How to Wire a 30A – 250V, NEMA 6-30 Receptacle

How to Install a NEMA 6-30 (30A – 250V) Receptacle with 2P Breaker & GFCI Protection for EVs & Heavy-Duty Appliances

A NEMA 6-30R is a 30-amp, 2P, 3W, 250V receptacle commonly used for high-power 240V appliances. It has two hot connections and an equipment grounding conductor but no neutral connection. This receptacle type is designed for heavy-duty applications such as welders, generators, large appliances, and certain EV charging stations.

A NEMA 6-30 outlet can handle 30 amps at 250 volts on a single-phase power supply. The industrial-grade 30-amp version is suitable for high-wattage industrial and residential equipment, including welders, generators, electric ranges, air compressors, and some Level 2 electric vehicle (EV) chargers.

In the following wiring tutorial, we will demonstrate how to wire a NEMA 6-30 receptacle using both standard and GFCI breakers. The wiring diagrams will also show the correct breaker and wire size for safely powering 30-amp receptacles used with high-wattage appliances and EV charging.

The NEMA 6-30 Receptacle

The NEMA 6-30R is a 250V receptacle without a neutral connection. It is designed for use with a matching 6-30P plug. As the name suggests, the “30” in 6-30R indicates the maximum current rating of 30 amperes, while the “R” stands for Receptacle (outlet). Similarly, the “P” in 6-30P stands for Plug, with “30” again denoting the maximum current rating.

The NEMA 6-30 configuration uses a 2-pole, 3-wire system for 240V appliances. This way, it does not require a neutral wire. It has two hot slots (Hot 1 and Hot 2) and one grounding slot for the equipment grounding conductor (EGC).

Terminals

There are three terminals in a 6-30 receptacle:

Click image or open in a new tab to enlarge

Terminals of NEMA 6-30, 30A-250V Receptacle

Electrical Ratings & Specifications

Good to Know:

Wiring NEMA 6-30 Receptacle with a 2P GFCI

A NEMA 6-30 receptacle for electric vehicle (EV) charging can be installed as either a plug-in outlet or a hardwired connection. The 30-amp outlet must be protected by a 30A GFCI breaker if ground-fault protection is not already built into the EV charger.

Wiring Instructions (as shown in the diagram):

Although a NEMA 6-30 receptacle can accept conductor sizes from #12 AWG to #4 AWG, the recommended wire size for this application is typically #10 AWG copper (or #8 AWG if required by derating or longer runs).

For outdoor installations, use a NEMA 3R weatherproof (rainproof) 2-gang enclosure to ensure protection against moisture and environmental exposure.

Good to Know:

The following wiring diagram illustrates the proper installation of a NEMA 6-30R, 30-amp industrial-grade receptacle using a 2-pole, 30A GFCI breaker.

Click image or open in a new tab to enlarge

Wiring NEMA 6-30 Receptacle with 2P GFCI for EVs

Good to Know:

Wiring NEMA 6-30 Receptacle with a 2P Breaker

The wiring configuration for a NEMA 6-30 receptacle with a 30A, 2-pole standard breaker is the same as when using a 2-pole GFCI breaker.

A standard breaker is often preferred for this installation because it helps prevent nuisance tripping, particularly when the EV charger or appliance already includes built-in GFCI protection (as is common with most modern EV chargers).

The following wiring diagram illustrates how to properly connect a NEMA 6-30, 30-amp receptacle using a 2-pole, 30A standard breaker for commercial and residential 240-volt applications, such as space and garage heaters, EV charging, HVAC systems, RVs and other high-power appliances.

Click image or open in a new tab to enlarge

Wiring 30A - 250V, NEMA 6-30 Receptacle with 2P Breaker

FAQs:

Should I Use a GFCI or Standard Breaker with NEMA 6-30 Receptacle?

You should use a standard 2-pole 30A breaker unless your local electrical code requires GFCI protection. Many EV chargers already have built-in GFCI protection, and double protection can cause nuisance tripping. If GFCI is required by NEC (e.g., in garages or outdoors), use a 2-pole 30A GFCI breaker.

NEC 210.8(A & B) now requires GFCI protection for 250V, 50A or less receptacles installed in, garages outdoors, basements, laundry areas, accessory buildings with a floor at/below grade not intended as habitable rooms.

That means if your NEMA 6-30R is in any of those locations, you must use a GFCI breaker (or GFCI receptacle – though GFCI receptacles for 6-30 are rare).

If the receptacle is in a dry indoor location (utility room, mechanical room, workshop) and not subject to the above, a standard 30A breaker is acceptable.

Good to Know: NEC – 210.8(A)(1) through (A)(11) and 625.54 in accordance with Articles 426.28 & 427.22 required outdoor receptacles and outlets used for EV charging must be GFCI protected.

How Many Amps Can 30A, 6-30R Handle Safely?

A NEMA 6-30 receptacle is rated for a maximum of 30 amps. For continuous loads (defined as 3 hours or more, such as EV charging), the NEC requires derating to 80% of the breaker rating (often referred to as the 125% rule), as specified in NEC 210.19(A)(1) and 210.20(A). This limits the allowable continuous current to:

An industrial-grade 30A receptacle, however, is designed to safely handle a full 30A continuous load for extended periods without overheating or deterioration, making it suitable for demanding applications such as EV charging.

These ratings comply with NEC 210.19(A)(1), 215.2, 230.42(A) for continuous and non-continuous load calculations, as well as 110.14(C) for temperature considerations.

Which Breaker Size is Suitable for 6-30 Receptacle?

For continuous loads, the NEC requires applying the 80% rule, meaning only 80% of the breaker’s rated capacity should be used for a load that runs for 3 hours or more. In addition, the overcurrent protection device (OCPD) i.e. fuse or circuit breaker must be sized at 125% of the continuous load.

According to NEC Table 210.21(B)(3), a 30-amp receptacle may serve a 30-amp branch circuit. Therefore, based on NEC 210.19(A)(1) and 210.20(A), the suitable breaker size for a 30A outlet (NEMA 6-30) is a 2-pole, 30A breaker or 30A GFCI breaker at 240V.

How Many Watts Can a 30A, 6-30 Receptacle Hold?

At 240V, a 30A outlet can supply:

What is the Correct Wire Size and Cable Type to Use with NEMA 6-30 Receptacle?

Wire Size

As stated earlier, a 30-amp outlet can be used for 24A continuous loads and 30A non-continuous loads (while an industrial-grade outlet can safely handle a full 30A continuous load).

For this ampacity, #10 AWG copper conductors are typically used and can carry:

This makes #10 AWG copper the standard wire size for a NEMA 6-30 receptacle, in compliance with NEC Table 310.16 and CEC Table 2.

For an added margin of safety (especially for long runs or high ambient temperatures) #8 AWG copper may be used with a 30A NEMA 6-30 receptacle.

Similarly, for a circuit protected by a 30A overcurrent protective device (OCPD), the equipment grounding conductor (EGC) can be #10 AWG copper, as specified in NEC Table 250.122.

Cable Types:

Can You Install NEMA 6-30R in 120V AC Circuit?

NO – NEMA 6-30R is specifically designed for two 120V hot legs that are 180° out of phase to provide 240–250V between them.

While technically possible, but you should NOT install a NEMA 6-30R on a 120V AC circuit. This is because a user could later plug in a 240V appliance in this 120V outlet expecting full voltage, which could cause the appliance to draw excessive current or fail to start properly.

Moreover, NEC 406.4(A) & 406.4(A) prohibit installing receptacles that are not properly rated for the circuit’s voltage.

If you need a 30A receptacle for 120V loads, use a NEMA 5-30R (30A, 125V, Hot + Neutral + Ground) or wire NEMA TT-30 for travel trailer and RVs.

Instructions, Precautions & Codes

Warning

Resources:

Related Wiring Tutorials

NEMA Family Outlets/Receptacle Wiring

NEMA 5 -Series

NEMA 6-Series

NEMA 10-Series

NEMA 14-Series

NEMA General Outlets/Receptacle

General Wiring Installations:

Switches Wiring

GFCI/AFCI Breaker/Outlet Wiring

Related Posts:

Exit mobile version