1-Phase CircuitsBasic ConceptsCircuit AnalysisDC CircuitsHow To

Current Divider Rule (CDR) – Solved Examples for AC and DC Circuits

Current Division “CDR” for for Resistive, Inductive and Capacitive Circuits

What is Current Divider Rule (CDR)?

When a number of elements are connected in parallel, the current divides into a number of parallel paths. And the voltage is the same for all elements which are equal to the source voltage.

In other words, when the current passes through more than one parallel path (the voltage divider rule “VDR” or voltage division is used to calculate the voltage in the series circuits), the current divide in each path. The value of current passes through a particular branch depends on the impedance of that branch.

The current divider rule or current division rule is the most important formula that is widely used to solve circuits. We can find the current that passes through each branch if we know the impedance of each branch and the total current.

The current always flows through the least impedance. So, the current has an inverse relationship with impedance. According to ohm’s law, the current that enters the node will be split between them in inverse proportion to the impedance.

It means that the smaller value impedance has a larger current as the current chose the least resistance path. And the larger value resistance has the least current.

According to the circuit elements, the current divider rule may describe resistors, inductors, and capacitors.

Related Posts:

Current Divider Rule for Resistive Circuits

To understand the resistive current divider rule, let’s take a circuit in which the resistors are connected in parallel. The circuit diagram is shown in the figure below.

Current Divider Rule for Resistive Circuits

In this example, a DC source supply to all resisters. The voltage of resisters is the same as the source voltage. But due to parallel connection, the current divides into different paths. The current divides at each node and the value of current depend on the resistance.

We can directly find the value of current passing through each resistor with the help of the current divider rule.

In this example, the main current supplied by the source is I. And it divides into two resistors R1 and R2. The current passes through the resistor R1 is I1 and the current passes through the resistor R2 is I2.

As the resistors are connected in parallel. So, the equivalent resistance is Req.

Resistors are connected in parallel. So, the equivalent resistance is Req

Now, according to Ohm’s law;

V = I Req

Ohm's Law (for CDR)

Both resisters are connected in parallel with a DC source. Therefore, the voltage across the resistor is the same as the source voltage. And the current that passes through the resistor R1 is I1.

So, for resister R1;

Current Divider Rule for Resistive Circuit

Similarly, for resister R2;

CDR for Resistive Circuit

So, these equation shows a current divider rule for resistance connected in parallel. From these equations, we can say that the current that passes through resister is equal to the ratio of multiplication of total current and opposite resistance with the total resistance.

Related Posts:

Current Divider Rule for Inductive Circuits

When inductors are connected in parallel, we can apply the current divider rule to find the current that passes through each inductor. To understand the current divider rule, we take a circuit in which the inductors are connected in parallel as shown in the figure below.

Current Divider Rule for Inductive Circuits

Here, two inductors (L1 and L2) are connected in parallel with a source voltage V. Total current passes through the source is I ampere. The current passes through the inductor L1 is I1 and the current passes through the inductor L2 is I2.

Now, we need to find the equations for current I1 and I2. For that, we will find the equivalent inductance Leq;

equivalent inductance Leq

We know that the total current passes through the circuit are I and it is equating as;

total current passes through the Inductive circuit

So,

Eq-7

Now, for inductor L1, current passes through this inductor is I1;

Current Divider Rule for Inductive Circuit

For inductor L2;

CDR for Inductive Circuit

The current divider rule for the inductor is the same as the current divider rule for the resistors.

Related Posts:

Current Divider Rule for Capacitive Circuits

When the capacitors are connected in parallel, we can find the current passes through each capacitor by using the current divider rule. To understand the current divider rule for the capacitor, we take an example in which the capacitors are connected in parallel as shown in the figure below.

Current Divider Rule for Capacitive Circuits

Here, two capacitors (C1 and C2) are connected in parallel with a voltage source V. The current passes through the capacitor C1 is I1, and the current passes through the capacitor C2 is I2. The total current supplied through the source is I.

Now, we need to find the equations for current I1 and I2. For that, we will find the equivalent capacitance Ceq;

Ceq = C1 + C2

We know the equation for the current that passes through the capacitor. And the equation for the total current supplied by the source is;

Current Division in Capacitors

For capacitor C1, the current that passes through this capacitor is I1;

Current Divider Rule for Capacitive Circuit

For Capacitor C2;

CDR for Capacitive Circuit

The current divider rule for the capacitor is slightly different from the current divider rule for the inductor and resistor.

In the capacitor current divider rule, the current passes through a capacitor is a ratio of the total current multiplied by that capacitor to the total capacitance.

Related Posts:

Solved Examples for AC and DC Circuits using CDR

Current Diver Rule for DC Circuit

Example:1

Find the current passes through each resistor by the current divider rule for the given network.

What Current Divider Rule (CDR) - Current Division

In this example, three resistors are connected in parallel. First, we find the equivalent resistance.

find the equivalent resistance

Req = 100/17

Req = 5.882 Ω

The total current supplied by the source is I. So, according to ohm’s law;

V = I Req

50V = I (5.882Ω)

I = 50V / 5.882Ω

I = 8.5 A

Now, we apply the current divider rule to the first resister (10 Ω), and the current passes through this resister is I1;

Solved Example on CDR

Here R2 and R3 are connected in parallel. So, we need to find the equivalent resistance between R2 and R3.

Solved Example on Current Divider Rule

(R2 || R3 ) = 14.285 Ω

Solved Example on Current Divider Rule

I1 = 4.9999 ≈ 5 A

Similarly, we apply the current divider rule to the Second resistor (20 Ω), and the current that passes through this resister is I2;

Eq-17

Here,

Eq-21

(R1 || R3 ) = 8.33 Ω

Solving Electric Circuits using CDR

I2 = 2.499 ≈ 2.5 A

Now, we apply the current divider rule to the third resistor (50 Ω), and the current that passes through this resistor is I3.

Eq-20

 

 

Here,

Eq-21

(R1 || R2 ) = 6.66 Ω

Solving Electric Circuits using CDR

I3 = 1.00 A

So, the summation of all three currents will be;

I1 + I2 + I3 = 5 + 2.5 + 1 = 8.5 A

And this current is the same as the total current supplied by the source.

Related Posts:

Current Diver Rule for AC Circuit

Example-2

Consider an AC circuit having a resistor and capacitor connected in parallel as shown in the figure below. Find the current passes through the resistor and capacitor using the current divider rule. Consider 60 Hz frequency.

Current Divider Rule for AC and DC Circuits

ZR = 200 Ω = 200∠0°Ω

ZC = 1/(2 πfC) = 1/(2 π 60(5×106) )

ZC = 106 / (600 π)

ZC = 530.78 ∠-90° Ω

Now, according to the current divider rule, the equation of current passes through the resistor is;

How to find the Current using CDR

Now, similarly, we can find the current passes through the capacitor. According to the current divider rule, the equation of current passes through the capacitor is;

How calculate the AC current in the circuit using CDR

IC = 120 ∠0° (0.3526 ∠ 69.353°)

IC = 42.31 ∠ 69.353°

If you want to prove this answer, you can add both currents. And the value of this current is the same as the source current.

Related Electric Circuit Analysis Tutorials:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button

Kindly permit ads on our free website.

It appears that you are using an ad blocker. We rely on advertising to support our website, provide free information, and sustain our services. Kindly consider whitelisting our website to allow ads.