How to Wire a Two-Pole Circuit Breaker in a 120/240V Panel
How to Install a Standard 2-P, 20A – 240V Breaker for Branch Circuits
Two-Pole Breakers:
A Two-pole breaker (also known as double-pole or 2-pole breaker) is a type of circuit breaker that connects to both hot wires (phase conductors) in a 240-volt circuit. It provides simultaneous protection for both conductors, meaning if an overload or short circuit occurs on either leg, both poles trip together, and shut-off the power to the entire circuit.
A double-pole breaker is essentially two single-pole breakers combined into one unit and occupies two slots in a breaker panel. It is commonly used in both residential and commercial applications for small to heavy-duty load appliances and equipment that need both hot legs for full voltage operation.
In residential applications, double-pole breakers (typically rated 15A to 60A) are used for 240V air-conditioners, water heaters, compressor, pumps, subpanel, EV charging and general-purpose outlets and receptacles. In commercial applications, double-pole breakers with ratings ranging from 15A up to 100A+ are used for heavier-duty circuits, such as HVAC, commercial kitchen appliances, industrial machinery, heavy-duty utility loads, subpanels and main switches, multi-wire branch circuits and specialized outlets.
Characteristics:
- Number of Poles: 2 poles for hot terminals (mechanically and electrically linked) which connects to both lines (L1 & L2) i.e. hot wires (red and black in the US followed by NEC).
- Voltage: Operates on and protects 240V branch circuits. (Two phases i.e. L1 and L2).
- Amperage Rating: Mostly used in 15A to 100A+. Standard Rating in NEC Table 240.6(A) is 10A – 6kA.
- Wiring: 2 hot wires from the breaker + 1 ground wire (+ 1 shared neutral (if required) from ground/neutral busbar connect to the branch circuit in a 240V supply.
- Operation: Trips when there is an overload, short circuit, or fault on the single or both hot (or phase) wire(s).
- Application: Used for standard lighting, outlets, receptacles, sockets and small to medium load appliances.
Wiring a Double-Pole Breaker
1. Before working inside the panel, switch off the main breaker to cut power to all branch circuits. Verify there’s no voltage using a non-contact voltage tester.
2. Identify the cable in 120V/240V main panel. For a 240V-only circuit, use 2-conductor cable with ground i.e.
- Black wire (Hot 1)
- Red wire (Hot 2)
- Bare/green wire (Ground)
3. Strip about ½ inch (≈12 mm) of insulation from both hot wires (black & red). Expose the ground wire for connection to the grounding bar. If using a neutral wire (white), strip it and connect it to the neutral bar.
4. Connect the Hot Wires to the Breaker:
- Insert the black wire into one terminal of the double-pole breaker.
- Insert the red wire into the other terminal.
Tighten both screws securely. These two wires will carry 120V each from opposite phases, totaling 240V between them.
5. Connect the Ground (and Neutral if applicable). Attach the bare/green wire to the grounding bar in the panel. If the circuit or appliance requires a neutral, connect the white wire to the neutral bar
6. Install the breaker into the panel. Align the breaker’s clips with the bus bars in the panel. Firmly press the breaker into place, so it should snap onto both bus bars (L1 & L2) to provide 240V.
7. Label the Breaker i.e. mark the breaker’s panel slot with a clear description, e.g., “Water Heater – 240V, 20A”.
8. Restore power and test. To do that, turn the main breaker back ON. Switch ON the new double-pole breaker. Test voltage at the appliance receptacle or connection:
- Between Hot 1 and Hot 2: ≈ 240V
- Between Hot 1 or Hot 2 and Ground: ≈ 120V each
In the example load shown in the fig, we have used to control and wire 20A – 240V receptacle (NEMA 6-20) with the help of 2-P breaker rated for 20A – 240V. For this circuit, we have used #12 AWG copper wire (Based on NEC Table 310.16), which is the correct size for a 20A circuit and the associated NEMA 5-15R outlet. In addition, Similar wire size i.e. 12AWG should be used for equipment ground conductor (EGC) per NEC Table 250.122.
As we know that 2-pole breakers are used for standard 240V circuits, therefore, two-pole breakers cannot be used in place of 1-pole breakers, which are designed for 120V circuits where only one pole (i.e., 1 hot wire either L1 or L2) are wired, control and protected.
Expect the 20A outlet, the double pole breaker can be wired for different ratings and NEMA outlets used in 240V supply systems such as.
- Wiring a two-pole breaker for 15A – 250V outlet
- Wiring a two-pole breaker for 20A – 250V outlet
- Wiring a two-pole breaker for 20A – 125/250V receptacle
- Wiring a two-pole breaker for 30A – 250V receptacle
- Wiring a two-pole breaker for 30A – 125/250V receptacle
- Wiring a two-pole breaker for 50A – 250V receptacle
- Wiring a two-pole breaker for 50A – 125/250V receptacle
- Wiring a two-pole breaker for 50A & 40A – 120/240V Spa & Hot tub
- Wiring a two-pole breaker for 60A – 125/250V receptacle
- Wiring a two-pole breaker for 60A subpanel
- Wiring a two-pole breaker for 100A Load
- Wiring a two-breaker for 100A Service Panel
Wiring 2-Pole GFCI Breakers
Wiring a 2-pole GFCI breaker is similar to wiring a standard 2-pole breaker, except for the white (built-in pigtail) wire. This pigtail must be connected to the neutral busbar in the main service panel.
In most 240V circuits, a neutral wire is not required. However, if the circuit does require a neutral, connect the neutral wire from the GFCI load side directly to the load instead of wiring it to the neutral busbar.
The following wiring diagram illustrates a 20A, 240V standard outlet protected by a 2-pole GFCI breaker rated for 20A at 240V.

Similarly, the given wiring diagrams shows the installation of 2-Pole GFI breakers with neutral and without neutral for 20A to 50A outlets etc. In addition, the wiring diagrams shows the installation of 2-Pole breakers with 15A, 20A and 30A GFCI outlets.
Instructions, Precautions & Codes
- The suitable wire size is 12 AWG copper (or #10 AWG aluminum) to use with a 20A outlet and circuit breaker – NEC Table – 310.16, Table – 210.24(1) and NEC 240.4(D)(4). Therefore, use #12/2 cable (two hot wires and one ground (and one neutral if required) for a 20A-240V breaker and associated load circuits.
- For a 20A circuit , the equipment grounding conductor (EGC) can be #12 AWG copper. NEC Table 250.122.
- The correct size of breaker is 2-pole, 20A circuit breaker or GFCI for a 20A-240V outlet – NEC 210.21(B)(2).
- With a 2-pole, 20A breaker, the appropriate cable types include NM-B (Non-Metallic Sheathed Cable) for indoor/dry locations, THHN / THWN-2 for conduit wiring (indoor/outdoor or wet locations), UF-B for outdoor or underground wiring, SOOW or SJTW (Flexible Cord) for industrial or flexible wiring.
- A double-pole 20A breaker can be used for 16A continuous load (which lasts 3 or more hours) and maximum 20A non-continuous load – 210.19(A), 210.20(A), 215.2(A), 215.3, and 230.42(A).
- A 2-pole, 20-amp breaker at 240 volt can handle non-continuous load of 4,800 watts (20A × 240V). For continuous use, limit the load to about 3,840 watts (80% of 4,800W).
- If more than one receptacle on the same circuit, you may allowed to use 15A outlet on 20A circuit breaker, otherwise, do not use 20A outlet on 15A circuit breaker. In short, It is code to use 15A outlet on 20A breaker (NEC 210.21(B)(2)), but it is not allowed to use 20A outlet on 15A breaker.
Resources:
Standard Breakers & GFCI Breakers Wiring Installations
- How to Wire a 1-Pole Breaker
- How to Wire a 2-Pole Breaker … You Are Here
- How to Wire a 3-Phase, 3-Pole Breaker
- How to Wire a Tandem Breaker
- How to Wire a 1-Pole GFCI
- How to Wire a 2-Pole GFCI
- How to Wire a 3-Phase, 3-Pole GFCI Breaker
- How to Wire GFCI Circuit Breakers
- How to Wire an AFCI Breaker
Sizing Breakers, Wires, and Panels
- How to Size a Circuit Breaker?
- How to Size a Breaker and Wires in AWG with EGC for Load?
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size a Branch Circuit Conductors with Protection?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- How to Size Motors FLC, HP, Voltage, Breaker Size and Wire Size
- What is the Correct Wire Size for 100A Breaker and Load?
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
General Outlets and GFCI/AFCI Receptacles Wiring
- How to Wire an Outlet Receptacle? Socket Outlet Wiring Diagrams
- How to wire a GFCI Outlet?
- How to Wire GFCI Combo Switch and Outlet
- How to Wire an AFCI Combo Switch
- How to Wire an AFCI Outlet?
- How to a Wire 3-Way Combination Switch and Grounded Outlet?
- How to Wire Combo Switch and Outlet? – Switch/Outlet Combo Wiring Diagrams
- How to Wire a 15A – 120V Outlet – NEMA 5-15 Receptacle
- How to Wire a 20A – 120V Outlet – NEMA 5-20 Receptacle
- How to Wire a 15A – 240V Outlet – NEMA 6-15 Receptacle
- How to Wire a 20A – 240V Outlet – NEMA 6-20 Receptacle
- How to Wire a 50A – 125/250V Outlet – NEMA 14-50 Receptacle
Switches Wiring
- How to Wire Single Pole, Single Throw (SPST) as 2-Way Switch?
- How to Wire Single Pole, Double Throw (SPDT) as 3-Way Switch?
- How to Wire Double Pole, Single Throw Switch? Wiring DPST
- How to Wire Double Pole, Double Throw Switch? Wiring DPDT
- How to Wire Double Switch? 2-Gang, 1-Way Switch – IEC & NEC
- How to Wire 4-Way Switch (NEC) or Intermediate Switch as 3-Way (IEC)?
- How to Wire Auto & Manual Changeover & Transfer Switch – (1 & 3 Phase)
Finding the Number of Breakers/Outlets in a Circuit
- How to Determine the Number of Circuit Breakers in a Panelboard?
- How to Find the Number of Outlets on a Single Circuit Breaker?
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- How to Calculate the Number of Fluorescent Lamps in a Final Sub Circuit?
- How to Calculate the Number of Incandescent Lamps in a Final Sub Circuit?
- How to Determine the Number of Lighting Branch Circuits?
- How to Determine the Number of Branch Circuits? – 3 Ways
- How to Find the Number of Lights on a Single Circuit Breaker?
Main Panels Wiring Tutorials
- How to Wire 120V/240V Main Panel? Breaker Box Installation
- How to Wire 208V/120V, 1-Phase & 3-Phase Main Panel?
- How to Wire 240V, 208V & 120V, 1 & 3-Phase, High Leg Delta Main Panel?
- How to Wire 277V/480V, 1-Phase & 3-Phase Main Service Panel?
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- Single Phase Electrical Wiring Installation in Home according to NEC & IEC
- Three Phase Electrical Wiring Installation in Home – NEC & IEC
- How To Wire a Single Phase kWh Meter – 120V/240V
- How to Wire a Three-Phase Meter? 120/208/240/277/347/480/600V
General Wiring Installation Tutorials:
- How to Toggle Electric Water Heater Between 120V and 240V?
- How to Wire 120V Water Heater Thermostat – Non-Simultaneous?
- How to Wire 240V Water Heater Thermostat – Non-Continuous?
- How to Wire 3-Phase Simultaneous Water Heater Thermostat?
- How to Wire Twin Timer for 120V/240V Circuits – ON/OFF Delay
- How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
- How to Wire Multifunction ON/OFF Delay Timer for 120V/240V Motors?
- Even More Residential Wiring Installation Tutorials
Related Posts:
- Difference Between 1-Pole and 2-Pole Breakers – NEC & IEC
- Should GFCI Protection Be in the Main Panel or Receptacle?
- Can you use 15A Breaker on 20A Circuit and Vice Versa?
- Can I Use a 1-Phase Breaker on a 3-Phase Supply & Vice Versa?
- Can I Use a 240V Breaker on a 120V Circuit and Vice Versa?
- Can You use a 15A Outlet on a 20A Circuit and Vice Versa?
- How Does a Standard Breaker Respond to Electrical Fault?
- Why Doesn’t a Standard Breaker Protract Against Ground Faults?
- How Do GFCI and Standard Breakers Respond to Ground Faults?







