1-Phase CircuitsBasic ConceptsCircuit AnalysisDC CircuitsHow To

Voltage Divider Rule (VDR) – Solved Examples for R, L and C Circuits

Voltage Division “VDR” for for Resistive, Inductive and Capacitive Circuits

What is Voltage Divider Rule?

In a circuit, when a number of elements are connected in series, input voltage divides across the elements. And in a circuit, when a number of elements are connected in parallel, the current divides across the elements.

Therefore, in a parallel circuit, the current divider rule is used and in a series circuit, the voltage divider rule is used to analyze and solve the circuit.

When two or more impedances are connected in series, the input voltage is divided into all impedances. To calculate the voltage across each element, the voltage divider rule is used. The voltage divider rule is the most important and simple rule in circuit analysis to calculate the individual voltage of any elements.

The voltage divider rule is also known as the potential divider rule. In some conditions, we require specific output voltage. But we don’t have that specific value of the source. In this condition, we make a series of passive elements and reduce the voltage level to a specific value. And here, the voltage divider rule is used to calculate the specific output voltage.

According to elements used in the circuit, the voltage divider rule can be classified into three types; resistive voltage divider, inductive voltage divider, and capacitive voltage divider. Now, we will prove the voltage divider rule for all these types of circuits.

Related Post:

Voltage Divider Rule for Resistive Circuits

To understand the resistive voltage divider rule, we take a circuit having two resistors are connected in series with the voltage source.

As the resistors are connected in series, the current that passes through both resistors is the same. But the voltage is not the same for both resisters. The input voltage of the circuit divides into both resisters. And the value of individual voltage depends on the resistance.

Voltage Divider Rule for Resistive Circuits

As shown in the above figure, two resistors R1 and R2 are connected in series with the voltage source Vs. The total current supplied by the source is I ampere. As all elements are connected in series, it will make a single loop and the current that passes through all elements is the same (I amp).

The voltage across resistor R1 is VR1 and the voltage across resistor R2 is VR2. And the total supplied voltage divides between both resisters. Hence, the total voltage is a sum of VR1 and VR2.

VS = VR1 + VR2 … (1)

According to Ohm’s law,

VR1 = IR1 + IR2 … (2)

Therefore, from the equation-(1) and (2);

VS = IR1 + IR2

VS = I(R1 + R2)

Now, put the value of current I in the equation-(2);

VR1 = IR1

Similarly;

VR2 = IR2

Hence, the voltage divider rule for a resistive circuit is opposite to the current divider rule. Here, the voltage of the resistor is a ratio of multiplication of total voltage and that resistance to the total resistance.

Related Posts:

Solved Example of Resistive Circuit using VDR

Example-1

Find the voltage across each resistor using the voltage divider rule.

What is Voltage Divider Rule - Voltage Division

Here, three resistors (R1, R2, and R3) are connected in series with 100V source voltage. The voltage across resistors R1, R2, and R3 are VR1, VR2, and VR3 respectively.

The voltage across resistor R1;

VR3 = 500 / 30

VR3 = 16.67 V

The voltage across resistor R2;

VR3 = 100 / 30

VR3 = 33.33 V

The voltage across resistor R3;

VR3 = 1500 / 30

VR3 = 50 V

Total voltage VT;

VT =VR1 + VR2 + VR3

VT = 16.67 + 33.33 + 50

VT = 100 V

VT = VS

Hence, it is proved that the total voltage= is similar to the supplied voltage.

Related Posts:

Voltage Divider Rule for Inductive Circuits

When a circuit having more than two inductors is connected in series, the current that passes through the inductors is the same. But the source voltage is divided into all inductors. In this condition, the voltage across the individual inductor can be found by the inductor voltage divider rule.

Voltage Divider Rule for Inductive Circuits

Consider as shown in the above figure, two inductors (L1 and L2) are connected in series. And total current I pass through the inductor. The voltage across inductor L1 is VL1 and the voltage across inductor L2 is VL2. And the supply voltage is VS. Now, we need to find the voltage VL1 and VL2 using the inductor voltage divider rule.

As we know the equation of voltage for inductor;

Where Leq is the total inductance of the circuit. Here, two inductors are connected in series. Therefore, the equivalent inductance is a sum of both inductances.

Leq = L1 + L2

From, equation-(3);

Now, the voltage across inductor L1 is;

Similarly, the voltage across inductor L2 is;

So, we can say that the voltage divider rule for an inductor is the same as the resistors.

Related Posts:

Solved Example of Inductive Circuit using VDR

Example-2

Find the voltage across each inductor for the given circuit using the voltage divider rule.

Solved Example of Inductive Circuit using VDR

Here, two inductors are connected in series with 100V, 60Hz source. The voltage across inductor L1 is VL1 and the voltage across inductor L2 is VL2.

To find the voltage across inductors, we need to find the reactive impedance of each inductor.

The reactive impedance across inductor L1 is;

XL1 = 2 π f L1

XL1 = 2 × 3.1415 × 60 x 10 × 10-3

XL1 = 3.769 Ω

The reactive impedance across inductor L2 is;

XL2 = 2 π f L2

XL2 = 2 × 3.1415 × 60 x 14 × 10-3

XL2 = 5.277 Ω

According to the voltage divider rule,

The voltage across inductor L1 is;

VL1 = 41.66 V

The voltage across inductor L2 is;

VL2 = 58.35 V

Total voltage VT is;

VT =VL1 + VL2

VT = 41.66 + 58.35

VT = 100 V

VT = VS

So, the total voltage is the same as supplied voltage.

Related Posts:

Voltage Divider Rule for Capacitive Circuits

In a capacitor, the voltage divider rule is different compare to the inductor and resistor. To calculate the voltage divider rule for capacitors, let’s consider a circuit having two or more capacitors connected in series.

Voltage Divider Rule for Capacitive Circuits

Here, two capacitors are connected in series with the source voltage VS. The source voltage divides into two voltages; one voltage is across the capacitor C1 and a second voltage is across the capacitor C2.

The voltage across capacitor C1 is VC1 and the voltage across capacitor C2 is VC2. As shown in the above circuit diagram, both capacitors are connected in series. Therefore, the equivalent capacitance is;

The total charge delivered by the source is Q;

Q = Ceq VS

The voltage across capacitor C1 is;

VC1 = Q1 / C1

The voltage across capacitor C2 is;

VC2 = Q1 / C2

So, from the calculation, we can say that the individual voltage across the capacitor is a ratio of multiplication of total source voltage and opposite capacitance to the total capacitance.

Related Posts:

Solved Example of Capacitive Circuit using VDR

Example-3

Find the voltage across each capacitor for a given network using the voltage divider rule.

Solved Example of Capacitive Circuit using VDR

Here, two capacitors are connected in series with 100 V, 60 Hz source. The voltage across capacitor C1 is VC1 and the voltage across capacitor C2 is VC2.

To calculate the voltage across each capacitor, we need to find the capacitive impedance.

The capacitive impedance across C1 is;

The capacitive impedance across C2 is;

XC2 = 1 / (2 π f C2)

XC2 = 1 / (2 π × 60 × 20 ×10-6)

XC2 = 10-6 / 7539.822

XC2 = 132.63 Ω

According to the voltage divider rule, the voltage across capacitor C1 is;

VC1 = 33.33 V

the voltage across capacitor C2 is;

VC2 = 66.67 V

The total voltage across capacitor VT is;

VT =VC1 + VC2

VT = 33.33 + 66.67

VT = 100 V

VT = VS

Related Electric Circuit Analysis Tutorials:

➡️ READ FULL ARTICLE 📖

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button