Part 2 – NEC Requirements for Motor Circuits

General Requirements for the Design, Installation, and Protection of Motors, Motor Circuits, Controllers, and Disconnects – 2023 NEC Article 430

As discussed in part 1, motor circuits differ significantly from general electrical circuits due to their high inrush current at startup. When a motor starts, its inductive load causes it to draw an inrush current that is typically 6 to 8 times higher than its full load current (FLC). Because of this high starting current, motor circuit requirements differ from those of general circuits. For example, the sizing of conductors and overcurrent protection for motor circuits must be designed differently than for lighting circuits or equipment with resistive loads.

To address these considerations, NEC Article 430 provides detailed guidelines for motor circuits and controllers. This article helps determine the appropriate conductor size, branch circuit protection, feeder protection, controller specifications, control circuit conductors, overload protection, and disconnecting means to ensure safe safe installation and operation of electric motors.

NEC Requirements for Motors

NEC Article-430 Requirements for Motors 

The National Electrical Code (NEC) 2023 outlines comprehensive rules and regulations for motor circuits. It explains the designing of motor circuits, calculation and installations to ensure safety, efficiency, and compliance with electrical standards. The extensive and compressive Article – 430 discusses the key requirements related to motors, covering motor locations, conductor sizing, overcurrent protection, disconnects, and controllers.

Motor Locations

The NEC defines requirements for motor locations based on environmental factors such as:

Highest Rated Motor

When multiple motors are supplied by a single feeder, the highest-rated motor affects conductor sizing and overcurrent protection (430.24). NEC 2023 requires the largest motor to be factored at 125% of its full-load current (FLC) when determining conductor size and protection ratings (430.17). The values of full load current (FLC) for different types of motors are given in Tables 430.247 430.248 430.249 and 430.250.

Motor Conductor Size

According to (430.6(A)(1) & 430.22(A) through (G)), conductors for single motor circuit must be sized based on FLC values listed in NEC Tables 430.247 through 430.250. For instance:

Feeder conductors supplying multiple motors are sized based on values of FLC (Tables 430.247 through 430.250) in accordance with 430.24(1) through (4) as follow:

Motor branch circuit conductors for multiple motors are selected from Table 310.16 based on the terminal temperature rating (60°C, 75°C, or 90°C) as per NEC 430.24.

All motor applications are considered continuous duty unless specified otherwise or controlled for non-continuous operation, such as an elevator motor.

For non-continuous motors, such as those used in short-time, intermittent, periodic, or varying-duty applications, the conductor size is selected based on a percentage of the motor nameplate full load amperes (FLA). According to Table 430.22(E), the conductors used for such motors must have an ampacity equal to the specified percentage of the motor’s FLA.

Warning: Do Not use the FLA rating of motor for sizing conductors. Instead, Use the FLC values in NEC tables. FLA rating is used for overload protection.

Sizing Motor Branch-Circuit Protection

An OCPD (overcurrent protective device) is used for branch circuit protection. These OCPDs (such as fuses and circuit breakers) protect the motor branch circuit conductors against short circuit and ground faults. (430.51)

According to 430.52(B), The rating of an OCPD device must capable to safely handle the high starting current of motor. OCPDs for motor branch circuit are used in accordance with 430.52(A), 430.52(B) through (D).

OCPD’s devices for motor branch circuit conductors against short circuit and ground faults are sized based on Table 430.52(C)(1). If the calculated value is not a standard ampere ratings, the next available standard rating or setting listed in 240.6 shall be selected. (430.52(C)(1)(A)).

Note: Branch circuit protection does not protect against overload conditions.

Per NEC 430.52 and Table 430.52(C)(1), the setting and rating of short-circuit and ground-fault protection must be sized based on motor type:

Good to Know: If the standard breaker or fuse rating does not match the allowed percentage, the next higher standard size can be used (NEC 240.6(A)).

Motor Feeder Protection (NEC 430.62)

Feeder conductors for motors are sized based on NEC 430.24. The maximum allowable rating for a specific protective device is determined by 430.52 or 440.22(A).

Motor Overload Protection

When the current exceeds the conductor ampacity due to equipment operating above its normal current rating, it is known as an overload condition. This type of overcurrent causes excessive heating, which can lead to equipment failure, inability to start, damage, or even fire hazards.

NEC 430.32(A) mandates overload protection to prevent overheating:

To protect motors, motor control equipment, and motor branch circuit conductors from overheating, overload protective devices are used.

Types of Overload Protective Devices

Good to Know:

Sizing Overload Protection Devices

A continuous-duty motor rated above 1 HP and without integral thermal protection must be protected using an overload device sized according to NEC 430.32(A)(1) through (4). For example, a separate overload device is sized based on the motor’s service factor (SF) or temperature rise, ensuring that the circuit opens at no more than 125% of the motor’s nameplate full load amperes (FLA) rating.

Motors with a service factor of 1.15 or higher or a temperature rise of 40°C or less, the overload protective device must not exceed 125% of the motor’s nameplate FLA. For all other motors, the overload protective device must not exceed 115% of the FLA, as specified in NEC 430.6(A)(2).

If a motor fails to start due to overload protection sized according to 430.32(A)(1) and 430.32(B)(1), higher overload device ratings are allowed per 430.32(C)(1). The exceptions for higher overload device ratings are as follow:

For motors with a service factor of 1.15 or greater or a temperature rise of 40°C or less: The overload device can be sized up to 140% of the motor’s nameplate FLA. For all other motors, the overload device can be sized up to 130% of the motor’s nameplate FLA.

In short, overload device may be sized for:

Combined OCPD

A combined OCPD is a single-unit device designed to protect a motor from overload, short circuits, and ground faults.

According to 430.55, a single OCPD can be used for small motors or grouped motor installations to provide protection against both overload and short-circuit faults (430.32 & 430.55).

When multiple motors (both single-phase and three-phase) are connected to the same feeder, the current varies across different lines (Line 1, Line 2, and Line 3). In such cases, the motor feeder “group” is determined by balancing the currents across the phases.

Unlike branch circuit protection, where the next size up protective device is allowed (NEC 430.52(C)(1)(A)), this rule does not apply to feeder protection.

Motor Controllers

NEC 430.81 required suitable controller for all motors such as contactor, soft starters etc. Article 430.82 mandates motor controllers design to be rated as per 430.83(A) for the motor load, with:

Motor controllers can be molded-case breakers and circuit breakers – 480.83(A). If other devices are used as motor controller, the HP rating must be at least equal to the motor horsepower.

A general-use snap switch can be used as a motor controller for motors rated 2 HP or less, provided that the switch’s ampere rating is at least 125% of the motor’s full load current (FLC). In other words, the rating of switch must not exceed 80% of FLC of the motor (430.83(C)(2)).

Overcurrent Protection for Motor Control Circuits

Motor control circuit conductors are separate wires used to control the ON/OFF or delay operations of a motor starter or contactor.

Circuits Tapped Before the Motor Overload Relay

If control circuit conductors are not tapped from the motor’s branch circuit, they require overcurrent protection as per NEC 724.43 (or Table 11(A) and Table 11(B) in Chapter 9) in accordance with 430.72(A). These circuits are classified as Class 1 remote-control circuits and must be protected accordingly.

Circuits Tapped After the Overload Relay

If control circuit conductors are tapped from the motor branch circuit OCPD and extend beyond the tap enclosure, they require overcurrent protection as per 430.72(B)(1) and based on the maximum rating of the overcurrent protective device listed in Table 430.72(B)(2).

Disconnects for Motor and Control Circuit

A disconnecting means must be provided within sight of the motor and controller. According to NEC 430.75, two disconnects are required for motors. Each disconnect must:

NEC 430.102 requires a disconnecting means for motor and control circuits:

Types of Disconnecting Means

Per NEC 430.110, types of motor disconnects can be 7 types listed in 430.109(A)(1) through (7). e.g.

Good to Know: If the disconnecting means is not in sight, a lockable breaker (per NEC 110.25) can be used.

Adjustable-Speed Drives (ASDs)

The ampacity of conductors supplying Adjustable Speed Drives (ASDs) (which have multiple power ratings and currents) must be at least 125% of the ASD’s rated input current (430.122(A)).

The ampacity of conductors between the power conversion equipment and the motor must be at least 125% of the motor’s full load current (FLC) as listed in NEC Tables 430.247 through 430.250.

The ampacity of conductors supplying multiple motors or other loads, including power conversion equipment, must be rated according to NEC 430.24.

The disconnect switch used for an ASD must be rated at least 115% of the rated input current of the conversion unit (430.128).

Power conversion equipment circuits must be protected by a branch circuit protective device as required by NEC 430.130(A). The protective device sizing can be determined using: 430.52(C)(1), or the motor’s full load current (FLC) rating (NEC 430.6(A) & (B)).

NEC 430.124 governs adjustable speed drives (ASDs) and variable frequency drives (VFDs) which must:

Additional overload protection is not required if the ASD has built-in overload protection.

General Requirements for Motor Circuit Design

  1. Conduit and Raceway Sizing: Must accommodate conductor fill limits – (300.17).
  2. Grounding and Bonding: Motors must be properly grounded to prevent electric shock. The size of the equipment grounding conductor (EGC) must follow Table 250.122 based on the breaker or fuse size. (NEC 250.110 & 250.122)
  3. Voltage Drop Considerations: Voltage drop must not exceed 5% from the panel to the motor (210.19(A)(1)).
  4. Multi-motor Installations: Use group motor protection when multiple motors share a feeder.

Series Overview: Motor Circuit Calculations

Resources & Tutorials:

Exit mobile version