How to Connect a Portable Generator to the Home Supply – 4 Methods
How to Wire a 1-P & 3-P Portable Generator to the Home Supply using Changeover & Without Changeover or Transfer Switch (ATS & MTS) for 230V/400V & 120V/240V
We all suffer from power failure in emergency breakdown (i.e. short circuit, overload, damage to electric transmission lines, substations or other parts of the distribution system as well as storms and other bad weather conditions etc.). In this case, emergency and portable generator can be used to restore the electric power to the home supply and other connected appliances.
In this step by step tutorial, we will be showing the portable generator wiring and connection diagram to the home supply and main distribution board according to NEC and IEC. We will be using Automatic Changeover Switch also known as Automatic Transfer Switch (ATS), Manual Changeover Switch (MTS or Manual Transfer Switch) to connect the generator to a house for 230V and 400V (IEC) and 120V and 240V (NEC). In addition, We will show how to wire a portable generator to home supply without a changeover switch or transfer switches.
By using the following basic electrical wiring installation diagrams for generator connection, you may restore an emergency electric supply in case of power outage by connecting a portable generator (Gas/Petrol/Diesel Generator) to the main distribution board.
Related Posts:
- How to Size a Generator? Portable, Backup & Standby for Home & Commercial Applications
- How to Wire Auto & Manual Changeover & Transfer Switch – (1 & 3 Phase)
So now let’s begin.
We can connect a portable generator to our home supply system by four methods.
Each method with wiring connection and working and operation has been explained in step by step tutorial. (Please read all cautions / warnings, user manual and care must be taken before installing a generator to the home electric power supply system. If you are not sure, contact a licensed electrician to do it properly).
Electricity is our friend as well as the worst enemy, if you give it a chance to kill you, Remember, they will never miss it. Please read all caution and instruction while doing this practical tutorial.
How to Hook Up a Portable Generator to the Home Supply using Manual Changeover & Transfer Switch for 120V, 240V & 230V – NEC & NIEC
Connecting a portable emergency generator to the home power supply system using manual or automatic changeover switches (Auto transfer Switch (ATS) is the safest and recommended method) for 230V (UK & EU – IEC) and 120V/240V (Canada, US – NEC).
Wiring an Emergency Generator Using Manual Changeover Switch 230V – IEC
Steps for Wiring & Installation of a Generator using Manual Changeover Switch
To connect a portable generator to the home electric supply system by manual changeover switch, follow the steps below:
- Install a changeover switch (rated for 63-100A depending on the load) near the main distribution board in the home.
- Connect the main power supply (Line and Neutral) as incoming to the first upper slots of changeover Switch as shown in fig.
- Connect a 6 AWG (7/064″ or 16mm2)” cable wire to the lower two slots of the changeover switch.
- Now connect a 3-pin power socket (for small load) or 32A, 240V power socket – male (for large load) to the 6AVG wire and install onto the wall (near to the generator) and put the generator 3-pin power plug or or 32A, 240V power socket (female) into the power socket which you have installed before.
- You have done and are ready to supply emergency electric power to the home appliances in case of an emergency power blackout.
Related Posts:
- Single Phase Electrical Wiring Installation in Home – NEC & IEC
- Three Phase Electrical Wiring Installation in Home – NEC & IEC
Below is the generator wiring connection diagram to the main distribution board using the manual changeover switch where all the load circuits are connected to the generator supply in case of a power outage. If you don’t need to power up the specific load circuits, you may switch-OFF the related breakers and the rest breakers remain switch-ON. This way, only specific load points can be fed-up through emergency power via generator.
Click image to enlarge
If you want to connect specific load to the generator when utility power goes off i.e. some load on generator and the rest on main power supply as there may be a case where generator may not be able to handle the overall load. You may just switch-off those load points or related circuit breakers to it.
Related Posts:
- How to Wire Single-Phase, 230V Consumer Unit with RCD? IEC, UK & EU
- How to Wire a Garage Consumer Unit?
Wiring a Portable Generator Using Manual Transfer Switch for 120 & 240V- NEC
The following wiring diagram shows a portable generator is wired to the 120V/240V main panel using manual transfer switch. Generally, you may connect a 30 amp transfer switch (like Protran or Reliance) for up to 7500 watts generator while other sizes (such as 50 amps) are also available for residential applications.
In this transfer switch, the single pole breaker is 15 amp while the double pole breaker is 30 amp having the max size of 12 gauge wire size.
To do this, just install a 30 amp (or 20 amp depending on the system requirement such as L14-30R, L14-20P) the twist lock plug for extension cord which plug into the generator.
The making of L14-30R, L14-20P plug and outlet indicates the following terminals:
- X = Hot 1 (Black)
- Y = Hot 2 (Red)
- G = Ground
- W = Neutral
Now, to wire the generator and main panel to the transfer switch, Remove the load wires from the related breakers and connect those wires to the corresponding wires from the transfer switch. Now connect the Black A and Red A from the transfer switch to the 2P breaker. Do the same for the SP breaker as shown in below wiring diagram (or according to the user manual). If not sure, contact a licensed electrician.
Click image to enlarge
Related Posts:
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire 208V & 120V, 1-Phase & 3-Phase Main Panel?
When Utility Power is not available, and Generator is ON
The breaker’s switch in the transfer switch pushes one direction and power is connected to the load appliances through Generator → Breaker in the transfer switch → to load points.
The direction of flow of power is followed through wires to the different circuits.
- 120V = Black C1 (to transfer switch) and Black C (from transfer switch) to the load and Neutral wire.
- 240V = Black A & Red A (to transfer switch) and Black B & Red B ( from transfer switch) to the load.
When Utility Power is available, and Generator is OFF
The breaker’s switch in the transfer switch pushes the other direction and power is connected to the load appliances through the main panel → Breaker in the transfer switch → to 120V and 240 load points.
The transfer switch won’t let go the power to energize the generator or power company wires e.g. it turns off the power supply that could come from the breaker in the panel. Keep in mind that only those breakers and load points will work which are connected according to the above (illustrated purpose) wiring diagram.
Related Posts:
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Number of Circuit Breakers in a Panel Board?
Wiring a Generator Using Manual Transfer Switch for 240V – NEC
The following wiring diagram shows a generator connected to the 120V/240V main panel and 240V load circuits in separate subpanels using a manual transfer switch. These kind of transfer switches (like 2P, GE TC10323R / GE TC35322 / TC10424R or 3P, GE TC35362R emergency power transfer switches and safety switches or disconnectors) are used to connect the generator for power transfer operation or any other appliance for service disconnection as safety switch.
Click image to enlarge
As shown, the generator is connected to the transfer switch through L14-30 (or L14-20) plug and power inlet. The two hot wires (Hot 1 and Hot 2) from the generator are connected to the lower main lugs in the transfer switch.
The upper two hot lugs of the transfer switch are wired to the 60A double pole breaker in the main panel. The center lugs of the transfer switch as load is connected to the 60A subpanel which is designed for 240V load circuits only. As it is a 240V load subpanel, so there is no need for a Neutral wire. Neutral is only required in case of 120V circuits or GFCI/AFCI protected circuits.
The lever operation of the transfer switch is follow:
- UP = Main Supply = ON
- Middle = OFF
- Down = Generator Supply = ON
When the generator is OFF, the lever is on Down position, so the 240V load points are connected to the generator supply, When main supply is available, the lever position is changed to the Up position (manual operation) and the load circuits are fed-up through utility power.
Related Posts:
- How to Wire 240V, 208V & 120V, 1 & 3-Phase, High Leg Delta Main Panel?
- How to Wire 277V & 480V, 1-Phase & 3-Phase, Commercial Main Service Panel?
How to Connect a 1-Phase, 230V Generator to a Home using Automatic Changeover Switch – IEC?
In this way, We have to use a two pole (2P) automatic changeover switch to connect the generator to a home. The connection method is the same as mentioned above for method 1, but we have to use single phase 2 pole automatic changeover instead of manual transfer switch. No hesitation in this way i.e. when the power restores from the utility, the auto transfer switch automatically detects the power and redirects from the generator supply to the main supply and vice versa.
Note: You may use Three Poles (3P) Changeover instead of 2 Poles as well.
Click image to enlarge
Related Posts:
- How to Wire 230V Dual Split Load Consumer Unit? – RCD+MCB
- How to Wire 1-Phase Split Load Consumer Unit? – RCD+RCBO
How to Connect a Portable Generator to a Home without Changeover / Transfer Switch – NEC & IEC
Wiring a Portable Generator without Transfer Switch using Interlock Kit for 120V & 240V – NEC
If you’re looking for a more affordable alternative to a transfer switch for connecting a generator to your home panel, an interlock kit is a practical solution. While you can manually switch off the main breaker and run the generator to power 120V and 240V circuits, it is still safer and highly recommended to use an interlock kit. The interlock kit ensures that the main breaker and the generator breaker cannot be turned on at the same time, preventing backfeeding and enhancing overall safety.
The following wiring diagram shows how to wire an interlock kit for the generator and its operation during the power failure. The interlock kit is installed in the main panel which prevents both (the main and generator breakers at once). Only one breaker (either main or generator) can be ON or OFF at a time by sliding up or down the interlock.
As the generator is wired to the main panel through L14-30 (or L14-20) plug and power inlet and interlock kit in the main panel, let’s see the working operation.
When Utility Power is OFF = Generator is ON
When the main power supply is unavailable, first switch OFF the main breaker and slide the interlock kit up (this locks the main breaker in the OFF position, as shown in the figure). This allows you to start the generator and then switch ON the two-pole (2P) breaker connected to the generator. Once the generator is running and the 2P breaker is ON, you can begin turning ON the 120V and 240V breakers one by one to supply power to the desired load circuits. The red arrow from the generator and power inlet to the 2P breaker and main panel indicates the direction of power flow to the load points.
Related Post:
- How to Determine the Right Size Capacity of a Subpanel?
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
Click image to enlarge
When Utility Power in ON = Generator is OFF
When the utility power is restored, just shut down the generator and switch OFF its related two-pole breaker. Now slide-down the interlock kit (it will prevent switching ON the breaker for generator) which will allow switching ON the main breaker. Just switch ON the main breaker and the supply will restore via main power to the connected load points. The red arrow from the main supply cables shows the power flow to the circuit.
Click image to enlarge
Related Posts:
- How to Wire Combo Switch and Outlet?
- How to Wire GFCI Combo Switch and Outlet
- How to Wire an AFCI Combo Switch
Wiring an Emergency Generator without Changeover Switch for 230V – IEC
Caution: Please follow the local area codes as this method may be not according to the codes in case of IEC following countries. This may lead to serious injuries and hazardous fire as it may be done with special attention as there are chances someone forget to OFF the desired breaker before the operation. In short, it can be done with special care if allowed by the code.
The Installation process and operation is the same as mentioned above but without the Changeover Switch. For this method, switch off both the main switch (MCB) in the distribution board to disconnect the power supply. Now install a separate 63 Amp breaker for the generator (same as main MCB).
Now, connect this new breaker via power inlet (3 Pin power socket or 32A, 230V male power socket) using 6 AWG (7/064″ or 16mm2)”. Finally, connect the 3 pin power plug or 32A, 230V female power plug of the generator in that power inlet or power socket (As shown in below fig). You have done it!
Related Posts:
Click image to enlarge
Operation and Working
1. In case when utility power supply is not available:
To do this, first of all switch OFF the main breaker and start the generator. Now switch ON the breaker for the generator and switch ON those breakers one by one which connected to the desired load and needed to be operated via emergency power supply from the generator.
When the generator is not in use, FIRST switch OFF the breaker for the generator, switch OFF the generator and then finally, switch ON the main breaker in the distribution board or consumer unit.
In this case, the generator supplies electricity to the home appliances and power flow will continue to those connected electrical appliances and devices through (the Red Line i.e. wires covered in the Red rectangle box) by generator (as shown in below image).
The Red Line in the Red rectangle box) and arrows (↑) shows the power flow in the circuit.
In this case, the first MCB (Main Switch which is connected to the main power supply) would be “OFF” and the second MCB switch wired for generator) should be “ON”. For extra safety purpose, switch off the 3-pin power socket or 32A generator socket and outlet by switching OFF the built-in ON/OFF button switch when generator is not in used.
Click image to enlarge
Related Posts:
- A Complete Guide About Solar Panel Installation. Step by Step Procedure with Calculation & Diagrams
- How to Wire Batteries in Series, Parallel and Series-Parallel?
- Series, Parallel and Series-Parallel Connection of Solar Panels
2. In case when power supply restores from power house:
In this case, the main electric lines supply electricity to the home appliances and power flow will continue to those connected electrical appliances in the system through the (the Red Line i.e. wires covered in the Red rectangle box) by main power supply from the power house. Thus, the portable generator remains standby.
Keep in mind that the breaker for the generator will be at OFF position. Never ever switch ON this breaker when main supply is available. For extra safety, switch OFF the power socket by bulletin ON/OFF button or remove the 3-Pin plug for the generator.
Click image to enlarge
Related Posts:
In this case, the second MCB switch wired for the generator should be “OFF”. For extra safety purposes, switch off the 3-pin power socket or 230V, 32A power outlet and socket by switching OFF the built-in ON/OFF button when the generator is not in use. In addition, shut down the generator and remove the power plug. Now Switch ON the main MCB (Main Switch which is connected to the main power supply).
Please read all the given notes, warnings, instructions, manuals and cautions before implementing this method as it may not be legal in some countries due to safety and hazard. Also, It is not recommended for beginners and only a possible way for practical engineers and experienced technicians in case of a very emergency (i.e. power supply failure in hospitals during serious operations) and there is no alternative to restore the power supply. Only 1 MCB should be “ON” at a time. If the second MCB is “ON” in the above shown figures and operation, i.e. both MSB’s switch “ON” at the same time. Then;
Related Posts:
- How to Wire and Install an Electrical Outlet Receptacle?
- How to wire a GFCI Outlet?
- How to Wire an AFCI Outlet?
How to Connect a 3-Phase Generator to Home with 4 Pole Automatic Changeover Switch?
To connect a three phase portable generator to the home supply, We have to use a four pole (4P) automatic changeover or transfer switch. The connection method is the same as mentioned above for single phase generator and changeover switch, but we have to use three phase 4 poles manual changeover switch. It is the most reliable and recommended way to connect a generator to the home supply because when the power restores from the utility, the automatic transfer switch automatically detects the power and redirects from the generator supply to the main supply and vice versa.
Note: You may use Three Poles (3P) Auto changeover switch instead if Four Poles (4P) changeover or transfer switch.
Click image to enlarge
How to Connect a 3-Phase Generator to Home with 4 Pole Manual Changeover Switch?
There is no big difference in wiring connections for automatic and manual changeover and transfer switches with portable generators. In the following wiring connection, we have used a four pole manual changeover switch to connect a three phase emergency generator to the distribution boards. The wiring connections for three phase transfer switch are same as wiring for single phase 2 pole changeover switch in method one, while there are another two slots for additional line and neutral as shown in fig below.
Note: You may use Three Poles (3P) Manual changeover switch instead if Four Poles (4P) changeover or transfer switch.
Click image to enlarge
Related Posts:
- How to Wire 1-Phase & 3-Phase Split Load Distribution Board?
- How to Wire Combo of 3 & 1-Φ, 400V/230V Distribution Board?
Wiring Color Code:
We have used the IEC and IEC wiring color codes for 230V/400V and 120V/240V circuits. You may use the local area codes or i IEC – International Electrotechnical Commission (UK, EU etc.) or NEC (National Electrical Code [US & Canada] where;
NEC:
Single Phase 120V AC:
- Black = Hot or Line
- White = Neutral
- Green / Yellow or bare conductor = Ground Wire
Single Phase 240V AC:
- Black = Hot 1 or Line 1
- Red = Hot 2 or Line 2
- White = Neutral
- Green / Yellow or bare conductor = Ground Wire
Three Phase 208 AC:
- Black = Hot 1 or Line 1
- Red = Hot 2 or Line 2
- Blue = Hot 3 or Line 3
- White or Gray = Neutral
- Green / Yellow or bare conductor = Ground Wire
Three Phase 240 AC (High Leg Delta):
- Blue = Hot 1 or Line 1
- Orange = Hot 2 or Line 2 (HIGH LEG DELTA)
- Black = Hot 3 or Line 3
- White or Gray = Neutral
- Green / Yellow or bare conductor = Ground Wire
Three Phase 480V & 600V AC
- Brown = Hot 1 or Line 1
- Orange = Hot 2 or Line 2
- Yellow = Hot 3 or Line 3
- White or Gray = Neutral
- Green / Yellow or bare conductor = Ground Wire
IEC:
Single Phase 230V AC:
- Brown = Phase or Line
- Blue = Neutral
- Green / Yellow = Earth Conductor = Earth Conductor
Three Phase 400V – 415V AC:
- Brown = Phase 1 or Line 1
- Black = Phase 2 or Line 2
- Grey = Phase 3 or Line 3
- Blue = Neutral
- Green / Yellow = Earth Conductor
Related Posts:
General Precaution
Related Electrical Wiring Installation Tutorials.
- How to Wire a Single Element Water Heater and Thermostat?
- How to Wire 120V Water Heater Thermostat – Non-Simultaneous?
- How to Wire 120V Simultaneous Water Heater Thermostat?
- How to Wire 240V Water Heater Thermostat – Non-Continuous?
- How to Wire 240V Simultaneous Water Heater Thermostat?
- How to Wire 3-Phase Simultaneous Water Heater Thermostat?
- How to Wire 3-Phase Non-Simultaneous Water Heater Thermostat?
- How to Toggle Electric Water Heater Between 120V and 240V?
- Staircase Wiring Circuit Diagram – How to Control a Lamp from 2 Places?
- Corridor Wiring Circuit Diagram – Hallway Wiring using 2-Way Switches
- Tunnel Wiring Circuit Diagram for Light Control using Switches
- Hospital Wiring Circuit for Light Control using Switches
- Hotel Wiring Circuit – Bell Indicator Circuit for Hotelling
- Hostel Wiring Circuit Diagram and Working
- Godown Wiring Diagram – Tunnel Wiring Circuit and Working
- Automatic UPS system wiring circuit diagram for Home or Office
- Manual UPS Wiring Diagram With Change Over Switch System.
- How to Wire 4-Way Switch (NEC) or Intermediate Switch as 3-Way (IEC)?
- How to Wire Single Pole, Single Throw (SPST) as 2-Way Switch?
- How to Wire Single Pole, Double Throw (SPDT) as 3-Way Switch?
- How to Wire Double Pole, Single Throw Switch? Wiring DPST
- How to Wire Double Pole, Double Throw Switch? Wiring DPDT
- How to Wire Double Switch? 2-Gang, 1-Way Switch – IEC & NEC
- How to a Wire 3-Way Combination Switch and Grounded Outlet?
- How to a Wire Double 3-Way Combination Switch Device?
- Even More Residential Wiring Installation Tutorials



















nice post sharing information related to electric supply
The only one that's legal is the one with a change over switch. All others are illegal in the U.S. by OSHA
Read the Description as will as cautions. Thanks
The second method which uses change over switch is safer than methods 1 and 3. Thank you<br />for the information.
Thanks for sharing useful information.
A.O.A.
Q1.Why inductors are not fabricated in the IC?
Q2.P=VI=V^2/R=I^2R
On what occasion,these formulas are used?
This is so good , thank
All of these diagrams are dangerous and illegal and shouldn’t be published here. No one should ever connect a generator to the house in these ways. The only way is to use a changeover switch so that the mains is isolated whilst the generator is in use and visa versa. In other words, the switchboard is connected to the common side of the changeover switch and the mains connected to the input 1 and the generator to the input 2.
i totally agree with Alan the way to go is either a auto change over or a mechanical change over either way it is no possible to have both supplies on at once
alan u are 100% correct
please sir how can one make interswich connection between solar, generator and grid supply for residential use
The switching is legally and safely installed by a licensed electrician who has the proper municipal work permits .
Not some con job installed by Mr Handy Man trying to be cheap .
Method 2 is almost right but there should be no wiring or connections to the top MCB’s.
The mains power should come into the top of the changeover switch only and no wiring to anywhere else.
Basicly you are interupting the mains power to the MCB’s by the changeover switch, when you switch it over, the power will flow from the generator to the MCB’s. Only one set of MCB’s is needed.
In Australia, if you published or told a non qualified person how to wire up electrical equipment like this, you could be prosecuted if they were injured. Please remove all other methods, there is only one method, the manual or automatic changeover swith.
I use 2 high power relays switching both L and N and have it so they are wired to automatically switch power source. This is wired with delay timers in the circuit to ensure clear separation of power supply when changing over and prevent accidentally making the Mains line live. You don’t want to kill the electrician working down line trying to fix the reason for the power cut in the first place. If you are going to have it manually switched you need to consider making it physically impossible to have both on.
Tim, you don’t need a delay you need to electrically interlock each relay coil with each other so only one can energise as well as mechanicaly interlocking them so it is impossible to energise both.
They do fail and I have worked on cranes with forward reverse contactors for years (relays) they do stick and jam on sometimes. Mechanical interlocks prevent this happening. The better way is to get a changeover contactor which is energised with the mains on with 2 normaly open contact and 2 normaly closed contacts. When the power fails, it drops out and the auxillary input is connected.
thank you brother you are giving very best information about electricity.
Bhai Generator relay lagany ka tricka
bata day plzzz
Hi,
Thank you very much for the information, By the way I have a question regarding the portable generators that I always power up my store unfortunately some times I found that when I switch on many things my generator sims to sound loudly and suddenly Shut down and offline. Please can you help me to rectify the fault.
In my Case, (When I face this problem) I check the generator oil (engine lubricant) if they need to change, Check the spark plug if they need to clean/replace, Check the load (especially overload), make sure the gas/oil as input is connected and sufficient to run the generator. Finally contact the generator mechanic for overhauling.
I find it amazing that no one has mentioned the PLUG from the generator!
He states this “Electricity is Our Enemy, if you give it a chance to kill you, Remember, they will never miss it. Please read all caution and instruction while doing this practical tutorial.” – YET
If the generator is running and the plug in your hand and not connected, you are going to be injured or worse, killed.
You CANNOT assume that people will “plug it in” prior to the generator being started. Humans will either forget or not read it fully.
A far “safer” way, if there is one looking at the diagrams and comments from others (which I in general agree with where changeovers are mentioned) is to have the plug and socket termination wired as a fixed item to a fused Isolator at the appropriate amperage for the size of the load.
The lead, which should also be sized for the load demand, can then have a plug on that will and be connected to the socket of the generator, therefore, no live ends.
You’re going to kill somebody!
Hi John,
I normally run an extension lead, of suitable current rating and fitted with male and female plugs, from generator to the switchboard where it plugs into an inlet socket similar to the type used on caravans. There is no way to get a shock from the lead. The inlet socket has 3 male pins and if wired to the proper changeover switch/relay is impossible to become live at the input pins. I would not put a changeover switch between a meter and the main switch but rather go from meter to main switch then to the changeover with maybe some protection inline with a MCB.
Thnx for sharing good and useful electrical information
I have only done 2 methods to use backup power (generator set)
1st method: use a 1-0-2 switch where 1 is concessionary power and 2 is backup power and the power change is done manually.
2nd method: I made an automatic electric command based on mini plc and contactors where the coils interlock and time the start of the generator set and backup power when the concessionary power cut occurs..
I think these are the 2 safe methods