ControlElectrical DesignElectrical WiringHow ToMotorsPLCProtection

Star – Delta Starter Using Different PLCs – Wiring and Ladder Diagram

Automatic Star – Delta Starter for Motor Control Using Different PLCs

An automatic Star Delta starter is a device that automatically controls the switching of an electric motor from the Star mode to the Delta mode. This switching is essential to reduce the inrush current that occurs during the starting of the motor. In today’s post, we will show how to program and control a three phase induction motor in star delta using PLC with wiring and ladder diagrams.

Related Posts:

Working of the PLC Program for Y – Δ Motor Starter using Timer 

Firstly, the PLC reads the status of two buttons – ON and OFF. Once the ON button is pressed, the timer Starts counting time. At the same time, the PLC monitors the status of the Star Delta Timer.

If the Timer is in the Star mode, the PLC activates the contactor for the Star mode operation of the motor. Once the preset time for the Star mode is reached, the Timer sends a signal to the PLC, which activates the contactor for the Delta mode operation.

If the Timer is already in the Delta mode, the PLC directly activates the Delta contactor. Once the OFF button is pressed, the PLC deactivates both the contactors, and the motor stops running.

In a PLC-based system, the Star Delta starter using Timer operates in the following manner:

  • Initially, the PLC reads the status of two push buttons, namely “ON” and “OFF”. Once the “ON” button is pressed, “Q1” switches on and coil “K1” becomes energized, causing Timer “T1” to Start counting time.
  • Simultaneously, when “Q1” turns on, it triggers “Q2” to turn on. This results in the energization of contactor “K3”, causing both contact “K1” and “K3” to close. Consequently, the motor Starts running in Star mode.
  • Upon reaching the preset time of 5 seconds, “T1” opens its normally closed contact, causing “Q2” to switch off and “K3” to open. At the same time, “T1” normally open contact closes, and “Q3” switches on, causing contact “K2” to close. This leads to the motor running in Delta mode.
  • Finally, if the “OFF” button is pressed, “Q1” switches off, and the circuit stops functioning.

Related Posts:

Wiring Diagrams of Start-Delta Starter Using Different PLCs

Wiring Diagrams

Wiring Diagram of Star Delta Starter using PLC – AC/DC/Relay

Click Image to enlarge

Wiring Diagram of Star Delta Starter Using PLC

Wiring Diagram of Star Delta Starter using LOGO! V8 PLC

Click Image to enlarge

Wiring Star Delta Starter using LOGO! V8

Wiring Diagram of Star Delta Starter using S7-1200 PLC

Click Image to enlarge

Wiring Star Delta Starter using S7-1200 PLC

Star Delta Motor Control Circuit using Omron PLC ZEN Programming Relay

Click Image to enlarge

Star Delta Motor Control Circuit using Omron PLC ZEN Programming Relay

Star Delta Motor Control Using Schneider Zelio Logic PLC Smart Relay

Click Image to enlarge

Star Delta Motor Control Using Schneider Zelio Logic PLC Smart Relay

Star Delta Motor Control Using DVP 14SS2

Click Image to enlarge

Wiring Diagram of Star - Delta Motor Control Circuit Using DVP 14SS2 Series PLC

Power Diagram

Power Circuit Diagram of Automatic Star - Delta Starter for Three Phase Motor

Control Diagram

Control Diagram of Star Delta Starter using Timer
Control Diagram of Star Delta Starter using Timer

Ladder Diagram

Ladder Diagram of Star Delta Starter using PLC

Related Posts: Star – Delta Motor Control Circuit Using Omron PLC ZEN Programming Relay

Programing the Star Delta Starter Using PLC

Following are the details of each rung in the ladder diagram of Star Delta starter using PLC.

Main Contactor

The operation of the main contactor is reliant upon three input devices: the normally open Start push button (I1), the normally closed stop button (I2), and the normally closed overload relay.

In order to activate the main contactor, the Start button “I1” must be pressed while the stop button “I2” is not pressed, and the overload relay remains inactive.

To ensure that the motor remains running even after the Start button is released, a normally open “NC” input labeled as “Q1” is added in parallel with the START button. This creates a push-button functionality that maintains the motor’s operation until the STOP button is pressed or the overload relay is activated.

Star Contactor

The energization of the Star contactor is dependent upon the main contactor, the normally closed contacts of the timer “T1”, and the normally closed contacts of the Delta contactor “Q3”.

As a result, the Star contactor will only activate if the main contactor is turned on, the time output is inactive, and the Delta contactor remains de-energized.

Timer T

The timer “T1” is responsible for measuring the duration after which the winding connection of the Star Delta Starter needs to be switched. The timer begins counting time as soon as the main contactor is energized.

Delta Contactor

The energization of the Delta contactor is dependent upon the activation of the main contactor (Q1), the activation of the timer “T1”, and the de-energization of the Star contactor “Q3”.

The Star Delta Timer is essential for the efficient and safe operation of electric motors, particularly in applications where high inrush currents are expected. With the help of a PLC, the switching of the motor between the Star and Delta modes can be automated, thereby ensuring a smooth and controlled Startup.

Related Power & Control Wiring Diagrams for Motors

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

One Comment

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button