Automatic & Manual Control of Motor Using VFD & DOL Starter

How to Control a 3-Phase Motor using VFD and DOL starter for Auto and Manual Operations?

In industrial applications, controlling the speed and operation of motors is vital for optimizing energy consumption and process efficiency. VFDs offer an advanced solution for this purpose. However, situations may arise where a motor needs to run at full speed without VFD control, prompting the integration of a Direct-On-Line (DOL) starter with a VFD bypass mechanism. In this wiring tutorial, we will show how to automatically and manually control the speed and operation of a three-phase motor using VFD and DOL starter with the help of power and control wiring diagrams.

VFD & DOL Starter

A Direct-On-Line (DOL) starter (based on a contactor and additional thermal overload relay) is a basic motor control method where the motor is directly connected to the power supply, resulting in an immediate full-voltage start. DOL starters are cost-effective and suitable for applications where speed control is not essential.

On the other hand, a Variable Frequency Drive (VFD) is an advanced control solution that enables precise adjustment of motor speed and torque by varying the frequency and voltage supplied to the motor. VFDs offer energy efficiency, reduced mechanical stress, and enhanced process control, making them ideal for applications requiring variable speed operation and optimized energy consumption.

Components Required

  1. Three-Phase Motor
  2. 3-P MCCB
  3. 2-P MCB
  4. Variable Frequency Drive (VFD)
  5. DOL Starter (based on Contactor)
  6. 8-PIN Relay
  7. Single-Phase & Three Phase Supply
  8. Selector Switch for manual ON/OFF and DOL/VFD Operation
  9. External Start and Stop pushbuttons
  10. Wires & Cables

Wiring Auto/Manual Control of Motor using VFD & DOL Starter

Power Diagram:

  • Connect the DOL contactor’s terminals to the three-phase lines L1,L2 and L3 from 3-P MCCB.
  • Connect the output of contactor (T1,T2 & T3) to the motor’s terminals (U1, V1 & W1)
  • Now, connect the 3-phase lines from MCCB to the input terminals of VFD (R,S & T)
  • Connect the output terminals of VFD (U,V & W) to the motor’s terminals (U1,V1 and W1) as shown in power diagram.

Power Diagram of Auto & Manual Control of Motor using VFD and DOL Starter

Control Diagram:

  • Connect the phase line from 2-P MCB to the common (OFF) terminal of selector switch.
  • Connect a wire from the 1st terminal (for VFD operation) from the selector switch to the 2-L terminal of 8-PIN relay.
  • Connect a wire from the 2nd terminal (for DOL operation) from the selector switch to the two series connected external buttons (for External OFF and ON in case of manual operation i.e. bypassing VFD). Connect the second terminal of external ON pushbutton to the 14-NO and A2 terminals of contactor.
  • Connect a wire from the starting terminal of ON pushbutton to the 13-NO terminal of contactor.
  • Connect a wire from the VFD’s terminal (DCM – COM) to the 8-COM terminal of 8-PIN relay.
  • Connect the MI1 terminal of VFD to the 6-NO terminal of 8-PIN PLA relay.
  • Finally, connect the Neutral wire from 2-P MCB to the A1 terminal of contactor and 7-N terminal of relay as shown in the control circuit diagram.

Control Diagram of Auto and Manual Control of Motor using VFD and DOL Starter

Power & Control Wiring Diagram

Power and Control Diagram of Automatic and Manual Control of Motor using VFD and DOL Starter

Working and Operation

Automatic Operation:

  • Rotate the switch to the “VFD Mode”. The VFD will automatically adjust the speed and motor’s direction of rotation according to the specified program (via external program or keypad control button).
  • The motor and VFD can be switched-OFF by rotating the selector switch to the OFF position. 

Manual Operation:

  • In case of emergency, or when you need to run the motor at full speed or want to bypass the VFD, simply rotate the selector switch to the “DOL position”.
  • The motor will run at full load as it is now directly connected to the three-phase supply via DOL contactor.
  • The external pushbuttons can be used to ON or OFF the motor.
  • If you need to fully terminate the operation, simply rotate the selector switch to the OFF position.
  • If you need switch the operation to operate the motor automatically via VFD, just rotate back the selector switch to the VFD mode. It will bypass the DOL starter and motor can be controlled automatically via VFD.

Related Posts:

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.