How to Wire a GFCI Outlet – Wiring a GFCI Receptacle

How to Install a 15A/120V and 20A/120V GFCI Receptacle Outlet

What is a GFCI?

GFCI (Ground Fault Circuit Interrupter) is a protective device that automatically detects ground faults and leakage currents, providing personal protection against electrocution. As an outlet/receptacle, combo unit, or circuit breaker, a GFCI disconnects the power supply within milliseconds when an electric shock hazard is detected.

According to the NEC (National Electrical Code), GFCIs must be installed in locations where water and electricity are likely to come into contact. These include bathrooms, kitchens, laundry areas, workshops, swimming pools, hot tubs, and other damp or wet environments (e.g., near water pipes). See NEC Code Requirements for GFCI.

GFCI devices are especially important for cord-connected appliances and equipment used outdoors or near water. There are several types of GFCIs, including:

Related Post: GFCI: Ground Fault Circuit Interrupter. Types, Working &  Applications

In today’s wiring tutorial, we will demonstrate how to wire and install a GFCI outlet in residential settings to protect ordinary receptacles, light switches, and other connected devices.

The figure below illustrates what a GFCI is and how to wire it.

What is a GFCI and How to Wire It

Before installation, it is important to understand the difference between a GFCI outlet and a standard (ordinary) receptacle. As shown in the figure above, the Line (Hot/Live/Phase) terminals are connected to the narrow blade, while the Neutral terminals are connected to the wide blade.

In a standard receptacle, there is a breakaway fin between the upper and lower terminals, which allows both outlets to share the same supply connection. This means that connecting the incoming phase and neutral wires to one side will power both outlets.

In contrast, a GFCI outlet has no such breakaway fin. Instead, it is equipped with clearly marked LINE and LOAD terminals. The correct identification of these terminals must be verified by the nameplate data rating printed on the device or in the manufacturer’s user manual.

In the example diagram above, the LOAD terminals are not connected, meaning any downstream outlets, switches, or additional loads are not protected by the GFCI. In this case, only the two outlets built into the GFCI device itself are protected.

Next, let’s see how to wire a GFCI receptacle so that it also provides protection to additional downstream loads.

NEC Requirements of GFCI:

Wiring 15A – 120V GFCI Receptacle Outlet

As shown in the wiring diagram, the line terminals of a 15-amp GFCI receptacle are connected to the 120V supply using #14 AWG wire. The hot wire (black) and the neutral wire (white) from the 15-amp breaker in the 120V/240V main panel are connected to the narrow blade (hot terminal) and the wide blade (neutral terminal) of the GFCI receptacle, respectively.

The ground wire (green or bare copper) is connected to the ground terminal of the outlet. The 15-amp GFCI receptacle typically comes in the NEMA 5-15R configuration.

Click image or open in a new tab to enlarge

How to Wire 15A-120V GFCI Receptacle Outlet

This wiring method ensures that the receptacle is GFCI protected. According to the NEC 80% rule, a 15-amp GFCI receptacle can safely supply up to 12 amps for continuous loads and 15 amps for non-continuous loads.

Wiring 20A 120V GFCI Outlet

The wiring method for a 20-amp, 120V GFCI receptacle is the same as for the 15-amp version. The main difference is that the neutral slot is T-shaped on a 20-amp receptacle, whereas it is a straight wide slot on a 15-amp receptacle. This receptacle type is classified as NEMA 5-20R.

Click image or open in a new tab to enlarge

How to Wire 20A - 120V GFCI Receptacle

For this circuit, use #12 AWG wire and a 20-amp breaker. As per the NEC continuous load rule, a 20-amp GFCI receptacle can safely supply up to 16 amps for continuous loads and 20 amps for non-continuous loads.

Good to Know: Currently, only 15A and 20A GFCI receptacles rated for 120V are available, commonly in NEMA 5-15 and 5-20 configurations. For 240V circuits, GFCI breakers must be used since 240V GFCI receptacles are not available.

Wiring a GFCI Outlet with a Light Switch

In the first diagram, the single way switch and light bulb is connected to the load terminal of GFCI. This way, the switch and light bulb is GFCI protected.

Wiring a GFCI Outlet with a Light Switch

In the second diagram, the light switch is connected to the line terminals of GFCI. It means, the light switch is not GFCI protected and will operate as a normal circuit.

Light & Switch Connected to the Line Terminals are NOT GFCI Protected

Wiring a GFCI Outlet with a Ordinary Outlet / Receptacle

Same like above GFCI wiring diagrams, the ordinary outlet is connected to the load terminals of GFCI. So the GFCI outlet and ordinary outlet connected to the load terminals of GFCI is protected from the ground and earth leakage current.

Wiring a GFCI Outlet with a Ordinary Outlet / Receptacle

In the following diagram, the normal outlet is connected to the direct line supply i.e. line terminals of GFCI. This way, the ordinary outlet is not GFCI protected.

Outlet Connected to the Line Terminals are NOT GFCI Protected

Wiring a GFCI Outlet with Combo Switch – Outlet, Receptacle & Light Switch

In this GFCI outlet wiring and installation diagram, the combo (switch + outlet), SPST (single way) switch and ordinary outlet is connected to the load side of GFCI. It means, all the connected loads to the load terminals of GFCI are protected. The toggle switch in the combo switch outlet controls the first light bulb while the single way switch controls the second bulb. In short, all the loads is GFCI protected.

Wiring a GFCI Outlet with Combo Switch - Outlet, Receptacle & Light Switch

In the following diagram, the above load mentioned before i.e. components and devices are connected to the line terminals of GFCI i.e. they are connected to the direct main supply. This way, the combo switch – outlet, light switch and ordinary outlet are not GFCI protected.

All devices connected to the Line Terminals are NOT GFCI Protected.

You can add more loads according to your needs but keep in mind that the maximum allowable number of boxed per circuit breaker is 12 where one circuit consists of all boxes on one circuit breaker. In addition, see the following general rules of thumbs and safety precautions for GFCI installation as well.

Rule of Thumbs for GFCI

Precautions:

NOTE: For illustration purposes, we have used black for hot, white for neutral, and green for ground conductors. Always follow the local area wiring color codes (e.g., NEC, IEC), or other applicable standards).

Resources:

Related Wiring Tutorials

GFCI / AFCI Devices Wiring

General Outlets & Receptacles Wiring

Standard Breaker Wiring

Sizing Breakers, Wires, and Panels

Switches Wiring

Finding the Number of Breakers/Outlets in a Circuit

Main Panels Wiring Tutorials

Related Posts:

Exit mobile version