1-Phase Circuits3-Phase AC CircuitsAlternating CurrentApps - SoftwareBasic ConceptsCircuit AnalysisEE CalculatorsElectrical DesignElectrical EnergyElectrical MachinesHow ToQuestions - Answers

kVA to Amps Calculator – How to Convert kVA to Amps?

How to Convert kVA to Amps? Calculator and Examples

kVA to Amps Calculator

The following kVA to Amps conversion calculator will convert the apparent power “S” (i.e. kilovolt amperes or kVA) into current “I” in amperes “A”, kiloamperes “kA”, milliamperes “mA “and megaampere “MA”.

To calculate the amperage rating of a device from the kVA rating, just enter the value of apparent power in kVA, voltage in volts, select power supply system (single phase or three phase) and hit the “Calculate” button to the get the result of current in A, kA, mA and MA.

Select Phase (1 or 3):
Enter Amps: kVA
Enter Volts: V
  
Result in Amps (A): A
Result in kiloamps (kA): kA
Result in Milliamps (mA): mA
Result in Mega-Amps (MA): MA

Related Calculators:

kVA to Amps Conversion Formulas & Equations

Single Phase kVA to Amps Conversion

I = (S x 1000) ÷ V

Amps = kVA x 1000 ÷ Volts

Three Phase kVA to Amps Conversion

Conversion with Line to Line Voltage (VL-L)

I = kVA x 1000 ÷ √3 x VL-L

I = (kVA x 1000) ÷ 1.732 x VL-L

Conversion with Line to Neutral Voltage (VL-N)

I = kVA x 1000 ÷ (3 x VL-L)

Where:

  • S = Apparent Power in Volt-Amps
  • V = Voltage in Volts
  • I = Current in Amperes
  • VL-L = Line to Line Voltage in 3-Phase Circuits
  • VL-N = Line to Neutral Voltage in 3-Phase Circuits

Note: There is no concept of apparent power in DC circuits as there is no frequency, power factor and reactive power exists in DC supply systems.

Related Posts:

kVA to Amps Calculator - How to Convert kVA to Amps

How to Convert kVA to Amps?

Keep in mind that you must know the value of apparent power in kVA and voltage to calculate the current rating in amperes of a machine.

Single Phase kVA to Amps Calculation

Current in Amperes = Apparent Power in kVA x 1000 ÷ (Voltage in Volts)

I = (kVA x 1000) ÷ V

Example: 

Find the current in amps if the RMS voltage of a 3kVA transformer is 120V.

Solution:

I = (3kVA x 1000A) ÷ 120V

I = 25 A

Three Phase kVA to Amps Calculation

Calculation with Line to Line Voltage

Current in Amperes = (kVA x 1000) ÷ √3 x Voltage in Volts

I = kVA x 1000 ÷ (√3 x VL-L)

Example:

Calculate the current in ampere of a 100kVA rated transformer having the line to line voltage of 240V.

Solution:

I = (100kVA x 1000 ÷ (1.732 x 240V)

I = 240.5 A

Calculation with Line to Neutral Voltage

Current in Amperes = Apparent Power in kVA  x 1000 ÷ ((3 x Voltage in Volts)

I = kVA x 1000 ÷ (3 x VL-N)

Example:

A three phase 180kVA rated transformer having the line to neutral voltage of 480V. Calculate the rating of current in amperes.

Solution:

I = (180kVA x 1000) ÷ (3 x 480V)

I = 125A

Related Electrical and Electronic Engineering Calculators:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button