How to Determine the Correct AWG Wire Size for a 4.8kW, 240V 1-Phase Electric Range According to NEC?
Since we’ve already covered various aspects of wire and cable sizing for different appliances, as we have already discussed the step-by-step calculation for determining the right wire size for wiring installation, sizing a circuit breaker, sizing the wire for 100 amp load circuits, and many more resources at the end of this article, we will now focus on the basic approach for determining the appropriate wire size for an 4.8kW electric range based on NEC codes and related tables.
Wire Size with Safety Factor
The first cramming approach by newbies to calculate wire size for ranges below 8kW is based on NEC Code 220-2 (safety factors) and refers to table 310-60, which, as we will see, is incorrect. Nevertheless, let’s explore how it works.
Let’s find the current in amperes in the circuit (using Ohm’s law)
I = P ÷ V
Where I is electric current in amperes, P is power in watts and V is voltage in volts.
I = 4800 W ÷ 240 V
I = 20 Amps.
As we can’t use the wire having ampacity of 20A for 20A load circuits. Let’s apply the safety factor of 1.25 (80% of the branch load should be connected to the rated ampacity of breaker or wire).
I = 20 A x 1.25
I = 25 Amps.
Based on conductor ampacity Table 310.15(B)(16), the right wire size for 25 Amps circuit is #10AWG at 60°C (140°F). Similarly, following the same rule as above, the rating of both the circuit breaker and associated 4 prongs connector/outlet (L14-30P Plug and L14-30R – Outlet) should not be less than 30A. Keep in mind that or a 4 wire system, a NEMA 14-50R outlet is recommended for higher-rated electric cookers, stoves, and ranges. You may use other types of plugs and outlets (such as 10-30R, 10-50R for old three wire system) when required/applicable.
This is all good for continuous load e.g. lighting, fans etc. Don’t stop here, move on to the next section for proper wire size based on the demand factor for non-continuous load.
Wire Size with Demand Factor
But wait a minute, the above case is different when it comes to non-continuous (non-simultaneous) loads, such as cooker ranges, water heaters, air conditioners, etc. In this scenario, another factor that affects the circuit current is known as the demand factor.
If the rating of electric ranges and other cooking appliances are less than 8-¾, the demand factor of 80% applies according to NEC Code 220.14, Table 220.55.
In this case, NEC-220.14 permits 220.55 and Table 220.55 to be used for calculating branch circuit loads for ranges. Similarly, NEC-220.11(C) permits using 220.55 for ranges for Branch Circuit load calculations. See note 3 of Table 220.55 too.
The demand for 1 unit in Column B of Table 220.55 is 80% of nameplate. This way
Wattage = 4800 W x 80% = 3840 W
Amps = Power ÷ Voltage
Amps = 3840 W ÷ 240 V
Amps = 16 A.
Additionally, if we apply safety factor of 1.25 to the calculated ampacity:
16 A x 1.25 = 20 Amps.
Now based on the NEC Table 310.16, the perfect wire size for 4.8kW (4800W), 240V single-phase electric range in #12AWG at 140°F (60°C).
The same rule applies to the associated miniature breaker, 4-prong plug (L14-20P) and outlet (L14-20R) used for an electric stove or range, i.e., the rating of the breaker should not be less than 20 amps.
Good to Know:
- Using 12AWG wire on a 20A breaker is permitted under NEC – 422.10(A)(4).
- NEC Code – 220.14 permits 220.55 and table 220.55 to be used for calculating branch circuit loads for ranges with 80% of demand factor.
- According to the safety factor specified in NEC Code – 220-2, a 20A breaker is appropriate for a 16A circuit, and similarly, a 15A breaker is recommended for a 12A load circuit.
- NEMA 14-50R outlet with associated 14-50P plug is recommended for higher-rated electric cookers, stoves, and ranges using 4 wires (two hot, neutral and ground wire). For old three wire system, you may use 10-30R, 11-30R, 10-50R.
- For added safety and to accommodate future expansions, such as replacing the current range with a higher-rated one, it’s advisable to use #10AWG wire.
Resources:
Wire Sizes for Standard Breakers, Outlet and Branch Circuits
- Wire Size for 15A Breaker and Outlet
- Wire Size for 20A Breaker and Outlet
- Wire Size for 25A Breaker and Load
- Wire Size for a 30A Breaker and Outlet
- Wire Size for a 35A Breaker and Load
- Wire Size for a 40A Breaker and Load
- Wire Size for 45A Breaker and Load
- Wire Size for 50A Breaker and Outlet
- Wire Size for 55A Breaker and Load
- Wire Size for 60A Breaker and Outlet
- Wire Size for 70A Breaker and Load
- Wire Size for 80A Breaker and Load
- Wire Size for 90A Breaker and Load
- Wire Size for 100A Breaker and Load
Sizing Wires for for General Wiring Installations
- Right Wire Size for100A Service Entrance and Load in AWG for 120V/240V Panel
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Find the Proper Size of Circuit Breaker?
- How to Size a Breaker and Wires in AWG with EGC for Load?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Size Branch Circuit Conductors with Protection?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- How to Size Motor Starter & Contactor – NEMA & NEC
- How to Size Motor Branch Circuit Conductors and Cables
- How to Determine the Number of Circuit Breakers in a Panelboard?
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- How to Determine the Right Size Capacity of a Subpanel?
- How to Size and Find the Numbers of Ceiling Fan in a Room?
- How to Size a Generator? Portable, Backup & Standby for Home & Commercial Applications
- How to Determine the Number of Lighting Branch Circuits?
- How to Determine the Number of Branch Circuits? – 3 Ways
- How to Size a Single Phase and Three Phase Transformer in kVA?
- How to Determine the Suitable Size of Inverter for Home Appliances?
- How to Calculate the Right Size of Solar Charge Controller?
- How to Calculate the Right Size Battery for PV System?
- How to Calculate the Number of Panels for a Load without Battery Backup?
- How to Size Panels, Batteries, Charge Controller and Inverter for PV System in Home
- How to Calculate the Number of Fluorescent Lamps in a Final Sub Circuit?
- How to Calculate the Number of Incandescent Lamps in a Final Sub Circuit?
- How to Calculate the Battery Charging Time & Battery Charging Current ?
- How to Calculate the Floor Area For General Lighting?
- How to Find the Number of Lights on a Single Circuit Breaker?
- How to Find the Number of Outlets on a Single Circuit Breaker?
- How to Size the Earth Conductor, Earthing Lead & Earth Electrodes?
- How to calculate the Cable size for LT & HT Motors?
- How To Locate Faults In Cables? Cable Faults, Types & Causes
- How To Calculate Your Electricity Bill?
Tools:
- Electrical Cable & Wire Size Calculator for Copper & Aluminum
- Wire & Cable Size in AWG Calculator for 1 and 3-Phase Load
- American Wire Gauge “AWG” Chart – Wire Size & Ampacity Table
- American Wire Gauge (AWG) Calculator – AWG Size Chart & Table
- Standard Wire Gauge “SWG” Calculator – SWG Size Chart & Table
- AWG/SWG to mm/mm2, inch/inch2 & kcmil Calculator & Conversion
General Wiring Installations:
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- How to Wire Single-Phase, 230V Consumer Unit with RCD?
- How to Wire a Garage Consumer Unit?
- How to Connect a Portable Generator to the Home Supply – 4 Methods
- How to Connect Automatic UPS / Inverter to the Home Supply System?
- How to Wire an Outlet Receptacle? Socket Outlet Wiring Diagrams
- How To: Electrical & Electronics Tutorials
- Basic Electrical Wiring Installation Tutorials

11 States Tighten Air Conditioner Rules Amid Heat Waves
Germany’s Electric Drone Hits 699 km/h, Eyes World Record
How to Wire and Use Tesla Gen 3 Mobile Connector Charger
How to Wire 48A Level 2 Dual Port EV Charging Station
How to Wire Smart Electric Vehicle Charging Station – 32A/80A
How to Wire ChargePoint Home Flex Charger for Every EV