Sizing a Star-Delta Starter with Contactors for a 3-Phase Motor
A Star-Delta starter is used to reduce the inrush current when starting large three phase motors. The starting current of a three-phase induction motor is typically 6 to 8 times higher than its normal full-load current. If this high inrush current is not properly controlled or reduced to a safe level, it can damage or burn the motor. That’s why a Star-Delta starter is used to safely start and operate a three-phase induction motor.
A Y-Δ (Wye-Delta) starter typically consists of three contactors (Main, Star, and Delta), a thermal overload relay, and optionally, a timer. The contactors used in a Star-Delta starter are generally rated smaller than the single contactor used in a Direct-On-Line (DOL) starter. This is because each contactor in a Star-Delta configuration only handles the phase (winding) current, which is approximately 1/√3 (or about 58%) for Main and Delta and 1/3 (33%) for star contractor of the line current (IL) or full load current (FLC).
The following step by step tutorial shows how to size contactors and components of star-delta starter for three phase motors.
Steps for Sizing a Star-Delta Starter
To properly size a star-delta starter, determine the motor’s full-load current (FLC from Table) and full-load amperes (FLA from motor’s nameplate), calculate the required current for the main and delta contactor (approximately 58% of the FLC) and 33% of FLC for the star contactor, and then size the components (contactors, thermal overload relay, and conductors) accordingly as shown in the below solved example.
1 – Identify the Motor Nameplate Data
The typical motor nameplate data printed on it generally indicates the motor class type, power rating in kW or HP, Line voltage, full load amperes (FLA), locked-rotor current (LRC), service factor (SF), power factor, efficiently etc. Keep in mind that full load amperes are used to determine the thermal overload setting, while the full load current (FLC) given in NEC Table 430.250 is used to size the short circuit and ground fault protective devices i.e. breakers and fuses.
2 – Determine Full Load Current (FLC)
If FLC is not given, use the NEC Table 430.250 for standard motor currents based on HP and voltage.
3 – Size the Components for Star-Delta Starter
| Component | Sizing Rule |
| Main Contactor | 58% of full-load current |
| Star Contactor | 33% of full-load current |
| Delta Contactor | 58 of full-load current |
| Overload Relay | Set at 100% of motor FLC |
| Circuit Breaker (CB) / Fuse | Use NEC Table 430.52 |
| Power Cable | Use NEC Table 310.16, select for FLC |
To properly size the star/delta contactors, selecting the correct size of conductors, breakers/fuses, and overload protection for motor starters, consider the following example.
Example – Y-Δ (Wye-Delta) Starter for 3-Phase Motor
What are the appropriate sizes for the Main, Star, and Delta contactors, along with the associated starting components, for a Star-Delta starter used with a 50 HP, 3-phase, 480V squirrel-cage induction motor operating at 95% efficiency and a power factor of 0.9? The FLA is 60A. The overload relay is placed after the winding split into main and delta contactor.
Given Data
- Motor Power: 50 HP
- Voltage: 480V, 3-phase
- Power Factor (PF): 0.9
- Efficiency (η): 95%
- Full Load Amperes (FLA) = 60A (From Motor nameplate)
- Full Load Current (FLC) = 65A (From NEC Table 430.250 for a 50 HP, 480V motor)
Step 1: Sizing the Contactors
Main and Delta Contactors:
As mentioned before, the size of all three contactors in start delta starter is smaller than the one main contactor used in DOL starter as they are used to control the phase current in motor winding only, not the line current or full load current.
The main contactor is used for start, transition and running while the delta contactor is used for running after transition from star configuration into delta.
The main contactor and delta contactor should be sized to handle 58% of the full-load current (FLC) or line current of the motor.
The value of winding current:
IP = 1/√3 × (IL or FLC)
IP = 1/1.732 × (IL or FLC)
IP = 58% × 65A
IP = 37.7A
Star Contactor:
Star contactor is used to carry the starting current only. Hence, it is sized 1/3 of the full load current (FLC) or line current. The star contactor carries approximately 33% of the motor’s full-load current.
IP = 1/3 × (IL or FLC)
IP = 33% × 65A
IP = 21.45A
In short, the required contactor ratings for a Star-Delta starter for the given motor are:
- Main Contactor: 58% × 65A = 37.7A ≈ 40A
- Star Contactor: 33% × 65A = 21.45A ≈ 25A
- Delta Contactor: 58% × 65A = 37.7A ≈ 40A
Selected Contactors: 40A (Main), 25A (Star), 40A (Delta).
The making and breaking capacity of AC3 contactors for squirrel cage induction motor can be calculated as follow:
- Making/Breaking Capacity : FLC × 10
- Making/Breaking Capacity : 65A × 10 = 650A
Step 2: Size the Overload Relay
According to the NEC, the overload relay should be rated at 125% of the motor’s full-load ampere (FLA) if the motor has a service factor of 1.15 or greater or a temperature rise of 40°C or less. For general-purpose motors that do not meet these conditions, the overload relay should be rated at 115% of the FLA. Refer to the motor nameplate to obtain the full-load amperage (FLA) at the operating voltage.
Since it is a Star-Delta starter and it draws phase current, which is lower than the line current (approximately 58%) the overload relay should be sized accordingly. Hence, the overload relay is typically rated at 58% of the motor’s full-load current, to match the reduced phase current during the start-up and running conditions in the star and delta connection.
Overload Setting = 60A × 58% = 34.8A
According to IEC standards, the thermal overload relay should be rated at 100% of the motor’s full-load current (FLC). However, in a Star-Delta starter configuration, the overload relay is typically sized at 58% of the FLC, since it is installed in the phase where the current is reduced during startup. The relay setting range usually allows adjustment from 70% to 120% of the full-load phase current for minimum and maximum rating based on motor characteristics and application.
- OL Relay Setting = 65A × 58% = 38A
- Min. Relay Setting = 65A × 70% = 26A
- Max. Relay Setting = 65A × 120% = 45A
Step 3: Size the Circuit Breaker
The size of Overcurrent Protection Devices (OCPDs) for short-circuit and ground-fault protection is determined according to NEC 430.52 and Table 430.52(C)(1). Based on the table: Dual-element time delay and non-time-delay fuses are rated at 175% and 300% of the motor’s full-load current (FLC), Inverse time circuit breakers are rated at 250% of the FLC, and Instantaneous trip circuit breakers are rated at 800% of the FLC.
- Dual Element Time-delay Fuse Size= 65A × 175% = 113A
- Non-time-delay Fuse Size= 65A × 300% = 195A
- Inverse Time Breaker Size = 65A × 250% = 162.5A
- Instantaneous circuit Breaker Size = 65A × 800% = 520A
If we go with inverse time circuit breaker, the next available size is 175A.
Step 4: Size the Power Cable
Using NEC Table 310.16, for 65A (for continuous load), the selected cable is THHN Copper wire in the 75°C column: 65A → 4AWG
Final Selection for Star-Delta Starter
| Component | Selection |
| Main Contactor | 40A |
| Star Contactor | 25A |
| Delta Contactor | 40A |
| Overload Relay | 34A |
| Circuit Breaker | 175A |
| Power Cable | 4 AWG Cu (THHN) |
Series Overview: Motor Circuit Calculations
- Part 1 – Motor Load Circuits: NEC Terms and Basic Terminologies
- Part 2 – NEC Requirements for Motor Circuits
- Part 3 – Understanding NEMA Motor Nameplate Data
- Part 4 – Calculating Locked Rotor Current (LRC) for Motors
- Part 5 – Sizing Motor Branch Circuit Conductors
- Part 6 – Sizing Motor Feeder Conductors
- Part 7 – Sizing Motor Overcurrent Protection and OCPD’s Devices
- Part 8 – Sizing Motor Feeder Protection
- Part 9 – Sizing Motor Overload Protection
- Part 10 – Overcurrent Protection for Motor Control Circuits
- Part 11 – Sizing Disconnecting Means for Motor & Controller
- Part 12 – Sizing Motor Starter & Contactor – NEMA – NEC
- Part 13 – Sizing Direct Online (DOL) Starters/Contactors for Motors (*Bonus)
- Part 14 – Sizing Star-Delta Motor Starters/Contactors for Motors (*Bonus) … (You are Here)
Resources & Tutorials:
- Difference Between NEMA and IEC Motor Starters & Contactors
- Difference Between Direct-On-Line (DOL) and Star Delta Starter
- Cable Size Calculation for LT & HT Motors
- Three Phase Motor Power & Control Wiring Diagrams
- What is Motor Efficiency & How to improve it?
- Star Delta 3-phase Motor Automatic starter with Timer
- VFD Bypass Star-Delta Starter – Power and Control Circuits
- Star & Delta Starter Using Different PLCs – Wiring and Ladder Diagram
- Star-Delta Starter for Reverse & Forward Operation Without Timer
- How to Run a Three-Phase Induction Motor on a Single-Phase Power Supply?
- How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
- How to Wire Twin Timer in Repeat Cycle & One-Shot Mode for 120V/240V Motors?
- How to Control a Single-Phase Motor from Multiple Locations?
- Wiring of DOL Starter for Automatic / Manual Control Using Digital Timer
- How to Reverse and Forward a Three-Phase Motor Using a VFD?
- How to Wire a VFD with Motor, PLC, Switches & External Devices
- Sequential Motor Control Circuit Using LOGO! V8 PLC
- Automatic Reverse Forward Motor Control Circuit Using Delta – DVP-14SS PLC
- Reverse Forward Motor Control Circuit Using PLC – ZEN Programming Relay
- Motor Protection – Types of Faults and Protection Devices
Wire Sizing Guides
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Size a Branch Circuit Conductors with Protection?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
- How Size a Circuit Breaker for Different Load Applications

Germany’s Electric Drone Hits 699 km/h, Eyes World Record
How to Wire and Use Tesla Gen 3 Mobile Connector Charger
How to Wire 48A Level 2 Dual Port EV Charging Station
How to Wire Smart Electric Vehicle Charging Station – 32A/80A
How to Wire ChargePoint Home Flex Charger for Every EV
How to Wire an EV Wall Charger – Hardwired and Plug-in