How to Replace a 15A – 125V, NEMA 1-15 Non-Grounding Receptacle with a 1-P Breaker
A NEMA 1-15 receptacle (also called a Type A outlet) is a 2-wire, non-grounding electrical outlet rated for 15 amps at 125 volts (AC). It is one of the oldest types of receptacles used (now obsolete) in North America (U.S. and Canada).
The NEMA 1-15 design dates back to the early 1900s (standardized around 1915–1920s). By the 1960s–1970s, grounding-type NEMA 5-15 outlets (Type B) became the standard for all new construction. Since NEC 1962, grounding receptacles have been mandatory for new outlets in most installations. Currently, they are available from different manufactures like Leviton etc. and can be used as replacement for already installed outlets.
Since 2-wire non-grounding receptacles are no longer permitted for new installations, NEC 406.4(D)(2) and 250.130(C) allow their replacement only under the following conditions:
- Replace with another 2-wire receptacle: You may replace the existing non-grounding receptacle with a new one of the same type.
- Replace with a GFCI receptacle: A GFCI-type receptacle may be installed as a replacement. In this case, the receptacle must be clearly marked with the words “No Equipment Ground” or “”GFCI Protected”” to indicate that it is not connected to an equipment grounding conductor.
- Replace with a grounding-type receptacle protected by a GFCI: You may install a grounding-type receptacle if it is protected by a GFCI device such as a GFCI circuit breaker or a GFCI receptacle located at the first outlet on the circuit. In this configuration, the GFCI provides shock protection even though an equipment grounding conductor (EGC) is not present.
The NEMA 1-15 Outlet and Receptacle
A NEMA 1-15 receptacle, rated for 125V, 15A, is an outdated, non-grounding, 2-pole, 2-wire electrical outlet that features two flat slots designed to accept the two-prong plug of a NEMA 1-15P. Actually, it is the ungrounded version of a NEMA 5-15R and 5-15P i.e. receptacle and plug.
While NEMA 1-15 is is an outdated and obsolete device and can’t be installed in new buildings, still they can be replaced in older installation having two wires, double insulated appliances, and non-US regions such as Japan, where 2-prong Type A plugs (same as NEMA 1-15) are still common but typically operate at 100V. It is also used in 3-to-2 prong adapter, though their use is not recommended for safety reasons.
Terminals
There are two terminals in a 1-15R outlet.
- Hot: Black Wire → Brass Screw – Vertical Slot (I)
- Neutral (N): White Wire → Silver Screw – Longer Vertical Slot (|)
Click image or open in a new tab to enlarge
Electrical Ratings & Specifications
- NEMA: NEMA 2-20R – Straight Blade – Duplex Receptacle
- Poles: 2-Pole, 2-Wire – Non-Grounding with Neutral
- Wires: Two Wires – Hot 1 (or Hot 2) and a Neutral
- Voltage: 125V – Single-Phase AC Supply – 60 Hz
- Breaker / GFCI: 15A
- Current: 15A – 12A
- Wattage: 1,800 W
- Wire Size: #14AWG Copper
- Grade & Material: Residential Grade – Thermoplastic with Steel Strap
- Termination: Back & Side Wired
- Mounting: Screw Mounting
- Wiring: Hardwired / Dedicated Circuit
Wiring 15A/125V, Non-Grounding Outlet
To replace an existing 2-wire non-grounding 15A, 125V receptacle, (NEMA 1-15R), connect the terminals of outlet to a single-pole, 15A breaker in a 120/240V main panel as follow (shown in the wiring diagram):
Use #14 AWG copper conductors, which are the appropriate wire size for a 15A circuit and compatible with the NEMA 1-15R receptacle.
Strip the insulation from the conductors as follows:
- Side wiring: ¾ inch (19 mm or 1.9 cm)
- Back wiring: ½ inch (12.7 mm or 1.27 cm)
Connect the wires:
- Hot wire (black or red) to the brass screw terminal, which corresponds to the shorter/narrow slot.
- Neutral wire (white) to the silver screw terminal, which corresponds to the longer/wider slot.
After making all connections, tighten each terminal screw to approximately 14-18 in·lbs (1.6-2 N·m) of torque.
Click image or open in a new tab to enlarge
Good to Know:
As per NEC 406.4(D)(2): “Non–grounding-type receptacles shall not be replaced with grounding-type receptacles unless an equipment grounding conductor is provided.” In simple terms: You can only replace a 2-wire (ungrounded) outlet with another 2-wire or a GFCI-type outlet labeled “No Equipment Ground.
FAQ:
When NEMA 1-15R Introduced and Becomes Obsolete?
The NEMA 1-15 receptacle, introduced in the early 1900s and standardized around the 1915–1920s, was gradually replaced by the grounding-type NEMA 5-15 outlets during the 1960s–1970s. With the adoption of the 1962 NEC, grounding receptacles became mandatory for most new installations, effectively phasing out non-grounding NEMA 1-15 outlets in modern construction.
Why NEMA 1-15 Receptacles are Outdated?
The National Electrical Code (NEC) and Canadian Electrical Code (CEC) now require grounding (3-wire) receptacles in almost all new residential and commercial installations. That’s why NEMA 1-15 is considered outdated under modern electrical safety standards.
Reasons It’s Outdated:
- No grounding protection – increases risk of electric shock.
- Incompatible with modern grounded appliances (which use 3-prong NEMA 5-15 plugs).
- Not permitted in new construction or major renovation projects under the NEC 406.4(D) requirements.
How Many Amps Can a 1-15 Receptacle Handle Safely?
A NEMA 1-15 receptacle is rated for 15 amps at 125 volts. It should only be used on circuits protected by a 15-amp circuit breaker or fuse. As per NEC Articles 210.19(A), the 15A outlet can be used for 12A continuous load (which runs 3 or more hours) and max 15A non-continuous load.
How Many Watts Can a NEMA 1-15R Receptacle Hold?
At its rated voltage and current (120V × 15A), a NEMA 1-15R receptacle can safely supply up to 1,800 watts. However, for continuous loads, the NEC recommends not exceeding 80% of the circuit’s rating, which equals about 1,440 watts on a 15A circuit.
Which Breaker Size is Suitable for a 1-15 Outlet?
The right size breaker for NEMA 1-15 outlet is 15A single-pole breaker or GFCI.
What is the Correct Wire Size and Cable Type to Use with a NEMA 1-15?
Use #14 AWG copper conductors, which are suitable wire size for 15A circuit as per NEC Table – 310.16.
The most common cable types used are Type NM-B (non-metallic sheathed cable) for residential indoor wiring and Type AC or MC cable for commercial or metallic raceway installations.
Can You Replace a NEMA 1-15 with a NEMA 5-15 or 6-15?
NO – You cannot directly replace a NEMA 1-15 (non-grounding) receptacle with a NEMA 5-15 (grounding) or NEMA 6-15 (240V) receptacle unless proper grounding and wiring are provided.
According to NEC 406.4(D)(2), a 1-15 can only be replaced with another 1-15, a GFCI receptacle, or a GFCI-protected 5-15 marked “No Equipment Ground.” Installing a 5-15 or 6-15 without proper wiring and grounding violates code and can pose a serious safety hazard.
Warning
- Make sure to disconnect the power supply by switching OFF the breaker in the main panel before doing any electrical work.
- If you are unsure, consult with a licensed electrician to ensure any electrical work is performed safely and in compliance with your local codes, as code requirements can vary.
- The author will not be liable for any losses, injuries, or damages from the display or use of this information or if you try any circuit in wrong format. So please! Be careful because it’s all about electricity and electricity is too dangerous.
Resources:
Related Wiring Tutorials
Related Wiring Tutorials
NEMA Family Outlets/Receptacle Wiring
NEMA 5 -Series
- How to Wire a 15A – 120V Outlet – NEMA 5-15 Receptacle
- How to Wire a 20A – 120V Outlet – NEMA 5-20 Receptacle
- How to Wire a 30A – 120V NEMA 5-30 Receptacle
- How to Wire a 50A – 120V – NEMA 5-50 Receptacle
NEMA 6-Series
- How to Wire a 15A – 240V Outlet – NEMA 6-15 Receptacle
- How to Wire a 20A – 240V Outlet – NEMA 6-20 Receptacle
- How to Wire a 30A – 240V – NEMA 6-30 Receptacle
- How to Wire a 50A – 240V – NEMA 6-50 Receptacle
NEMA 10-Series
- How to Wire a 20A, NEMA 10-20 Non-Grounding Receptacle
- How to Wire a 30A, NEMA 10-30 Non-Grounding Receptacle
- How to Wire a 50A, NEMA 10-50 Non-Grounding Receptacle
NEMA 14-Series
- How to Wire a 20A – 125/250V NEMA 14-20 Receptacle
- How to Wire a 30A – 125/250V NEMA 14-30 Receptacle
- How to Wire a 50A – 125/250V NEMA 14-50 Receptacle
- How to Wire a 60A – 125/250V – NEMA 14-60 Receptacle
NEMA General Outlets/Receptacle
- How to Wire a 15A/125V, NEMA 1-15 Non-Grounding Outlet … (You are Here)
- How to Wire a 20A/250V, NEMA 2-20 Non-Grounding Receptacle
- How to Wire a 30A – 125V, NEMA TT-30 Receptacle for RVs
- How to Wire a 3-Phase, 60A – 250V NEMA 15-60 Receptacle
- How to Wire a 3-Phase, 60A – 120/208V NEMA 18-60 Receptacle
Smart Devices Wiring Series
- How to Wire 120/240V Smart Load Center with Smart Breakers
- How to Wire a Smart Breaker in a Smart 120/240V Panel
- How to Wire a Smart GFCI Breaker in a 120/240V Smart Panel
- How to Wire Smart AFCI/GFCI Breaker in a Smart Load Center
- How to Wire a Smart Switch in a 120/240V Load Center
- How to Wire a 15A Wi-Fi Smart Outlet in a Smart Panel
- How to Wire 15A and 20A Wi-Fi Smart GFCI Outlets
General Wiring Installations:
- How to Size a Breaker and Wires in AWG with EGC for Load?
- How to Wire an Outlet Receptacle? Socket Outlet Wiring Diagrams
- How to a Wire 3-Way Combination Switch and Grounded Outlet?
- How to Wire Combo Switch and Outlet? – Switch/Outlet Combo Wiring Diagrams
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- How to Wire 277V & 480V, 1-Phase & 3-Phase, Commercial Main Service Panel?
- How to Wire 240V Water Heater Thermostat – Non-Continuous?
- How to Wire 3-Phase Simultaneous Water Heater Thermostat?
- How to Wire Twin Timer for 120V/240V Circuits – ON/OFF Delay
- How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
- How to Wire Multifunction ON/OFF Delay Timer for 120V/240V Motors?
Switches Wiring
- How to Wire Single Pole, Single Throw (SPST) as 2-Way Switch?
- How to Wire Single Pole, Double Throw (SPDT) as 3-Way Switch?
- How to Wire Double Pole, Single Throw Switch? Wiring DPST
- How to Wire Double Pole, Double Throw Switch? Wiring DPDT
- How to Wire Double Switch? 2-Gang, 1-Way Switch – IEC & NEC
- How to Wire 4-Way Switch (NEC) or Intermediate Switch as 3-Way (IEC)?
GFCI/AFCI Breaker/Outlet Wiring
- How to Wire a GFCI Circuit Breaker?
- How to wire a GFCI Outlet?
- How to Wire GFCI Combo Switch and Outlet – GFCI Switch/Outlet
- How to Wire an AFCI Breaker?
- How to Wire an AFCI Outlet?
Related Posts:
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Difference Between 15-Amp and 20-Amp Outlet?
- Difference Between Socket, Outlet and Receptacle
- Difference Between NEMA 14-50 Standard Vs EV Receptacle
- How to Find the Number of Outlets on a Single Circuit Breaker?
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- Can you use 15A Breaker on 20A Circuit and Vice Versa?
- Can You use a 15A Outlet on a 20A Circuit and Vice Versa?
- Ground Terminal Up or Down: Which Way Should Outlets Face?
- What Do the Green Dot or Orange Triangle Outlets Mean?
- What Do the Different Colors of Electrical Outlets Indicate?
- Why are Outlets and Receptacles in Hospitals Upside Down?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Number of Circuit Breakers in a Panelboard?
- How to Find the Proper Size of Circuit Breaker? Breaker Size Calculator & Examples
- How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation?
- Why is the Neutral Prong or Slot Wider on a Plug or Outlet?
- What Will Happen If You Connect a Male-to-Male Plug Between Outlets


Germany’s Electric Drone Hits 699 km/h, Eyes World Record
How to Wire and Use Tesla Gen 3 Mobile Connector Charger
How to Wire 48A Level 2 Dual Port EV Charging Station
How to Wire Smart Electric Vehicle Charging Station – 32A/80A
How to Wire ChargePoint Home Flex Charger for Every EV
How to Wire an EV Wall Charger – Hardwired and Plug-in