kVAR to Farad Calculator – How to Convert kVAR to μ-Farads?

How to Convert kVAR to Farad & Microfarad? Calculator and Examples

kVAR to Farad Calculator

The following kVAR to Farad and microfarad conversion calculator will convert the reactive power “Q” (i.e. volt amperes reactive or VAR) into microfarad “μF” millifarad “mF” and farad “F”. Both kVAR and μ-farad are terms used in capacitor banks and power factor improvement & correction to eliminate the reactive components from the load side which has multiple advantages.

To calculate the farad rating of a capacitor from the kVAR rating, just enter the value of reactive power in kVAR, voltage in volts, frequency in hertz and hit the “Calculate” button to the get the result of capacitance in μF, mF and F.

Enter Reactive Power in k-volt-amp-reactive: kVAR
Enter Frequency in Hertz: Hz
Enter Voltage in Volts: V
  
Capacitance Value of Capacitor:

kVAR to Farad Conversion Formulas & Equations

The SI unit of capacitor for capacitance is Farad. As it is a big unit and unusual to use it for small capacitors, here comes small units i.e. mF “millifarad = 10-3” and μF “microfarad = 10-6“.

Similarly, the SI unit of reactive power “Q” is VAR “Volt-Amp-Reactive”. For higher values, we mostly use kVAR “103” or MVAR “106” etc.

μF = Q in kVAR x 159.155 x 106 ÷ (Frequency in Hertz x Voltage2 in Volts)

C = 159.155 x 106 x kVAR ÷ f x V2     …     in microfarad

or

C in μF = Q in kVAR x 109 ÷ (2π x Frequency in Hertz x Voltage2 in Volts)

C = kVAR x 109 ÷ (2π x f x V2)     …     in microfarad

C = kVAR x 109 ÷ (6.283 x f x V2)     …     in microfarad

In Short:

  • C = 159.155 x 106 x Q in kVAR ÷ f x V2     …     in microfarad
  • C = 159.155 x 103 x Q in kVAR ÷ f x V2     …     in millifarad
  • C = 159.155 x Q in kVAR ÷ f x V2     …     in Farad

or

  • C = kVAR x 109 ÷ 2πf x V2     …     in microfarad
  • C = kVAR x 106 ÷ 2πf x V2     …     in millifarad
  • C = kVAR x 103 ÷ 2πf x V2     …     in Farad

Where:

  • C = Capacitance of a Capacitor in Farads
  • kVAR = kilo-Volt-ampere-reactive “Q”
  • V = Voltage in volts
  • f = Frequency in Hertz

kVAR to Farad Calculator - How to Convert kVAR to Farads

Related Posts:

How to Convert kVAR to μF & Farad?

To convert the kVAR to Farad or microfarad, you must know the value of voltage, kVAR and supply frequency (i.e. 50Hz or 60Hz). Lets see the following solve example which shows how to convert the kVAr to Farad, millifarad and microfarad.

Example:

An 8 kVAR capacitor bank is connected across the 480V having a 60Hz frequency for power factor improvement. Find the value of capacitor in Farad, millifarad and microfarad?

Solution: 

Putting the values in the related formulas as follows:

Capacitor Value in Farad “F” :

C = 159.155 x 8kVAR ÷ (60Hz x 4802 V)

C = 0.000092     …     F

Capacitor Value in Farad “mF” :

C = 159.155 x 10-3 x 8kVAR ÷ (60Hz x 4802 V)

C = 0.092     …    mF

Capacitor Value in Farad “μF” :

C = 159.155 x 10-6 x 8kVAR ÷ (60Hz x 4802 V)

C = 92.10     …    μF

Related Posts:

kVAR to Microfarad Conversion Chart

The following table shows the different values of kVAR converted to Microfarad “μF” at 240V and 480V having 50Hz and 60Hz frequency respectively.

kVAR Microfarad “μF”
240V 480V
50 Hz 60 Hz 50 Hz 60 Hz
1 55.26 46.05 13.82 11.51
2 110.52 92.10 27.63 23.03
3 165.79 138.16 41.45 34.54
4 221.05 184.21 55.26 46.05
5 276.31 230.26 69.08 57.56
6 331.57 276.31 82.89 69.08
7 386.84 322.36 96.71 80.59
8 442.10 368.41 110.52 92.10
9 497.36 414.47 124.34 103.62
10 552.62 460.52 138.16 115.13
11 607.88 506.57 151.97 126.64
12 663.15 552.62 165.79 138.16
13 718.41 598.67 179.60 149.67
14 773.67 644.73 193.42 161.18
15 828.93 690.78 207.23 172.69
16 884.19 736.83 221.05 184.21
17 939.46 782.88 234.86 195.72
18 994.72 828.93 248.68 207.23
19 1049.98 874.98 262.50 218.75
20 1105.24 921.04 276.31 230.26
21 1160.51 967.09 290.13 241.77
22 1215.77 1013.14 303.94 253.28
23 1271.03 1059.19 317.76 264.80
24 1326.29 1105.24 331.57 276.31
25 1381.55 1151.29 345.39 287.82
50 2763.11 2302.59 690.78 575.65
100 5526.22 4605.18 1381.55 1151.29
500 27631.08 23025.90 6907.77 5756.47
1000 55262.15 46051.79 13815.54 11512.95

Here is the chart in image form if you need to download it for later use.

 

Related Electrical and Electronic Engineering Calculators:

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.