Automatic Reverse – Forward Motor Control Circuit Using Omron CP2E PLC

How to Wire Automatic Reverse – Forward Motor Control Circuit Using Omron CP2E & CP1E PLC?

Reverse forward motor control circuits are used to control the direction of rotation of a three-phase motor. The direction of rotation of the motor is controlled by reversing the phase sequence of the supply to the motor. The control of the reverse forward motor can be achieved using a Programmable Logic Controller (PLC). The CP2E PLC is a cost-effective and compact solution that can be used to control the reverse forward motor control circuit. In this article, we will discuss the automatic reverse – forward motor control circuit using CP2E PLC.

Reverse Forward Motor Control Circuit:

The reverse forward motor control circuit is a three-phase motor control circuit that controls the direction of rotation of the motor. The control circuit consists of two contactors, a thermal overload relay, and a PLC. The contactors are used to reverse the phase sequence of the supply to the motor, and the thermal overload relay is used to protect the motor from overloading. The PLC is used to control the contactors and to monitor the status of the thermal overload relay.

Related Posts:

Hardware & Components Required

Power, Wiring & Ladder Control Diagrams

Wiring Diagram

The wiring diagram of automatic reverse forward motor control circuit using CP2E PLC is shown in the figure below.

Click image to enlarge

Reverse Forward Motor Control Circuit Using Omron CP2E PLC

In this circuit, the forward contactor (KM1) and the reverse contactor (KM2) are controlled by the PLC. The thermal overload relay is connected in series with the motor and is used to monitor the motor’s temperature. The CP2E PLC is connected to the contactors and the thermal overload relay through digital input and output modules.

Related Post:

Power Diagram

Reverse-Forward Control Circuit For 3-Phase Motor - Power Diagram

Ladder Control Diagrams

Automatic Operation

The main program for the automatic reverse forward motor control circuit using CP2E PLC is shown below.

Automatic Reverse Forward Motor Control using PLC

Manual Operation

REV - FWD Motor Control using PLC

Related Posts:

Programing & Working

Program for Automatic Reverse Forward Motor Control Circuit:

The program for the automatic reverse forward motor control circuit is written using ladder logic programming such as Omron’s CX-Programmer software. The ladder logic program consists of two parts: the main program and the subroutine program. The main program is used to control the reverse forward motor control circuit, while the subroutine program is used to monitor the status of the thermal overload relay.

In the main program, the forward contactor (KM1) and the reverse contactor (KM2) are controlled by digital output modules (Q0.1 and Q0.2). The status of the thermal overload relay is monitored by digital input module (I0.5). The program starts with the initialization of the contactors and the thermal overload relay. The forward contactor (KM1) is energized, and the reverse contactor (KM2) is de-energized, and the thermal overload relay (OL) is monitored for any faults.

If the thermal overload relay (OL) is in the fault state, the contactors are de-energized, and an alarm is activated. If there are no faults, the forward contactor (KM1) is de-energized, and the reverse contactor (KM2) is energized. The program waits for a predefined time, and then the reverse contactor (KM2) is de-energized, and the forward contactor (KM1) is energized.

In the subordinate program, the status of the thermal overload relay (OL) is monitored by the PLC. If the OL relay is not in a fault state, the PLC turns on the forward contactor and turns off the reverse contactor, allowing the motor to operate in the forward direction. The motor overload flag is cleared to indicate that the motor is operating normally.

However, if the OL relay goes into a fault state, indicating that the motor is overheating, the PLC sets the motor overload flag to 1 and turns off both the forward and reverse contactors. The PLC then waits for a predetermined time before activating the motor overload alarm, which alerts the operator to the issue.

If the motor overload flag is clear, indicating that the motor is operating normally, the PLC turns off the forward contactor and turns on the reverse contactor, allowing the motor to operate in the reverse direction. The PLC then waits for a predefined time before turning off the reverse contactor and turning on the forward contactor again. This cycle repeats periodically to prevent wear and tear on the motor and ensure even usage of the contacts.

Related Posts:

To enable automatic REV-FWD operation, you can set specific timer values (e.g. 120ms) according to the ladder logic diagram. These timers will trigger automatic change in the motor’s rotation direction based on the given time.

The program ensures the safe and reliable operation of the motor by continuously monitoring the thermal overload relay and activating the motor overload alarm if necessary. It also prevents damage to the motor by periodically reversing the direction of the motor.

Overall, the Automatic Reverse Forward Motor Control Circuit using CP2E PLC is an efficient and reliable system for controlling the operation of an electric motor in both forward and reverse directions, ensuring the longevity and optimal performance of the motor.

Disclaimer: The typical circuit diagram and control program logic shown above are provided for illustration, reference, and educational purposes only. The live circuit may be expanded with additional modifications, such as interlocks, safety devices, or other applications, as per the circuit’s requirements.

Related Power & Control Wiring Diagrams for Motors

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.