Electrical DesignElectrical WiringHow ToLighting

How to Wire Double Pole, Single Throw Switch? Wiring DPST

How to Wire an DPST Switch? Controlling 120V/240V & 230V Circuit using Double Pole, Single Throw Switches

What is Double Pole, Single Throw (DPST) Switch?

DPST stands for Double Pole, Single Throw switch. It is basically two SPST switches packed in a single unit and operated by a single handle (common for both single pole, single throw switches).

Double Pole, Single Throw switch has 4 terminals as L1, L2, L3 and L3. The L1 and L2 terminals are connected to the incoming lines (say Hot 1 and Hot 2 in case of 240V – NEC or Phase and Neutral in case of 230V – IEC) and L3 and L4 connect to the load appliances.

DPST Double Pole Single Throw Switch

The DPST switch is the same as the 2-Poles 240 volts breaker which is used to breaker (OFF) or ON the 240V circuits via Line 1 and Line 2. Alternately, it can be used to control two circuits while the ON and OFF operation for both circuits will be the same e.g. it can only perform a single operation either ON or OFF.

The following fig shows the basic operation (Opening and Closing of both contacts) of a DPST switch rated for 120V – 277V.

Click image to enlarge

DPST - Double Pole, Single Throw Switch

Double Pole, Single Throw (DPST) switch is used to control a 240V circuit, where both supply lines (Hot1 and Hot2) must be switched at the same time. While there is no need for a Neutral wire in 240V circuits, if so, it may be directly connected to the load point according to the user manual.

Caution: Switches are always wired on the Phase (Line or Hot) wires same as fuses.

Related Wiring Diagrams:

Working of DPST Switch?

The following gif and short video illustrates how a double pole, single throw switch works in the circuit.

Operation of DPST- Double Pole, Single Throw Switch

Short Video:

Let’s see how to wire a DPST switch for different applications.

Related Posts:

Controlling & Wiring a Light Bulb as Single Load using DPST Switch

The following wiring diagram shows an LED bulb is wired and controlled through a dual pole, single throw switch. Both the Line and Neutral can be connected as well as disconnected using the DPST switch. The wiring diagram applies on both DC and AC 230V or 120V.

How to Wire Double Pole, Single Throw Switch How to Wire DPST Switch

Related Posts:

Controlling Two Light Bulb as Double Load using DPST Switch

The following wiring diagram shows two LED bulbs are wired and controlled through a DPST switch. As shown, both Lines are connected to the input terminals of double pole, single throw switch from two different sources (say Hot1 & Hot 2 or backup generator and solar panels or batteries etc.).

The Neutral wire is directly connected to the lamp holders of both lighting points. This way, both bulbs can be ON or OFF at the same time while using two different sources.

Working of Double Pole, Single Throw Switch Working of DPST Switch

Related Posts:

Wiring & Controlling a 240V Circuit using Double Pole, Single Throw Switch

In this wiring diagram, a 240V – AC load appliance (such as dryer, water heater etc.) is wired through a 30A DPST switch.  As shown, there is no need to wire the neutral wire, hence both Hot 1 and Hot 2 wires for 240V are directly connected to the double pole, single throw switch and the load point. The ground wire is connected directly to the dryer.

The DPST switch will break both the hot wires when OFF. Similarly, it will connect both Hot wires when at ON position.

Wiring & Controlling a 240V Circuit using Double Pole, Single Throw (DPST) Switch

Controlling a Water Heater Using DPST Switch

The following diagram shows a water heater is wired and controlled using a double pole, single throw switch. As shown, the common (black screws) are connected to the 240V source (Hot 1 and Hot 2) from a 2-pole breaker. The L1 and L2 terminals (brass screws) are wired to the water heater. Finally, the ground wire is connected to the water heater terminal box. Keep in mind that neutral is not needed in 240V circuits.

Click image to enlarge

How to Control Water Heater using double-pole Switch
Controlling a Water Heater Using DPST Switch

This way, the up position of the switch will ON the water heater (via both Hot wires) while the lower position will OFF the water heater. In other words, the operation of the double pole rocker will make or break both the Lines at once.

The following wiring diagram shows the wiring and controlling of 240V non-simultaneous water heater thermostat and elements using 20A DPST switch.

Click image to enlarge

230V & 240V AC Non-Continuous Dual Element 3.5kW Water Heater Thermostat Wiring

  • The brass screws should be connected to the Hot (line, live or phase) wire using the IEC & NEC Wire color codes. 
  • The green screw should be connected to the ground / earth wire (Green/Yellow or naked wire)
  • If there are no color coded screws on outlets, refer to the user manual or contact a licensed electrician.
  • Neutral Wire is not required in 240V outlets wiring (US). Also, Neutral is never connected to the switches.
  • Use the suitable voltage and ampere rating of switch with appropriate wire size and proper size MCB according to the load rating.

Precautions:

  • Switch off the main circuit breaker to make sure the power supply is OFF before wiring an existing or new outlet or switch with an electrical/junction box.
  • Contact the authorized and licensed electrician for switch installation if you are not sure about the wiring diagrams.
  • The author will not be liable for any losses, injuries, or damages from the display or use of this information or if you try any circuit in the wrong format. So please! Be careful because it’s all about electricity and electricity is too dangerous.

Related Electrical Wiring Installations tutorials:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button