Three Phase Electrical Wiring Installation in Home – NEC & IEC

How to Wire 3-Phase Electrical Distribution Board & Consumer Unit in Home

In our today electrical wiring installation tutorial, we will show how to wire and install a Three Phase distribution board and Consumer Unit from utility pole to a 3-Phase Energy Meter & 3-Phase Distribution board. We will also be showing that How to connect Three Phase & Single Phase Load circuits in a Three Phase Wiring Distribution System in home and commercial electric supply system.

Related Wiring Tutorials:

What is Three Phase & Single Phase Power?

In power generation plants, Three Phase power is generated by an electrical generator or alternator. In an alternator, the generated voltage and current by three independent coils in the stator are separated by 120 degrees from each other. The generated power from alternators then transmitted and distributed through transmission and distribution lines to the sub distribution. Both single phase and three phase supply is further distributed by the three single phase transformers or a single unit of three phase transformer (configured in Star “Y” or Delta Connection) installed on the utility pole near the residential or commercial area.

The voltage levels are step-up via step-up transformers for power transmission. In the distribution system, they are again step-down the level of voltage via step-down transformer for further utilization. RCD, MCB, MCCB, CB, RCD, RCBO, Fuses, Switches etc are used as controlling and protective devices in the MDB, DB, Sun & Final Sub circuits. For example,

In the UK and EU, 11kV from the step-down transformer wired in Delta connection via (3 Phase, 3-Wires System) enters the 400V/230V distribution transformer wired in Star “Y” Connection (Three Phase, 4 Wires System).

In the US, 4.5k-7.2kV from the step-down transformer wired in Delta connection via 3 Phase, 3-Wires System enters the 240V/120V distribution transformer wired in Star Connection (Two Phase, 3 Wires System). For a three phase system, the arrangement can be different for different levels of voltage. We will show the wiring diagram in the next sections of this post.

Related Wiring Tutorials:

As high power is needed in industrial and commercial buildings, they are connected to the three phase Delta connection (3 Phase – 3 Wire System – No Neutral Wire) before distribution transformer and then manage the required voltage and current according to the system requirements in three phase and single phase supply.

On the other hand, buildings that need low as well as high power in three phase and single phase are connected to the secondary of the distribution transformer. This way, they get a three phase Star connection (3-Phase, 4 Wire System with Neutral Wire). In the Star connection, Three Phase Line to Line (Phase to Phase) voltages are 400V AC (in US, 208V, 240V, 480V etc) and Single Phase Line to Neutral (Phase to Neutral), there are 230V AC (120V, 208V, 240V, 277V, 480V etc in the US).

In Three Phase Supply, motors and large electric heaters can be directly connected to the three Phases (Neutral is not needed in all cases) while in Single Phase, load circuits (light, fan etc.) can be connected in between Phase and Neutral through proper protective devices e.g. earthing/grounding wire. In the US, The 240V Single phase load can be connected to two phases without a Neutral wire.

Why Do We Need Three Phase Power Supply?

To operate high power equipment and appliances such as electric motors, high power rated air compressors & air-conditions, water heaters etc. we need Three Phase Power supply instead of Single Phase Power supply. In ordinary homes (domestic as residential), we mostly use Single Phase power supply to operate lighting load, fans, washing machines etc. But in some cases e.g. industries, high torque motors, multi-story & large buildings (industrial as commercial), Three Phase power supply needed to operate and maintain the high power and voltage systems.

In our previous posts about Single Phase electrical wiring installation in home and already know what MDB, DB, Final Sub Circuit, MCB, MCCB, CB and RCD etc. So we will never repeat it again.

Related Posts:

3-Phase & 1-Phase Voltage Levels in the US – NEC

In United States and Canada, different single phase and three phase voltage levels are available i.e. single phase voltage is available for domestic and residential applications while three phase voltage can be used for industrial and commercial applications.

Following are the Voltage levels available in the USA and Canada.

3-Phase Voltage in the USA

i.e.

1-Phase Voltage in the USA

i.e.

Note: In case of High Leg Delta (Power Leg or Wild Leg), additional of 208V single phase voltage are available between High Leg & Neutral as well as 120V, & 240V are available from the meter box to the load center and panel box.

Related Wiring Tutorials:

Three Phase and Single Phase Supply Voltage Systems “120V, 208V, 240V, 277V & 480V” – NEC – US

277V & 480V, Single Phase and Three Phase Supply Voltage Systems

High Leg Delta Configurations (120V, 208V & 240V)

What is High Leg Delta - 120V, 208V & 240V Configurations

3-Phase & 1-Phase Voltage Levels in the UK, EU – IEC

The three phase system is simpler in the UK & EU as compared to the USA and most of the countries (e.g. India, Pakistan, UAE and other Arab countries) follow the same voltage distribution system as UK, EU and IEC voltage levels. Both three phase and single phase voltage are available for residential and commercial application in the same unit as follows.

Operation of 11kV to 400V - 230V Distribution Transformer

3-Phase Voltage in the UK & EU

I.e.

1-Phase Voltage in the UK & EU

i.e.

230V & 400V Single Phase & Three Phase Power Supply Systems – IEC – UK & EU

230V & 400V Single Phase & Three Phase Power Supply Systems

Related Posts:

Requirements for Three Phase Wiring Installation

In this tutorial, we need the following wiring accessories to wire three phase power in home.

How to Wire Three Phase Main Distribution Board?

Generally, Electric supply and service providers install a single phase energy meter when load is less than 7.5kW (10HP) in domestic areas (consumer unit for home). If the limit is exceeded, then it’s recommended to install a 3-phase energy meter for consumer units. When load exceeds from 7.5 kW, then 3-phase electrical wiring is recommended in domestic areas (homes).

In this tutorial, We assume that we will only connect single phase load (Light points, fans, TV, Power Socket, AC etc.) in the current section of three phase electrical wiring installation. In other words, we will not power up 3 phase motors because in our homes, we don’t have that kind of (three phase) loads. If a three phase load exists in your home, then you can do so. As we can see that the total load is exceeded the limit of single phase electrical wiring installation as we will be feeding different rooms and areas in home, that’s why we have to wire our distribution in three phase system. For direct three phase loads, see the next sections in this post.

Practical Procedure of Three Phase wiring of distribution board & installation

We have learned the basic electrical wiring of bulb, fans etc (i.e. Sub-circuits and final sub circuits) in our previous posts, so follow the steps below to do the same as mentioned below.

 Click image to enlarge
Three Phase Electrical Wiring Installation Diagram
Fig  – Three Phase Electrical Wiring Installation Diagram

Good to Know: You may also use a Four Pole MCCB or MCB instead of Three Pole MCCB/MCCB. Simply connect the Neutral wire in the last slot of that MCCB (The letter N for Neutral is printed on the nameplate). Incoming and Outgoing Neutral wire like other phases should be connected to the copper strip (i.e. Earth-link or Neutral bar in the panel b box) as shown in fig.

In addition, If you need to connect a single phase load or need to wire a separate consumer unit or subservice panel, read the previous published posts on single phase wiring diagrams.

Related Posts:

Below are given the Three Phase Distribution Electrical Wiring Installation Diagram according to NEC & IEC.

Three Phase Electrical Wiring Installation Diagrams – US -NEC

Three Phase 208V Distribution and Panel Wiring.

Click image to enlarge

How to Wire 208V & 120V, 1-Phase & 3-Phase Main Panel Distribution Board Wiring

Three Phase 240V (High Leg Delta) Distribution and Panel Wiring.

Click image to enlarge

Main Panel Wiring for High Leg Delta 120V, 208V and 240V According to NEC

Three Phase 480V Distribution and Panel Wiring.

Click image to enlarge

How to Wire 277V & 480V, 1-Phase & 3-Phase, Commercial Main Service Panel

Good to know: it is against the code to use three separate single pole circuit breakers for 208V or 240V or 480V circuits. If you still want to connect three SP breakers as triple pole for three phase circuit, the switches of all the breakers should be bonded and connected together i.e. All the SP breakers should be switched ON & OFF with the same common switch. In addition, use the proper rated breaker, wire size, outlets, and switches etc. (check the bottom note (instruction & precaution) for calculators and tutorials about wire size, sizing outlets, switches and socket etc.

Related Posts:

Three Phase Electrical Wiring Installation Diagrams – UK, EU – IEC

Click image to enlarge

Three Phase Distribution Board Electrical Wiring Installation Diagram According to IEC Color Code
Fig – Three Phase Distribution Wiring According to IEC Color Code

Note: The same description and details can be used for both NEC and IEC wiring diagrams as mentioned for the above general fig 1.

Three Phase, 400V, Split Distribution Board Wiring with RCD – Only 3-Φ Loads

Click Image to enlarge

3-Φ Load in a Split Load Distribution Board

Three Phase, 400V, Split Distribution Board Wiring with RCD – 1-Φ Loads from 3-Φ Supply

Click image to enlarge

1-Φ Load in a Split Load Distribution Board

Three Phase, 400V, Split Distribution Board Wiring with RCD – Combo of 3-Φ & 1-Φ Loads

Click Image to enlarge

3-Phase & 1-Phase Split Distribution Board Wiring

Three Phase, 400V, Typical Distribution Board Wiring with RCD for 3-Φ Load Circuits

Click image to enlarge

How to Wire Three-Phase, 400V Distribution Board IEC - UK & EU

Three Phase, 400V, Typical Distribution Board Wiring with RCD for Both 3-Φ & 1-Φ Load Circuits

Click image to enlarge

How to Wire Combo of 3-Phase & Single-Phase, 400V-230V Distribution Board

Related Posts:

Good to Know: According to IET (Institution of Engineering and Technology) wiring regulations: 17th Edition (BS 7671:2008 – 1: 2011), an RCD protection must be provided in the consumer unit except smoke and burglar alarms system.

How to Connect Single Phase 120V Loads in a 1-Phase Wiring Distribution System? – NEC – US

Three phase load circuits can be directly connected to the three hot wires. Keep in mind that Neutral is not needed in all cases. The single phase load can be connected to hot and neutral (120V) or two hot wires (240V single phase). Below are the typical three phase panel wiring for US and Canada.

Wiring Installation of Three Phase, 208V Circuits & Breakers in Main Service Panel.

How to Wire 120V & 208V, 1-Phase & 3-Phase Load? NEC - USA

Wiring Installation of Three Phase 240V (High Leg Delta) Circuits & Breakers in Main Service Panel.

High Leg Delta Wiring - How to Wire 240V, 208V and 120V, 1-Phase & 3-Phase Load

Wiring Installation of Three Phase 480V Circuits & Breakers in Main Service Panel.

Wiring of 277V & 480V, 1-Phase & 3-Phase Main Breaker Box

Related Posts:

How to Connect Three Phase, 400V Loads in a 3-Phase Wiring Distribution System? – IEC & UK

As mentioned above, Three Phase loads (400V, 3-Phase Motors) can be directly connected to the three lines accordingly i.e. there is no need to connect to the neutral point (In some cases, Neutral is still needed in a three phase system which depends on the system design. Refer to the user manual before installing such an appliance). For Single Phase Loads (230V or 120V AC Light, TV, Power socket, Fans etc.), they can be connected to the Phase and Neutral wire as shown below. Note that Earth or ground wire must be connected to the electrical appliances and equipment connected to both single phase and three phase supply systems for safety as it prevents electric shock hazards.

How to Connect Single Phase & Three Phase Loads in a Three Phase Wiring Distribution System?
Fig 5 – Single Phase & Three Phase Load Connected in Three Phase Supply System

Wiring 3-Phase, 400V Load Points and MCB with RCD & RCCB in Distribution Board

Wiring 3-Phase, 400V Load Circuits in 3-Φ Distribution Board

Wiring Three Phase 400V load and MCB’s in the Split Load Distribution board and consumer unit with RCD.

Wiring 3-Φ, 400V & 1-Φ 230V Load Circuits in Split Load Distribution Board

Wiring Typical Three Phase 400V load circuits and MCB in the Distribution board and consumer unit.

Wiring 400V, 3-Φ & 230V, 1-Φ Load Circuits in Distribution Board

Related Posts:

Schematic Wiring Diagram of Three Phase Distribution Board

The following typical layout wiring diagram shows three phase distribution board and consumer unit installation in a residential/commercial area.

Electrical Wiring Diagram of Three Phase & Single Phase Consumer Unit with RCD
Fig 2 – Electrical Wiring Diagram of Three Phase & Single Phase Consumer Unit with RCD

Three Phase Wiring Color Codes – IEC and NEC

We have used Red for Phase, Live or Hot, Black for Neutral and Green for Earth/Ground Wire in the typical single phase wiring diagram. You may use the specific region or general practiced codes in the local area i.e. IEC – International Electrotechnical Commission (UK, EU etc.) or NEC (National Electrical Code [US & Canada] see the detailed post about NEC & IEC wiring Color Codes where;

NEC – USA:

Three Phase 208V & 240V AC (High Leg Delta):

Three Phase 277V & 480V AC:

Single Phase 120V AC:

Single Phase 240V AC:

Related Posts:

IEC & UK:

Three Phase 400V:

Single Phase 230V AC:

For reference, here is the OLD UK Wiring Color Codes (Prior 2004) which still applicable in other countries i.e. India, Pakistan, UAE, KSA and other Arab Countries.

400V Three Phase

230V Single Phase

Related Posts:

General Precautions & Instructions

Related Electrical Wiring Installation Tutorials.

↑
Exit mobile version