How to Wire 277/480V, 1-Phase & 3-Phase Main Service Panel?
Wiring a 480V/277V, Single & Three Phase Main Breaker Box for Commercial Applications
What is 277 & 480V Commercial Supply?
277V is a standard single phase voltage derived from 480V three phase voltage system available in commercial applications. It can be achieved by three transformers connected in Wye (Star – connection) having a neutral point. The transformer’s secondary provides 277V single phase and 480V single phase and three phase voltage levels. Generally, 277V is not available in typical homes for residential purposes.
For 480V & 277V three phase supply, the electric power providers install three transformers in Wye-Wye configuration. The primary side of the transformer (configured in Wye) is connected to the 7.2 kV distribution lines. The output voltage levels of the transformer (from the secondary side wires in Wye) are 277V, 1-Phase and 480V, 1-Phase & 3-Phase. The three different levels of voltages are then used in the commercial buildings and industrial installations as per requirements of the consumer.
In this kind of power distribution system, the following three types of levels of voltage are available as three phase, four wires (three hot wires + neutral).
- 277V Single Phase, 3 Wires (One Hot wire + Neutral wire + Ground wire)
- 480V Single Phase, 3 Wires (Two out of phase Hot wires + Ground wire)
- 480V Three Phase, 4-5 Wires (Three out of phase Hot wires + Neutral wire + Ground wire)
480V can be achieved by high leg delta, four wires + neutral wire which provides 480V-415V-240V or open-delta configuration. Additionally, it can also be achieved by three wires without neutral as 480V-480V-480V. Another setup to provide 480V to the end user is four wires + neutral in wye configuration which provides 480V-480V-480V and 277V. For more details, you may read about the differences between Wye and Delta connections.
277V can also be achieved by using on site buck-boost transformer with other types of voltages such as installing an on-site (buck boost) transformer with 240V delta and 480V delta, in standard voltage system i.e. 277V can only be achieved without additional transformers in 480V-480V-480V and 277V (Wye connection). In this kind of system having both windings of T/F in Wye configuration, we will get the following 3-types of voltage levels based on the related math calculation.
- Voltage between two hot Phases = 480V (1-Φ).
- Voltage between Phase and Neutral = 480V / √3 = 277V (1-Φ).
- Voltage between three Phases = 277V x √3 = 480V (3-Φ).
For this kind of service, the three phase supply including single phase supply from the secondary of the distribution transformer through insulated wires enters the meter box and safety switch and lastly enters to the main panel box. Each hot or line wire connects to a separate busbar in the panel box for further power distribution.
The color codes for three hot wires are Yellow, Orange and Blue for Hot1, Hot2 and Hot3, White or gray for neutral and green for ground.
Three poles, two poles and single pole circuit breakers are used to snap (i.e. in the metal tracks to hold the CB’s tightly) over three busbars which draws HOT from each busbar. There are additional two busbars for Neutral and Ground respectively. The ground wire is connected to the ground rod (see the full setup of earthing and grounding) for safety purposes.
In 277V and 480V, 1-Phase & 3-Phase, wiring systems, the available voltage levels are as follows inside the main service panel.
- Voltage between three hot wires (hot 1, hot 2 & hot 3) = 480V, 3-Phase
- Voltage between any two hot wires = 480V, 1-Phase
- Voltage between any hot wire and Neutral = 277V, 1-Phase
Click image or open in a new tab to enlarge
Let’s see how to wire 480V and 277V, single phase and three phase breakers and load circuits in the breaker box as follows.
How to Wire 277V, 1-Phase Circuits & Breakers?
The following tutorial shows how to wire a 277V single phase breaker derived from 480V three phase supply for commercial uses.
A 277V single phase can be achieved between any hot wire (either H1, H2 or H3) and Neutral. For example, in the fig below, we have connected a 277V troffer to a single pole MCB breaker as most troffers for lighting operate on 120V-277V. The single pole breaker is connected to hot2 wire, neutral and ground wire.
Other NEMA outlets which can be wired to the 277V single phase supply using 1-pole breakers are as follow:
- NEMA 7-15, 7-20, 7-30, 7-50, 7-60 and L7 series – (2P, 3W – Grounding with Neutral)
All of them are 2-pole, 3-wires and rated for 277V i.e., they need three wires e.g. a hot from the breaker, a ground + neutral.
How to Wire 480V, 1-Phase Circuits & Breakers?
In the same panel having 480V three phase and single phase, we may connect and install single phase 480V load circuits. To do so, simply connect the appliance (highway lighting circuit for example) via two poles breaker connected to any two hot wires (such as Hot1 and Hot 3) and ground wire. Connect the additional neutral wire if needed as per the circuit requirements.
Such NEMA outlets are:
- NEMA L8-20R, L8-30R, L8-50, L8-60 – (2P, 3W – Grounding – No Neutral)
These outlets are 2-pole, 3-wire and rated for 480V and need three wires connection i.e. they can be connected without neutral e.g. two hot wires plus ground wire. Same is the case for single phase 277-480V surge found in water heaters, motors and parking lots for lighting circuits.
How to Wire 480V, 3-Phase Circuits & Breakers?
For 480V, three phase circuits, we need four or five wires (three as out of phase hot i.e. all different lines). As shown in the following fig, we have two appliances e.g. three phase motor and L22-30R outlet. You can see that we have connected all the three hot wires in both cases. Additionally, we have connected neutral and gerund wires as well as per the circuit requirement. The same applies for 20 Amps outlets such as L22-20R.
You don’t always need the neutral wire in all cases for 480V three phase circuits as it depends on the rating and design of the appliances. For example following are different 480V three phase rated NEMA outlets and receptacles such as 2P, 3W, 3P-4W, 4P, 4W and 4P-5W – grounding and non-grounding.
- NEMA L12-20, L12-30 (3-pole, 3 wire) non-grounding – No neutral
- NEMA L16-20, L16-30, L16-50, L16-60 (3-pole, 4 wire) grounding – No neutral
- NEMA L19-20, L19-30 (4-pole, 4 wire) non – grounding with neutral
- NEMA L22-20, L22-30, L22-50 , L22-60 (4-pole, 5 wire) grounding with neutral
Click image or open in a new tab to enlarge
Wiring Color Codes for 480 & 277V:
For 277V & 480V service, we have used different wire colors for illustration purposes only. Please follow the National Electric Codes i.e. NEC wiring color codes or other local area color codes.
In this tutorial, 277V and 480V, 1-phase and 3-phase circuits, we have used the NEC + general practice wiring color codes as follows.
- Brown = Hot 1 or Line 1
- Orange = Hot 2 or Line 2
- Yellow = Hot 3 or Line 3
- White = Neutral Wire
- Green or Green with Yellow stripes = Bare Conductor as Ground wire
Keep in mind that green, green/yellow, or bare conductors must never be used for any wire that carries voltage. These colors are reserved exclusively for equipment grounding conductors. Always use copper conductors for main panel wiring to minimize resistance and heat buildup; avoid using aluminum wires unless specifically permitted and properly rated. Additionally, the terms Hot, Phase, and Line all refer to the same thing i.e. conductors that carry live voltage.
Instructions & Precautions
- Always disconnect the power source (and confirm it is completely switched OFF) before servicing, repairing, or installing any electrical equipment. Turn off the main switch in the main panel before beginning any work.
- Follow all applicable CEC and NEC requirements for main panels, load centers, and electrical installations.
- Never stand on or touch wet surfaces or metallic parts while working on live electrical circuits.
- Read all cautions and instructions carefully, and follow them strictly when performing this tutorial or any practical electrical work.
- Always use properly sized service-entrance cables, feeder conductors, and branch-circuit conductors for service disconnects, main panels/load centers, and branch circuits.
- Use correctly sized Equipment Grounding Conductors (EGC) and Grounding Electrode Conductors (GEC) for the main panel and all load points.
- Use the correct wire and cable size (based on NEC Table 310.16 or CEC Table (1-4), as well as appropriate outlets, switches, and properly sized circuit breakers. A wire and cable size calculator may also be used to determine the proper gauge and associated ampacities.
Resources:
Related Main Panels Wiring Tutorials
- How to Wire 120/240V Main Panel – Breaker Box Installation
- How to Wire 120V/208V, 1-Phase & 3-Phase Main Panel?
- How to Wire 120/208/240V High Leg Delta Main Panel?
- How to Wire 277/480V, 1-Phase & 3-Phase Main Service Panel … You are Here
- How to Wire 347/600V, 1 and 3-Phase Main Service Panel?
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- Single Phase Electrical Wiring Installation in Home according to NEC & IEC
- Three Phase Electrical Wiring Installation in Home – NEC & IEC
- How To Wire a Single Phase kWh Meter – 120V/240V
- How to Wire a Three-Phase Meter? 120/208/240/277/347/480/600V
Sizing Breakers, Wires, and Panels
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- How to Size a Circuit Breaker?
- How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems
- How to Size a Breaker and Wires in AWG with EGC for Load?
- How to Size Service-Entrance Conductors and Feeder Cables?
- How to Size Feeder Conductors with Overcurrent Protection
- How to Size a Branch Circuit Conductors with Protection?
- How to Size Equipment Grounding Conductor (EGC)?
- How to Size Grounding Electrode Conductor (GEC)?
- How to Size Motors FLC, HP, Voltage, Breaker Size and Wire Size
- What is the Correct Wire Size for 100A Breaker and Load?
- What is the Right Wire Size for 15A Breaker and Outlet?
- What is the Suitable Wire Size for 20A Breaker and Outlet?
Standard Breakers & GFCI Breakers Wiring Installations
- How to Wire 1-Pole Breaker
- How to Wire 2-Pole Breaker
- How to Wire 3-Pole Breaker
- How to Wire Tandem Breaker
- How to Wire a GFCI Circuit Breaker?
- How to Wire an AFCI Breaker?
General Outlets and GFCI/AFCI Receptacles Wiring
- How to Wire an Outlet Receptacle? Socket Outlet Wiring Diagrams
- How to wire a GFCI Outlet?
- How to Wire GFCI Combo Switch and Outlet
- How to Wire an AFCI Combo Switch
- How to Wire an AFCI Outlet?
- How to a Wire 3-Way Combination Switch and Grounded Outlet?
- How to Wire Combo Switch and Outlet? – Switch/Outlet Combo Wiring Diagrams
- How to Wire a 15A – 120V Outlet – NEMA 5-15 Receptacle
- How to Wire a 20A – 120V Outlet – NEMA 5-20 Receptacle
- How to Wire a 15A – 240V Outlet – NEMA 6-15 Receptacle
- How to Wire a 20A – 240V Outlet – NEMA 6-20 Receptacle
- How to Wire a 50A – 125/250V Outlet – NEMA 14-50 Receptacle
Switches Wiring
- How to Wire Single Pole, Single Throw (SPST) as 2-Way Switch?
- How to Wire Single Pole, Double Throw (SPDT) as 3-Way Switch?
- How to Wire Double Pole, Single Throw Switch? Wiring DPST
- How to Wire Double Pole, Double Throw Switch? Wiring DPDT
- How to Wire Double Switch? 2-Gang, 1-Way Switch – IEC & NEC
- How to Wire 4-Way Switch (NEC) or Intermediate Switch as 3-Way (IEC)?
- How to Wire Auto & Manual Changeover & Transfer Switch – (1 & 3 Phase)
Finding the Number of Breakers/Outlets in a Circuit
- How to Determine the Number of Circuit Breakers in a Panelboard?
- How to Find the Number of Outlets on a Single Circuit Breaker?
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- How to Calculate the Number of Fluorescent Lamps in a Final Sub Circuit?
- How to Calculate the Number of Incandescent Lamps in a Final Sub Circuit?
- How to Determine the Number of Lighting Branch Circuits?
- How to Determine the Number of Branch Circuits? – 3 Ways
- How to Find the Number of Lights on a Single Circuit Breaker?
General Wiring Installation Tutorials:
- How to Toggle Electric Water Heater Between 120V and 240V?
- How to Wire 120V Water Heater Thermostat – Non-Simultaneous?
- How to Wire 240V Water Heater Thermostat – Non-Continuous?
- How to Wire 3-Phase Simultaneous Water Heater Thermostat?
- How to Wire Twin Timer for 120V/240V Circuits – ON/OFF Delay
- How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
- How to Wire Multifunction ON/OFF Delay Timer for 120V/240V Motors?
- Even More Residential Wiring Installation Tutorials