 16A

A maximum load of 5760 watts may be safely connected to this 20A, 240V outlet with ground fault protection.

Good to Know: In a 240V single-phase circuit, the 2-pole GFCI does not require an output neutral wire for the load circuit. Instead, one of the hot wires (out of the two hot wires) serves as the returning path for the current, completing the circuit and allowing it to function properly (similar to the phase and neutral connection in a 120V circuit).

Click image or open in a new tab to enlarge

Wiring 2-P, 15A-240V GFCI Breaker
Wiring 15A-240V, 2-P GFCI Breaker

Wiring 20A – 240V GFCI Breaker

The following wiring diagrams demonstrates a 2-Pole, 20A – 240V GFCI breaker is used to protect the 20A/250V (NEMA 6-20R) outlet.

Click image or open in a new tab to enlarge

How to Wire a 20A - 240V, 2-Pole GFCI Breaker
Wiring 20A-240V, 2-Pole GFCI Breaker

Wiring 30A – 240V GFCI Breaker

Wiring NEMA 6-30 Receptacle with 2P GFCI for EVs

Wiring 50A – 240V GFCI Breaker

Wiring NEMA 6-50 Receptacle with 2-P GFCI for EVs

Wiring Two-Pole GFCIs with Neutral

As we know, in a 240V system, the neutral connection is typically not required. However, in certain cases, appliances must be connected to the neutral in accordance with the manufacturer’s specifications and user manuals.

The following wiring diagrams shows the different ratings of 2-pole GFCI breakers with neutral wire used in 3-P, 4-W configurations.

Wiring 20A – 120/240V GFCI Breaker

The following wiring diagram shows the installation of a 20A, 120/240V 2-Pole GFCI breaker with a 20A , 125/240V (NEMA 14-20) which required neutral connection.

Wiring NEMA 14-20 Receptacle with a 2-Pole GFCI

Wiring 30A – 120/240V GFCI Breaker

In a two-pole, 3-wires configuration, the following 30A-125//250V (NEMA 14-30) grounding receptacle is wired and protected using 30A – 120/240V GFCI breaker.

How to Wire NEMA 14-30 Receptacle - 30A, 125/250V with 2-Pole GFCI for EVs

Wiring 40A & 50A – 120/240V GFCI Breaker for Spa & Hot Tub

The following wiring diagram shows a hot water tub spa or whirlpool spa wired and protected through a 2-pole GFCI circuit breaker using a three-wire system (two hot wires, one neutral, and one ground).

In this 4-wire GFCI wiring diagram, the built-in white wire from the GFCI is connected to the neutral busbar in the main panel. Two lines from the main panel (L1 and L2, single-phase 240V) are connected to the input terminals of the GFCI, which is installed in the L1 and L2 terminal slots in the panel or load center.

As shown in the figure, the three output terminals are connected to the spa control box according to the printed markings: the middle terminal is neutral, and the first and last terminals are the two lines (L1 and L2). Finally, the ground wire from the ground busbar is connected to the ground terminal in the spa control box.

Click image or open in a new tab to enlarge

Wiring 40A - 240V, 2-Pole GFCI Breaker for Hot Tub

Similarly, the following wiring diagram shows a 50A – 120/240V spa panel box with a 2-pole GFCI breaker controlled by downstream 2-pole standard breaker in the main panel.

Click image or open in a new tab to enlarge

Wiring 50A - 120/240V Spa Panel using 2-P GFCI & Breaker

Wiring 50A – 120/240V GFCI Breaker

If the 2-pole GFCI breaker has only two output terminal screws (mostly used in 240V circuits), you will have to arrange a separate neutral from the neutral busbar in the main panel or load center. For example, the following wiring diagram shows a 2-pole GFCI breaker with two output terminals (L1 and L2) installed with a NEMA 14-50R outlet rated at 50A, 240V, which is used for heavy-duty EV charging, stoves, laundries, etc.

Click image or open in a new tab to enlarge

How to Install 14-50R Receptacle with 2-Pole GFCI
Wiring a 14-50R Receptacle with 2-Pole GFCI

If the 2-pole GFCI breaker has three output terminal screws (mostly used in 120/240V circuits), you may directly wire the neutral to the center screw labeled “N”, and Line 1 and Line 2 to the first and last terminal screws, connecting to the outlet or any other load.

For example, the following wiring diagram shows a 2-pole GFCI breaker with three output terminals installed with a NEMA 14-50R receptacle rated at 50A, 240V, which is used for heavy-duty electric vehicle charging, mobile connectors, electric ranges, etc.

Click image or open in a new tab to enlarge

Wiring a 14-50R Outlet with 2-P, 50A GFCI and Neutral
Wiring a 14-50R Outlet with 2-P, 50A GFCI and Neutral

Wiring 60A – 120/240V GFCI Breaker

The following wiring diagrams shows a NEMA 14-60 receptacle/outlet is protected using 2-P, 60A – 240V GFCI breaker.

How to Wire a NEMA 14-60 Receptacle with a 2P GFCI

Wiring 3-Phase, 3-Pole GFCI Breakers

The following wiring diagram demonstrates how to wire a 20A, 120/208V, three-phase, three-pole GFCI breaker using a four-wire system (three hot wires, one neutral, and one ground).

As shown in the wiring diagram, the pigtail of the built-in white wire is connected to the neutral busbar in the load center. The three hot conductors (black, red, blue) are connected to the input terminals of the 3-phase GFCI.

Similarly, the output terminals are wired through the same phase wires from the GFCI to the three-phase load. If a neutral is needed, it should be connected from the neutral bar located in the main panel or load center.

Click image or open in a new tab to enlarge

How to Wire a 3-Phase, 3-Pole GFCI Breaker

It should be noted that this three-line wire supply arrangement will provide a 208V, three-phase supply to the load points. The same wiring diagram applies to a 120/208/240V (high leg delta), three-phase supply or any other three-phase power while wiring a 3-pole, 3-phase GFCI breaker.

Similarly, the following wiring diagram illustrates a three-phase, three-pole, four-wire GFCI breaker installed in a 120/208V, three-phase panel. Note that the load neutral is optional and if the connected equipment does not require a neutral conductor, the neutral terminal on the three-phase GFCI breaker should remain unused.

Click image or open in a new tab to enlarge

Wiring a 3-Phase, 3-Pole GFCI Breaker in a 120-208-240V High Leg Delta

Moreover, the following wiring configuration is used to wire a 3-phase, 208Y/120V NEMA 18-60 receptacle. As illustrated below, the non-grounding receptacle is supplied via a 3-pole GFCI circuit breaker equipped with a neutral conductor and without EGC.

Wiring a 3-Phase, 208Y/120V, NEMA 18-60 Receptacle with a 3-Pole GFCI

In addition, the diagram given below illustrates the wiring connection for a 3-phase, 120/208/240V, NEMA 15-60 receptacle. The circuit is protected by a 3-pole GFCI circuit breaker and, as shown, does not require a neutral conductor.

Wiring a 3-Φ - 250V, NEMA 15-60 Receptacle with a 3-Pole GFCI

Good to Know:

The wiring connections are same for both GFCI and AFCI breakers in both single phase and three phase circuits.

Related Posts:

Wiring a 3-Phase, 4-Pole GFCI Breaker (RCD/RCBO)

Since there are no official 4-pole GFCI products available, you may use a 4-pole RCCB or RCBO for the same purpose when needed. Although it’s unclear what specific scenario in North America would require a 4-pole GFCI, as a 3-pole GFCI with an additional neutral from the neutral bar can often suffice, this solution addresses a query from a member who needs all four wires secured in a single unit.

If you encounter a situation where you need to install and wire a 4-pole GFCI in a three-phase circuit, a quick fix is to wire a 4-pole RCCB, which functions similarly to a GFCI.

In the three-phase wiring diagram for GFCI, RCD, or RCBO, the three lines (L1, L2, and L3) and neutral are connected as inputs to the RCCB from the main board, following an MCB for overcurrent protection.

The lower four terminals and ground wire of the RCBO are connected to the spa control box in the following sequence: Red (L1), Yellow (L2), Blue (L3), Black (Neutral), and Green/Yellow (Ground/Earth).

The following diagrams show the three-phase four-pole RCBO (RCCB + MCB) circuit breaker used to control and protect a hot water spa.

Wiring a Three Poles RCBO (MCB + RCB or RCD)Circuit Breaker

For three-phase spa wiring, use 12 or 10 gauge wire for each line. For example, use #12 or 4.0mm² wire for up to 12kW, three-phase 415V – 480V systems where the maximum current is 18.2A. Use #8 or 6.0mm² wire for the same 12kW spa in a three-phase 208V system where the maximum current is 33.3A. For higher wattage, use the appropriate wire size according to the table and user manual.

Related Posts:

Precautions:

  • Switch off the main circuit breaker to ensure the power supply is OFF before wiring a GFCI outlet.
  • Use the suitable voltage and ampere rating of the switch with the appropriate wire size and proper size MCB according to the load rating.
  • Use the correct polarity, i.e., verify the load and line terminals while installing a GFCI for protection. In other words, connect the wires to the correct side of the GFCI and outlet for proper operation.
  • Regular maintenance, checks, and tests are recommended. Test the portable GFCI before each operation.
  • Contact an authorized and licensed electrician for GFCI installation if you are unsure about the wiring diagrams.
  • For illustration purposes only, we have used in the last wiring diagram (where RCD or RCBO is wired instead of GFCI) red for hot or line 1, yellow for line 2, blue for line 3, black for neutral, and green for ground. Follow your area’s wiring color codes according to NEC, IEC, etc.
  • The author will not be liable for any losses, injuries, or damages from the display or use of this information or if you try any circuit in the wrong format. So please, be careful because it’s all about electricity, and electricity is very dangerous.

Resources

Related Wiring Installation Diagrams and Tutorials:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

11 Comments

  1. I wants to know about types of earthing,,energy saving lights,safty divice,transformer safty and new incoming of electrical technology

    1. Why is a plug intended for 15 amps shown attached to a 30 amp breaker?

      I admit to doing something similar in mexico using a 240 volt 30 amp 2 pole breaker on a 15 amp circuit, only because it was available, but I wired in a 15 amp sub panel breaker so pump and wire was protected for amp overload while people were protected for current to ground.

  2. Notice: if you are not an electrician, leave this work to the professionals. The only way to make sure you and your family is safe is to have a valid licensed electrician perform these tasks. Thanks.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button