How to Wire a 30A, 125V/250V – NEMA 14-30 Receptacle

How to Install a 30A – 125/250V Grounding Receptacle with Neutral – Wiring NEMA 14-30 with Breaker & GFCI Protection for Heavy-Duty EV Chargers, RVs, Electric Ranges & Dryers

A NEMA 14-30R is a common type of receptacle (outlet) found in homes and industrial equipment. They are most often used to power clothes dryers, electric ranges, welders, cooktops, compressors, generators and Level 2 electric vehicle (EV) charging.

NEMA 14-30 is a 3P, 4W receptacle which is capable to handle 30-amps at 125/250 volts of single phase power supply. The industrial grade 30-amp receptacle is suitable for high-wattage residential equipment and charging electric vehicles (EVs) which runs for hours.

In the following wiring tutorial, we will demonstrate how to wire a NEMA 14-30 receptacle using both standard and GFCI breakers. The wring diagrams also shows the correct breaker and wire size used with 30-amp receptacle for high-wattage appliances and charging EVs.

The NEMA 14-30 Receptacle

The NEMA 14-30R is a 125/250V receptacle with grounded neutral used with 14-30P plug. As the name suggests, the “30” in the 14-30R indicates the maximum amperes of current, while the “R” stands for “Receptacle (outlet). Similarly, the “P” in the NEMA-14-30P indicates “Plug”, with “30” denoting the maximum current in amperes.

NEMA 14-30 comes in a 3-pole, 4-wire configuration which means it requires a neutral wire. It has two hot slots (prongs) for Hot 1 and Hot 2, a neutral slot (in shape of half “T”, and a grounding slot for EGC.

Terminals

There are four terminals in a 14-30R receptacle in accordance with UL 498 and CSA:

Click image or open in a new tab to enlarge

Terminals of NEMA 14-30, 30A - 125/250V Receptacle

Electrical Ratings & Specifications

Good to Know:

Wiring NEMA 14-30R Receptacle with a GFCI

A NEMA 14-30 receptacle for electric vehicle (EV) charging can be either plug-in or hardwired. The 30-amp outlet must be protected by a 30A GFCI breaker if ground-fault protection is not already built into the EV charger.

As shown in the wiring diagram:

Although the NEMA 14-30 receptacle can accept wire sizes from #12 AWG to #6 AWG, the recommended conductors for this application are #10 AWG or #8 AWG, depending on the load and installation conditions.

For outdoor installations, use a NEMA 3R weatherproof (rainproof) 2-gang enclosure to provide adequate protection against moisture and environmental exposure.

Good to Know:

The following wiring diagram shows how to install a NEMA 14-30R, 30-amp industrial grade receptacle using a 2-pole, 30A GFCI breaker.

Click image or open in a new tab to enlarge

How to Wire NEMA 14-30 Receptacle - 30A, 125/250V with 2-Pole GFCI for EVs

Good to Know:

Wiring NEMA 14-30 Receptacle with Breaker

The wiring configuration of a NEMA 14-30 receptacle with a 30A, 2-pole standard breaker is the same as when using a 2-pole GFCI breaker.

A standard breaker is often preferred for this installation because it helps prevent nuisance tripping, especially when the EV charger or appliance already includes built-in GFCI protection (as most modern EV chargers do).

The following wiring diagram illustrates how to connect a NEMA 14-30, 30-amp receptacle using a 2-pole, 30A standard breaker for RVs, induction ranges, EV charging, or other high-wattage devices.

Click image or open in a new tab to enlarge

How to Wire a 30A, 125-250V, NEMA 14-30 Receptacle with a 2P Breaker for RVs

FAQs:

Should I Use a GFCI or Standard Breaker with NEMA 14-30 Receptacle ?

You should use a standard 2-pole 30A breaker unless your local electrical code requires GFCI protection. Many EV chargers already have built-in GFCI protection, and double protection can cause nuisance tripping. If GFCI is required by NEC (e.g., in garages or outdoors), use a 2-pole 30A GFCI breaker.

For instance, If you are in a state which adopted the NEC – 2020 or 2023, you have the following options:

Good to Know: NEC – 210.8(A)(1) through (A)(11) and 625.54 in accordance with Articles 426.28 & 427.22 required outdoor receptacles and outlets used for EV charging must be GFCI protected.

How Many Amps Can NEMA 14-30 Receptacle Handle Safely?

A NEMA 14-30 receptacle is rated for 30 amps maximum. For continuous loads (3+ hours, such as EV charging), NEC requires derating to 80% of breaker rating (also known as 125% rule) specified in 210.19(A)(1) and 210.20(A), so it can handle up to 24 amps continuously.

In the case of an industrial-grade 30-amp receptacle, it is designed to safely handle a continuous load of 30 amps for extended periods of time.

These ratings comply with NEC Sections 210.19(A)(1), 215.2, and 230.42(A) for continuous and non-continuous loads, and 110.14(C) for ambient temperature.

Which Breaker Size is Suitable for NEMA 14-30 Receptacle ?

For continuous load, we will use the 80% rule (which shows only 80% of the load should be connected to the rated circuit breaker). In addition, the size of the OCPD (fuse or circuit breaker) should handle 125% of the load circuit.

NEC Table 210.21(B)(3) shows 30-amp receptacle can be used to service 30-amp load circuit. Therefore, based on NEC 210.19(A)(1) and 210.20(A), the correct breaker size for 30-amp outlet (NEMA 14-30) is a 2-pole 30A breaker or GFCI at 240V.

How Many Watts Can a 30A, 14-30 Receptacle Hold?

At 240V, a 30A receptacle can supply:

What is the Correct Wire Size and Cable Type to Use with NEMA 14-30?

As mentioned before, the 30-amp receptacle can be used for 24A continuous and 30A non-continuous load, (industrial grade can be used for 30-amp continuous).

For this ampacity, the #10 AWG copper can carry 30A at 60°C (140°F), 35A at 75°C (167°F) and 40A at 90°C (194°F) which is suitable wire size for NEMA 14-30 receptacle according to NEC Table 310.16) and CEC Table 2.

To be on the very safe side, you may use #8 AWG copper with a 30-amp, NEMA 14-30 receptacle (outlet).

Similarly, for a circuit of up to 30-amp protected by OCPDs, ground wire (EGC) can be #10 AWG as per NEC Table 250.122.

Can I Use NEMA 14-30 Outlet on a 40/50A Breaker?

A NEMA 14-30 receptacle must be protected by a 30A breaker when the intended continuous/non-continuous load is up to 30A.

While 14-50 on a 30A breaker is code-compliant and technically possible, but it will cause issues with many plug-in chargers. In this case, using a NEMA 14-30 on 40/50A breakers is generally not the best idea. For maximum safety and reliability, it is better to install a hardwired EV charger instead of relying on a plug-and-outlet connection.

Can You Install NEMA 14-30R in 120V AC Circuit?

No, a NEMA 14-30 is designed for 240V, 4-wire circuits (2 hots, 1 neutral, 1 ground). This configuration is not feasible in single phase 120V supply (1 Hot + Neutral + Ground).

If 30-amp in a 120V single-phase supply is required for RVs, a NEMA TT-30 receptacle may be used instead.

Instructions, Precautions & Codes

Warning

Resources:

Related Wiring Tutorials

NEMA Family Receptacles/Outlets Wiring

NEMA 5 -Series

NEMA 6-Series

NEMA 10-Series

NEMA 14-Series

NEMA General Outlets/Receptacle

General Wiring Installations:

Switches Wiring

GFCI/AFCI Breaker/Outlet Wiring

Related Posts:

Exit mobile version