Electrical DesignElectrical WiringHow To

How to Wire Spa Panel for Hot Tub using 2-P GFCI & Breaker

Wiring Installation of 40A & 50A Spa Panel for Hot Tub using 2-Pole Breaker and GFCI

A spa panel is a small, outdoor-rated disconnect enclosure that contains a 2-pole GFCI breaker and serves as the required maintenance or emergency disconnect for a 240V hot tub. The most common configuration is single-phase 120/240V, consisting of L1 Hot 1, L2 Hot 2, Neutral, and Ground. When the hot tub is located more than 5 ft 1.5 m from the main panel, a spa panel must be installed as the disconnecting means within sight of the equipment, in accordance with NEC 680.13.

The spa electrical enclosure or junction box is wired in the same manner as a subpanel. The neutral and grounding busbars are kept separate and are not bonded, unlike in the service disconnect where bonding of both ground and neutral is required.

Before beginning the wiring installation, see the NEC requirements for spas, hot tubs, and electrically heated pools provided immediately after the wiring tutorials in this article.

In the following wiring tutorial, the installation of 40A and 50A – 240V rated GFCI breakers and overcurrent protection devices for a hot tub installed in a spa panel is shown in the following figures.

Wiring 50A – 120/240V Spa Panel using 2-P GFCI & Breaker

If the hot tub is located faraway than  the the main panel, a disconnecting means (not less than 1.5m (5 ft) from the inside wall of the spa or hot-tub) is required within sight of the equipment. For this purpose, a rainproof, outdoor-rated NEMA 3R spa panel is installed. The spa panel contains a 2-pole, 240V GFCI breaker connected to two hot buses, along with separate neutral and grounding busbars. The neutral and ground are isolated and not electrically bonded, as this enclosure functions as a subpanel.

As shown in the wiring diagram for 50A dedicated GFCI panel, a 2-pole, 50A/240V standard breaker is installed in the main panel and connected to the Hot 1 and Hot 2 busbars. This breaker provides overcurrent protection for the feeder conductors supplying the spa panel.

Wiring 50A - 120-240V 2-Pole GFCI Spa Panel Box

Inside the spa panel, a 2-pole, 50A, 120/240V GFCI breaker is snapped onto the two hot bus slots. The neutral conductor and the equipment grounding conductor (EGC) are run from the main panel to the spa panel and terminated on their respective isolated busbars.

From the spa panel, four conductors (2 Hots, 1 Neutral, and 1 Ground) are connected to the spa control box and terminated as Hot 1, Hot 2, Neutral, and Ground.

Click image or open in a new tab to enlarge

Wiring 50A - 120/240V Spa Panel using 2-P GFCI & Breaker

For this 50A circuit, the appropriate conductor size is #6 AWG copper, as per NEC Table 310.16. The equipment grounding conductor (EGC) may be #10 AWG copper for a general 50A circuit, as specified in NEC Table 250.122. However, the equipment bonding conductor for pools and spas must be #8 AWG insulated solid copper or larger to reduce voltage gradients with in 5 ft of pool area, as per NEC 680.26, in accordance with NEC 250.8.

Good to Know:

  • A 240V hot tub must be hardwired to a dedicated circuit with a GFCI (Ground Fault Circuit Interrupter) safety disconnect.
  • In the spa panel the GFCI is wired downstream the standard breaker. The standard 2-pole 50A – 240V breaker can be used as maintenance disconnect, while the 2-pole 50A – 240V GFCI breaker can be used as emergency disconnect.
  • For most 240V & 208V dedicated circuits, the load side white neutral from GFCI is not required. Meanwhile, the built-in white pigtail must be connected to the neutral busbar in the main panel.
  • In a spa panel, neutral and ground must be isolated. Remove any bonding screw or strap if present.
  • Connect the GFCI breaker neutral pigtail to the spa panel neutral bar
  • The spa neutral must terminate on the GFCI breaker’s load side neutral terminal, not on the neutral bus. If landed on the neutral bus, the breaker will trip instantly.

Wiring 40A – 120/240V, 2-Pole GFCI Breaker for Hot Tub

If the hot tub or spa is located close to the main panel (not less than 5 ft (1.5m)), it is permitted to install a 2-pole GFCI breaker in the main panel and use it as the disconnecting means, without installing an additional spa panel. In simple terms, a single 2-pole GFCI breaker in the main panel is sufficient, instead of using a standard 2-pole breaker along with a separate 2-pole GFCI in a spa subpanel.

The following wiring diagram shows a hot tub, whirlpool spa, electric water heater, pool, or fountain supplied and protected by a 2-pole GFCI circuit breaker using a three-wire system consisting of two hot conductors, one neutral, and one equipment grounding conductor.

In this 2-pole, 3-wire GFCI wiring arrangement, the built-in white pigtail from the GFCI breaker is connected to the neutral busbar in the main panel. The two line conductors, Hot 1 and Hot 2, from the main panel L1 and L2 busbars of a single-phase 240V system are connected to the GFCI breaker input terminals as the breaker snaps onto the L1 and L2 busbar slots in the load center.

As shown in the diagram, the three load terminals of the GFCI breaker are connected to the spa control box according to the printed terminal markings. The center terminal is the neutral, while the first and last terminals are the two hot conductors, Hot 1 and Hot 2. Finally, the equipment grounding conductor from the ground busbar is connected to the grounding terminal in the spa control box.

Click image or open in a new tab to enlarge

Wiring 40A - 240V, 2-Pole GFCI Breaker for Hot Tub

The right wire size for 40A circuit is #8 AWG copper, as per NEC Table 310.16. Similarly for the above circuit, the equipment bonding conductor for pools and spas must be 8 AWG or larger solid insulated copper in accordance with NEC 680.26 and 250.8.

NEC Requirements for Spa Panel & Hot Tub

  1. All hot tubs, spas, swimming pools, wading pools, therapeutic pools, decorative pools, fountains, and hydromassage bathtubs must be protected by a Class A GFCI or a special-purpose ground-fault circuit interrupter (SPGFCI), in accordance with NEC 680.5.
  2. Feeders and branch circuits installed in wet locations must include an equipment grounding conductor and be electrically bonded using insulated copper conductors sized in accordance with NEC Table 250.122. The grounding conductor shall not be smaller than 12 AWG. The same requirements apply to flexible cords, plugs, and terminals used for spas and bathtubs, as specified in NEC 680.7 and 680.8.
  3. Flexible cords used for permanently installed hot tubs shall not exceed 3 ft (900 mm) in length, as required by NEC 680.8(A).
  4. The ampacity of branch-circuit conductors and the rating of overcurrent protective devices OCPDs shall be not less than 125 percent of the total nameplate-rated load for electric water heaters and swimming pool heat pump equipment, in accordance with NEC 680.10.
  5. At least one 15A or 20A, 120V, GFCI-protected receptacle supplied from a general-purpose branch circuit must be installed within the equipment area, as required by NEC 680.12(B). All receptacles supplying power to a hot tub or spa must be GFCI protected, in accordance with NEC 680.44.
  6. One or more disconnecting means must be provided within sight of the equipment and located not less than 5 ft (1.5) m away. The disconnect must be readily accessible and capable of disconnecting all ungrounded conductors supplying pool, spa, fountain, or hot tub equipment, except for lighting, as required by NEC 680.13.
  7. In corrosive or wet environments, approved wiring methods include intermediate metal conduit, rigid metal conduit, reinforced thermosetting resin conduit, rigid polyvinyl chloride PVC conduit, or liquid tight flexible nonmetallic conduit LFNC. Aluminum conduit or tubing is not permitted for these installations, in accordance with NEC 680.14.
  8. Junction boxes and electrical enclosures used for GFCI connections must be listed, labeled, and identified as swimming pool junction boxes, in accordance with NEC 680.24(A)(1) and 680.24(B)(2), and must meet the following spacing requirements:
    • Vertical spacing: The enclosure shall be installed not less than 4 in (100 mm) above finished ground level or the pool deck, measured from the bottom of the box. When measured above the pool water level, it shall be installed not less than 8 in (200 mm) above the maximum water level.
    • Horizontal spacing: The enclosure shall be installed not less than 4 ft (1.2 m) from the inside wall of the pool.
  9. Equipotential bonding using a solid copper conductor not smaller than 8 AWG is required to reduce voltage gradients in the pool and spa area, in accordance with NEC 680.26 and NEC 250.8.
  10. All receptacles rated for 125/250V, 60A or less, and located within 10 (ft 3) m of a pool, spa, or hot tub must be GFCI protected. Receptacles supplying power directly to spa or hot tub equipment must also be GFCI protected, as required by NEC 680.43(2), 680.43(3), and 680.44.

Precautions:

  • Disconnect the power source and verify that it is completely switched OFF before servicing, repairing, or installing any electrical equipment. To do this, turn OFF the main switch in the main panel.
  • Never stand on or touch wet surfaces, and avoid contact with metal parts while performing installation or repair work.
  • Carefully read all cautions and instructions, and follow them strictly while performing this tutorial or any other practical electrical work. Never attempt to experiment with electricity without proper guidance and safety precautions, as it is dangerous and can be fatal. Always carry out installation and repair work in the presence of experienced and qualified personnel who have the knowledge and practical skills to handle electrical systems safely.
  • Performing electrical work on your own can be dangerous and, in some cases, illegal. Consult a licensed electrician or the electric power supply provider before making any changes or modifications to electrical wiring or connections.
  • The author shall not be held liable for any losses, injuries, or damages resulting from the use or misuse of this information, or from attempting any circuit in an incorrect manner. Exercise extreme caution at all times. Electricity is inherently dangerous and must be handled with the highest level of care.

Resources:

Standard Breakers & GFCI Breakers Wiring Installations

Sizing Breakers, Wires, and Panels

General Outlets and GFCI/AFCI Receptacles Wiring

Switches Wiring

Finding the Number of Breakers/Outlets in a Circuit

Main Panels Wiring Tutorials

General Wiring Installation Tutorials:

Related Posts:

Electrical Technology

We are a professional team specializing in Electrical and Electronic Engineering & Technology. Join us on the Electrical Technology Official WhatsApp Channel to receive the latest content, articles, and updates. You can also follow us on our social media platforms given below or subscribe via email to get premium engineering articles delivered directly to your inbox.

Leave a Reply

Your email address will not be published. Required fields are marked *

Back to top button