1-Phase Circuits3-Phase AC CircuitsApps - SoftwareCapacitorsCircuit AnalysisEE CalculatorsElectrical DesignElectrical EnergyHow ToPower FactorPower System
Trending

Power Factor Correction Calculator – How to Find P.F Capacitor in µF & kVAR?

How to Calculate Capacitor in kVAR & µF for Power Factor Improvement? Calculator & Example

Power Factor Calculator

The following P.F calculator will calculate the existing or current power factor, apparent power “S” in kVA, existing reactive power “Q” in kVAR and the value of needed capacitor for P.F correction in microfarad “µF” and kVAR.

To calculate the value of capacitance of a capacitor bank in µF and kVAR, existing power factor, current reactive power in kVAR and apparent power in kVA, just enter the values of real or active power in kW, current in amps, voltage in volts, frequency in Hz (50 or 60Hz), select supply voltage system (single or three phase) and the targeted power factor (the value of needed or corrected power factor) and hit the “Calculate” button to the get the result of capacitance in μF, S in kVA and Q in kVAR.

Select Phase (1 or 3):  
Active Power in kilowatts: kW
Current in Amps: A
Voltage in Volts: V
Frequency in Hertz: Hz
Improved Power Factor:  
      
Existing Power Factor:  
Apparent Power: kVA
Existing Reactive Power: kVAR
Capacitor Needed for P.F Correction: µF
Capacitor Needed for P.F Correction: kVAR

Good to Know:

  • Both kVAR and μ-farad are terms used in capacitor banks and power factor improvement & correction to eliminate the reactive components from the load side which has multiple advantages.
  • This power factor calculator can be used for educational purposes which does not differentiate between lagging or leading power factor.
  • We assume inductive load as power factor plays an important role in inductive circuits. Capacitive circuits provide leading power factor and the value of power factor is unity “1” in pure resistive circuits.
  • The power factor correction capacitor must be connected in parallel with each phase load.

Related Posts:

Power Factor Correction Calculator – How to Find P.F Capacitor in µF & kVAR?

Power Factor Calculation Formula

Single Phase P.F Calculation

The following formula can be used to calculate power factor in single phase AC circuits.

Where:

  • Cosθ = Power factor
  • P = Real power in kW
  • S = Apparent power in kVA
  • V = Voltage in Volts
  • I = Current in Amps
  • R = Resistance in Ohms “Ω”.
  • Z = Impedance (Resistance in AC circuits i.e. XL, XC and R known as Inductive reactance, capacitive reactance and resistance respectively) in Ohms “Ω”.

Three Phase P.F Calculation

Calculation with Line to Line Voltage (VL-L)

Cosθ = kW / √ (3 x VL-L x I)

Calculation with Line to Neutral Voltage (VL-N)

Cosθ = kW / 3 x VL-N x I

Related Posts:

Capacitor in Microfarad & kVAR Calculation for P.F

The following formulas can be used to calculate the capacitance of a capacitor in farad and microfarad for power factor correction.

  • C = 159.155 x 106 x Q in kVAR ÷ f x V2     …     in microfarad
  • C = 159.155 x Q in kVAR ÷ f x V2     …     in Farad

or

  • C = kVAR x 109 ÷ (2π x f x V2)     …     in microfarad
  • C = kVAR x 103 ÷ (2π x f x V2)     …     in Farad

Additionally, the required capacitor bank in kVAR can be calculated as follow:

  • Required Capacitor kVAR = P in kilowatts (Tan θ– Tan θ2)
  • kVAR = C x f x V2 ÷ (159.155 x 106)      …     in kVAR
  • kVAR = C x 2π x f x V2  x 10-9     …     in kVAR

Where:

  • C = Capacitor in microfarad
  • kVAR = Reactive Power
  • f = Frequency in Hertz
  • V = Voltage in volts

Good to Know:

The following formulas for Impedance “Z”, active power “P”, reactive power “Q” and apparent power “S” are useful while calculating the value of desired power factor and capacitor bank in kVAR and µF.

Impedance “Z” :

  • Z =   (R2 + (XL + XC)2)     …     Z, R, XL, XC in Ohms 
  • XL = 2πfL     …     L is inductance in Henry
  • XC = 1/ 2πfC     …     C is capacitance in Farads

Active Power “P” :

Real or True Power or Active Power =   (Apparent Power– Reactive Power2) or

  • P = V x I x Cosθ     …     (in Single phase AC Circuits)
  • P =   (S2 – Q2)
  • P =  (VA– VAR2)
  • P =  3 x VL-L x I x Cosθ     …     (in Three Phase Line to Line)
  • P = 3 x VL-N x I x Cosθ     …     (in Three Phase Line to Neutral)
  • kW =   (kVA2 – kVAR2)

Reactive Power “Q” :

Reactive Power =   (Apparent Power2 – True power2)

  • Q = V I Sinθ
  • VAR =   (VA– P2)
  • kVAR =   (kVA2 – kW2)

Apparent Power “S” :

Apparent Power =   (True power2 + Reactive Power2)

  • S = V I
  • S =   (P + Q2)
  • kVA =   (kW2 + kVAR2)

Related Posts:

How to Calculate Power Factor & Capacitor in µF & kVAR

The following example shows how to calculate the required power factor, correction capacitor rating for capacitor bank in microfarad and kVAR, existing reactive power, active power and apparent power. You may compare the result of the solved example with the power factor calculator results.

Example:

A Single phase 240V, 60Hz, motor takes a supply current of 25A at a P.F (Power factor) of 0.60. The motor power factor has to be improved to 0.92 by connecting a capacitor in parallel with it. Calculate the required capacity of Capacitor both in microfarads and kVAR.

Solution:

Step 1: Calculate the Active Power of Load:

P = V x I x Cosθ1

  • P = 240V x 25A x 0.6
  • P = 3.6 kW

Additionally,

Actual KVA at Current lagging P.f

P = V x I

  • P = 240V x 25A
  • P = 6 kVA

Actual kVAR at Current lagging P.f

kVAR =   (kVA2 – kW2)

  • kVAR =   (62 kVA – 3.62 kW)
  • kVAR = 4.8 kVAR

Actual kVAR at Current lagging P.f

Step 2: Calculate the required kVAR for power factor correction

Existing P.F = Cosθ1 = 0.60

Needed P.F = Cosθ2 = 0.92

θ1 = Cos-1 = (0.60) = 53°.130; Tan θ= Tan (53°.130) = 1.333

θ= Cos-1 = (0.92) = 23°.073; Tan θ= Tan (23°.073) = 0.426

Required Capacitor kVAR to improve power factor from 0.60 to 0.92

Required Capacitor in kVAR

Required Capacitor kVAR = P in kW (Tan θ1 – Tan θ2)

kVAR = 3.6kW x (1.333 – 0.426)

VAR = 3265.2 VAR

Required kVAR = 3.2652 kVAR

Step 3: Convert kVAR to Microfarad

Required Capacitor in µF

C = kVAR x 109 ÷ (2πf x V2)     …     in microfarad

C = 3.2625 kVAR x 109 ÷ (2π x 60Hz x 2402 V)

C = 150.4 µF

Related Electrical and Electronic Engineering Calculators:

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.
Back to top button